Modular discovery packs, Zelio Logic, smart relay discovery pack, 10 I/O, 24 V DC

Modular discovery packs, Zelio Logic, smart relay discovery pack, 10 I/O, 24 V DC

SQDSR3PACKBD SR3PACKBD 785901571858
332.10 / EACH
  • Certifications: CSA, C-tick, GL, GOST, UL
  • Net Weight: 0.7 kg
  • Number of Outputs: 4
  • Operating Temperature: -20-40 °C In Non-ventilated Enclosure IEC 60068-2-1 And IEC 60068-2-2 || -20-55 °C IEC 60068-2-1 And IEC 60068-2-2
  • Standard: EN/IEC 60068-2-27 Ea, EN/IEC 60068-2-6 Fc, EN/IEC 61000-4-11, EN/IEC 61000-4-12, EN/IEC 61000-4-2 Level 3, EN/IEC 61000-4-3, EN/IEC 61000-4-4 Level 3, EN/IEC 61000-4-5, EN/IEC 61000-4-6 Level 3
  • Storage Temperature: -40-70 °C
  • Warranty Length: 18 mth
This Schneider Electric Zelio Logic SR3 discovery pack compact smart relay / programmable controller uses a supply voltage of 24 volts direct current, has 10 inputs / outputs with screw-clamp terminals and has an integrated LCD display. This compact programmable relay discovery pack is ideal for discovering the Zelio Logic range of programmable smart relays. It has compact form-factor, allowing installation on DIN rail. It also offers simple programming, display and diagnosing of malfunctions display and navigation buttons. Discovery package includes one copy of Zelio Soft and one USB cable to connect the relay to your PC. Simple ladder programming, adapted for non-specialists. Discovery package, coming with Zelio Soft programming software, the simplest way to learn and use this relay. Built-in EEPROM flash memory for data backup up to 10 years, easy-to-recover after a power shortage or incident.
  • Specifications
  • Checks : program memory on each power up
  • Output Voltage Limits : 24...250 V AC relay output) || 5...30 V DC relay output)
  • Range Of Product : Zelio Logic
  • Analogue Input Resolution : 8 bits
  • Clock : with
  • Number Or Control Scheme Lines : 120-120 ladder || 0-200 FBD
  • Relative Humidity : 95-95 % without condensation or dripping water
  • Ambient Air Temperature For Operation : -20-40 °C in non-ventilated enclosure IEC 60068-2-1 and IEC 60068-2-2 || -20-55 °C IEC 60068-2-1 and IEC 60068-2-2
  • Ip Degree Of Protection : IP20 IEC 60529 terminal block) || IP40 IEC 60529 front panel)
  • Input/Output Number : 10
  • Conversion Time : smart relay cycle time analogue input circuit
  • Maximum Altitude Transport : 3048 m
  • Conversion Error : +/- 5 % 25 °C analogue input circuit || +/- 6.2 % 55 °C analogue input circuit
  • Ambient Air Temperature For Storage : -40-70 °C
  • Net Weight : 0.7 kg
  • Discrete Input Voltage : 24 V DC
  • Operating Rate In Hz : 0.1 Hz at Ie)relay output || 10 Hz no load)relay output
  • Discrete Input Type : resistive
  • Product Certifications : GL || UL || CSA || GOST || C-tick
  • Tightening Torque : 0.5 N.m
  • Warranty : 18 months
  • Current State 1 Guaranteed : >= 1.2 mA IB...IG used as discrete input circuit) || >= 2.2 mA I1...IA and IH...IR discrete input circuit)
  • Pollution Degree : 2 EN/IEC 61131-2
  • Input Compatibility : 3-wire proximity sensors PNP discrete input
  • Connections - Terminals : screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) semi-solid || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 25...AWG 14) solid || screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) solid || screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end
  • Maximum Permissible Voltage : 30 V analogue input circuit
  • Backup Time : 10 years 25 °C
  • Immunity To Microbreaks : 1 ms
  • Kit Composition : Zelio Soft 2 programming software CD-ROM || cable PC SR2USB01 for connection to PC || SR3B101BD
  • Counting Frequency : 1 kHz discrete input
  • Environmental Characteristic : EMC directive EN/IEC 61000-6-2 || EMC directive EN/IEC 61000-6-3 || EMC directive EN/IEC 61000-6-4 || EMC directive EN/IEC 61131-2 zone B || low voltage directive EN/IEC 61131-2
  • Response Time : 10 ms from state 0 to state 1)relay output || 5 ms from state 1 to state 0)relay output
  • Voltage State 0 Guaranteed : <= 5 V I1...IA and IH...IR discrete input circuit || <= 5 V IB...IG used as discrete input circuit || <= 5 V
  • Mechanical Durability : 10000000 cycles relay output
  • Reverse Polarity Protection : with
  • Operating Distance : 10 m between stations, with screened cable (sensor not isolated) analogue input circuit
  • Clock Drift : 12 min/year 0-55 °C || 6 s/month 25-25 °C
  • Standards : EN/IEC 60068-2-27 Ea || EN/IEC 60068-2-6 Fc || EN/IEC 61000-4-3 || EN/IEC 61000-4-6 level 3 || EN/IEC 61000-4-11 || EN/IEC 61000-4-5 || EN/IEC 61000-4-2 level 3 || EN/IEC 61000-4-12 || EN/IEC 61000-4-4 level 3
  • Voltage State 1 Guaranteed : >= 15 V I1...IA and IH...IR discrete input circuit || >= 15 V IB...IG used as discrete input circuit
  • Discrete Input Current : 4 mA
  • Repeat Accuracy : +/- 2 % 55 °C analogue input circuit
  • Number Of Outputs : 4 relay
  • Electrical Durability : AC-12 500000 cycles 230 V, 1.5 A relay output EN/IEC 60947-5-1 || AC-15 500000 cycles 230 V, 0.9 A relay output EN/IEC 60947-5-1 || DC-12 500000 cycles 24 V, 1.5 A relay output EN/IEC 60947-5-1 || DC-13 500000 cycles 24 V, 0.6 A relay output EN/IEC 60947-5-1
  • Analogue Input Range : 0...24 V || 0...10 V
  • Overvoltage Category : III EN/IEC 60664-1
  • [Uimp] Rated Impulse Withstand Voltage : 4 kVEN/IEC 60947-1 and EN/IEC 60664-1
  • Disturbance Radiated/Conducted : class B EN 55022-11 group 1
  • Input Impedance : 12 kOhm IB...IG used as analogue input circuit || 12 kOhm IB...IG used as discrete input circuit || 7.4 kOhm I1...IA and IH...IR discrete input circuit
  • Contacts Type And Composition : NO relay output
  • Power Dissipation In W : 3 W without extension || 8 W with extensions
  • Cycle Time : 6-90 ms
  • Lsb Value : 39 mV analogue input circuit
  • Discrete Input Number : 6 EN/IEC 61131-2 type 1
  • Local Display : with
  • [Us] Rated Supply Voltage : 24 V
  • Analogue Input Number : 4
  • Maximum Supply Current : 100 mA with extensions) || 100 mA without extension)
  • Switching Capacity In Ma : >= 10 mA 12 V relay output)
  • Output Thermal Current : 8 A for all 4 outputs relay output
  • Product Or Component Type : modular discovery packs
  • Operating Altitude : 6561.68 ft (2000 m)
  • Current State 0 Guaranteed : <= 0.5 mA IB...IG used as discrete input circuit) || <= 0.75 mA I1...IA and IH...IR discrete input circuit)
  • Analogue Input Type : common mode
  • Supply Voltage Limits : 19.2-30 V