EPSITRON ® ECO power supply; single-phase; 24 VDC; 1.25 A; DIN and chassis mount options

110V/24VDC 1.25AMP POWER SUPPL

WGO7871702 7871702 WGO7871702
28.90 / EA
http://schema.org/OutOfStock
  • Conductor Size: 12 AWG, 2.5 mm
  • Country of Origin: China
  • Height: 3.543 in, 90 mm
  • Mounting Type: DIN-35 Rail, Screw Mount
  • Package Type: Box
  • Strip Length: 0.28 in, 7 mm
  • Weight: 257.000 g
  • Width: 1.181 in, 30 mm
QTY
  • Features
  • Specifications
  • Approvals
    • Brjansker Zertifizierungsstelle, EAC, EAC RU C-DE.AM02.B.00089_19, TP TC 004/2011
    • Underwriters Laboratories Inc., UL, E255815, UL 60950-1
    • Brjansker Zertifizierungsstelle, EAC, EAC RU C-DE.AM02.B.00089_19, TP TC 020/2011
    • Underwriters Laboratories Inc., UL, E255817, UL 508
  • Features
    • Switched-mode power supply
    • Natural convection cooling when horizontally mounted
    • Encapsulated for use in control cabinets
    • Suitable for both parallel and series operation
    • Electrically isolated output voltage (SELV) per EN 60335-1 and UL 60950-1; PELV per EN 60204
    • DIN-35 rail mountable in different positions
    • Direct installation on mounting plate via cable grip
  • Safety And Protection
    • Isolation voltage (pri.-sec.) : DC 4.242 kV
    • Isolation voltage (pri.-PE) : DC 2.2 kV
    • Isolation voltage (sec.-PE) : DC 0.7 kV
    • Protection class : I
    • Protection type : IP20; per EN 60529
    • Resistance to reverse feed : ≤ DC 30 V
    • Overvoltage category : II
    • Pollution degree : 2
    • Transient suppression (primary) : Varistor
    • Short-circuit-protected : Yes
    • Open-circuit-proof : Yes
    • Parallel operation : Yes
    • Series operation : Yes, for 2 devices of the same type
    • MTBF : > 300,000 h (per IEC 61709)
  • Environmental Requirements
    • Ambient temperature (operation) : -20 … +60 °C
    • Ambient temperature (storage) : -25 … +75 °C
    • Relative humidity : 10 … 95 % (no condensation permissible)
    • Derating : -4 %/K (> 45 °C)
  • Connection Data
    • Connection type 1 : Input/output
    • Connection technology : CAGE CLAMP®
    • WAGO connector : WAGO 236 Series
    • Solid conductor : 0.08 … 2.5 mm² / 28 … 12 AWG
    • Fine-stranded conductor : 0.08 … 2.5 mm² / 28 … 12 AWG
    • Strip length : 6 … 7 mm / 0.24 … 0.28 inches
    • Note (conductor cross-section) : 12 AWG: THHN, THWN
  • Signaling And Communication
    • Signaling : 1 x LED DC OK (green)
    • Operation status indicator : Green LED (Uo)
  • Physical Data
    • Width : 30 mm / 1.181 inches
    • Height : 90 mm / 3.543 inches
    • Depth from upper-edge of DIN-rail : 99 mm / 3.898 inches
  • Material Data
    • Fire load : 0.129 MJ
    • Weight : 257.000 g
  • Input
    • Phases : 1
    • Nominal input voltage Ui nom : 1 x AC 100 … 240 V
    • Input voltage range : 1 x AC 90 … 264 V; DC 125 … 375 V
    • Nominal mains frequency range : 47 … 63 Hz; 0 Hz
    • Input current Ii : ≤ 0.3 A (230 VAC); ≤ 0.6 A (115 VAC)
    • Discharge current : ≤ 1.5 mA
    • Inrush current : ≤ 18 A
    • Power factor correction (PFC) : Passive
    • Mains failure hold-up time : ≥ 10 ms (230 VAC)
  • Output
    • Nominal output voltage Uo nom : DC 24 V (SELV)
    • Output voltage range : DC 22 … 26 V (adjustable)
    • Default setting : DC 24 V
    • Nominal output current Io nom : 1.25 A (24 VDC; 110 … 240 VAC); 1 A (24 VDC; 100 … 240 VAC)
    • Nominal output power : 30 W
    • Deviation : ≤ 1 %
    • Residual ripple : ≤ 200 mV (peak-to-peak)
    • Overload behavior : Constant power (in overload range: 1.05 … 1.4 x Io nom); Shutdown and automatic restart in the event of a short circuit
  • Standards And Specifications
    • Conformity marking : CE
    • Standards/specifications : EN 61204-3 || EN 60335-1 || EN 62368-1 || UL 60950-1 || UL 508 || SEMI F47
  • Mechanical Data
    • Mounting type : DIN-35 rail || Screw mount
  • Specifications
    • Product Group Code : 0006
  • Commercial Data
    • Packaging type : Box
    • Country of origin : CN
    • GTIN : 4055143372459
    • Customs tariff number : 85044083900
  • Efficiency/Power Losses
    • Power loss Pl : ≤ 6 W (230 VAC; 24 VDC; 1.25 A)
    • Efficiency (typ.) : 87 % (230 VAC; 1.25 ADC)
  • Circuit Protection
    • Internal fuse : F 1 A / 250 VAC
    • Backup fusing (required) : An external DC fuse is required for the DC input voltage.
    • Backup fusing (recommended) : Circuit breaker: B6, B10