SQUARE D

universal protection relay, PowerLogic P3U 3CT 1Io RINGLUG 4VT 8DI 16DO 48-230V DI24V 2RJ45 ANSI

universal protection relay, Po

SQDREL53000 REL53000 3606482171459
3728.77 / EA
http://schema.org/OutOfStock
  • Depth: 205 mm
  • Display Type: LCD 128 X 64 Pixels With Single Line Diagram
  • Number of Outputs: 8 DO, 1 Watchdog
  • Warranty Length: 10 yr, 2 yr
QTY
  • Specifications
  • Communications & Management Attributes
    • Communication Port Protocol : IEC 61850 ed. 1, IEC 61850 ed. 2, IEC 60870-5-101, DNP3 TCP, Modbus TCP, EtherNet/IP
    • Redundancy Communication Port Protocol : RSTP, PRP
  • Physical Attributes
    • Mounting Case Size : 30TE
  • Complementary Attributes
    • Integrated Connection Type : front USB port 1, rear RJ45 2
    • Us Rated Supply Voltage : 48...230 V AC/DC
  • Important Information Attributes
    • Control Type : switchgear control and monitoring, programmable switchgear interlocking, local control on single-line diagram, local control with I/O keys, local/remote control, 2 function keys, mobile application with Easergy SmartApp, web-server, programmable logic
    • Cybersecurity : password protection, port hardening
    • Electromagnetic Compatibility : emission tests IEC/EN 60255-26 ed. 3, emission tests CISPR 11, emission tests CISPR 22, EMC immunity IEC/EN 60255-26 ed. 3, EMC immunity EN/IEC 61000-4-18, EMC immunity level 4 EN/IEC 61000-4-2, EMC immunity level 3 EN/IEC 61000-4-3, EMC immunity level 4 EN/IEC 61000-4-4, EMC immunity level 3 EN/IEC 61000-4-5, EMC immunity level 3 EN/IEC 61000-4-6, EMC immunity EN/IEC 61000-4-8, EMC immunity level 5 EN/IEC 61000-4-9, EMC immunity EN/IEC 61000-4-29, EMC immunity EN/IEC 61000-4-11, EMC immunity EN/IEC 61000-4-17, EMC immunity IEC 60255-22-1, EMC immunity IEC 60255-22-2, EMC immunity IEC 60255-22-3, EMC immunity IEC 60255-22-4, EMC immunity IEC 60255-22-5, EMC immunity IEC 60255-22-6, EMC immunity IEC 60255-27, EMC immunity class III IEC 60255-5, EMC immunity EN/IEC 60255-1
    • Environmental Characteristic : exposure to dry heat Bb EN/IEC 60068-2-2, exposure to cold Ad EN/IEC 60068-2-1, exposure to damp heat in service Db EN/IEC 60068-2-30, exposure to damp heat in service Cab EN/IEC 60068-2-78
    • Local Signalling : 4 LEDs, 8 LEDs programmable
    • Mechanical Robustness : vibrations class II) IEC 60255-21-1, vibrationsFc IEC 60068-2-6, shocks class II) IEC 60255-21-2, shocksEa IEC 60068-2-27, seismic tests method A class II) IEC 60255-21-3
    • Monitoring Function : trip circuit supervision 74, circuit breaker monitoring, relay self-monitoring
    • Network And Machine Diagnosis Type : event recording, disturbance recording, tripping context
    • Number Of Sensors : 0 temperature sensor(s), 0 arc sensor(s)
    • Protection Type : switch ON to fault (SOTF) 50BF, programmable curve 99 8-8, phase overcurrent 50/51, directional phase overcurrent 67, earth fault overcurrent 50N/51N, directional earth fault 67N 8-8, transient earth fault 67NI, capacitor bank unbalance 51C, broken conductor 46 I2/I1, cold load pick-up 50N/51N, H2 detection 68H2, H5 detection 68H5, breaker failure 50BF, cold load pick-up 37P, switch ON to fault (SOTF) 37P, directional active underpower 37P, fault locator 21FL, recloser 79, phase undercurrent 37, excessive starting time, locked rotor 48/51LR, motor restart inhibition 66, capacitor overvoltage 59C, negative sequence overcurrent 46, overvoltage 59, undervoltage 27, positive sequence undervoltage 27P, earth fault overvoltage 59N, underfrequency 81/81N, rate of change of frequency 81R, synchro-check 25, lockout relay 86, CT supervision 60 8-8, VT supervision 60, programmable stages 99 8-8, programmable curve 68H2
    • Software Name : eSetup Easergy Pro virtual simulation test, Easergy SmartApp
    • Switchgear Diagnosis Type : CT supervision TCS, trip circuit supervision TCS
    • Type Of Measurement : voltage zero sequence, voltage positive sequence, voltage negative sequence, voltage ratio of negative and positive, short circuit fault reactance ratio of negative and positive, fault location voltage phasor diagram view, current phasor diagram view, current 2nd, 15th harmonics with THD, RMS voltage 2nd, 15th harmonics with THD, reactive power positive sequence, RMS reactive power zero sequence, apparent power positive sequence, RMS apparent power ratio of negative and positive, voltage interruption 2nd, 15th harmonics with THD, current 3-phase, current zero sequence, current positive sequence, current negative sequence, current ratio of negative and positive, voltage phase to earth, voltage phase to phase, short circuit fault reactance 2nd, 15th harmonics with THD, fault location current zero sequence, earth fault reactance ratio of negative and positive, frequency phase to earth, active power zero sequence, RMS active power positive sequence, reactive power negative sequence, RMS reactive power, apparent power, RMS apparent power, active energy, frequency phasor diagram view, reactive energy, cos φ, tan φ, power angle, power factor, condition monitoring CB wear 2nd, 15th harmonics with THD, voltage interruption
    • Connections Terminals : screw removable (digital input/output), pin removable (voltage transformer), ring lugs removable (current transformer)
    • Carbon Footprint Of The Distribution Phase A4 : 3.8985926996634443, 4 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 8 kg CO2 eq., 7.82537379006275
    • Carbon Footprint Of The Installation Phase A5 : 0.1507432854636962, 0.2 kg CO2 eq.
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 95 kg CO2 eq., 94.8654267903303
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 624 kg CO2 eq., 623.8010019422173
    • Local Data Status : Publishable
    • Local Publishable Date : 2024-02-10
    • Return Indicator : N
    • Stocking Flag : Y
    • Stock Policy : 2
    • Device Type : Relay, Control & Measurement - Protection relay
    • Serviceability : Yes
    • Traceability : Yes
    • Field Service Division : DPIBS
    • Average Life Duration : 15 year(s)
    • Legacy Weee Scope : In
    • Weee Product Category : 5
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI1706006_V2
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 2412
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : Yes
    • China Rohs Label : 5
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : No
    • Product Contributes To Saved And Avoided Emissions : No
    • Product Kit Identifier : N
    • Arc Flash Protection : no
    • Device Short Name : P3U30-6AAA1BCAB
    • Display Type : LCD 128 x 64 pixels with single line diagram
    • Mounting Mode : flush mounting
    • Number Of Key : 2 customizable
    • Operating Threshold : 24 V AC/DC
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Or Component Type : protection relay
    • Protective Treatment : conformal coating
    • Range Of Product : PowerLogic P3
    • Relay Application : universal
    • Returnability : No
    • Setting : 4
    • Single Line Diagram : 4 controlled + 8 displayed
    • Software Version : v6.3.0.1-4
    • Sustainable Packaging : No
    • Time Synchronisation Protocol : SNTP
    • Total Lifecycle Carbon Footprint : 731 kg CO2 eq.
    • Web Server : embedded HTTP server
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Warranty In Months : 24
    • Pep Code : ENVPEP1706006EN
    • Database Version : 2024-01
    • Pep Verification Date : 2025-07-11
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent external review
    • Data Source : extrapolated product
    • Functional Unit Description : Other switchgear and controlgear solutions mentioned in the scope (e.g. fuses TC32, all-or-nothing relays TC94, Measuring relays and protection equipment TC95), apply the general rules of PCR and mention in the accompanying report the functional unit, the reference product characteristics, the reference lifetime and the use scenario which are applied consistently with the relevant IEC technical standards.Protect distribution networks and medium voltage equipment like feeder and motor against faults, (short circuit,over load) 24h per day, for 10 years of continuous operations.
    • Functional Unit Quantity : 1
    • Functional Unit Unit : unit
    • Product Weight In G2 : 3792
    • Reference Lifetime In Y2 : 10
    • Energy Model Manufacturing A1 A3 2 : Electricity Mix; Low voltage; 2020; Latvia, LV
    • Energy Model Installation A5 2 : No energy used
    • Energy Model Use B6 2 : Electricity Mix; Low voltage; 2020; Asia Pacific, APAC
    • Energy Model End Of Life C1 C4 2 : Global, European and French datasets are used.
    • Recyclability Potential In 2 : 32
    • Offer Owner Code : 190781
    • Height Nominal : 169.5 mm
    • Width Nominal : 170 mm
  • Environment Attributes Main
    • Ambient Air Temperature For Operation : -40-65 °C, -40-65 °C, -40-65 °C, -40-65 °C
    • Ambient Air Temperature For Storage : -40-70 °C, -40-70 °C, -40-70 °C, -40-70 °C
    • Take Back : No
    • Recycled Metal Content At Cr Level : 0 %
    • China Rohs Regulation : X
    • Carbon Footprint : 730.5411385077375
    • Circularity Profile : ENVEOLI1706006_V2
    • Environmental Disclosure : ENVPEP1706006EN
    • Eu Rohs Directive : Compliant By Exemption
    • Ip Degree Of Protection : IP54 front IEC 60529
    • Operating Altitude : 6561.68 ft (2000 m)
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : No
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Relative Humidity : 0-95 %, without condensation
    • Pep Code : ENVPEP1706006EN
    • Pep Verification Date : 2025-07-11
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent external review
  • General Attributes
    • Product Or Component Type : protection relay
    • Range Of Product : PowerLogic P3
  • Output Attributes
    • Number Of Outputs : 8 DO, 1 watchdog
    • Analogue Output Number : 0
  • Contractual Warranty Attributes
    • Warranty Period : up to 10 years (Standard warranty 2 years. Please check with your local SE representative for extended warranty availability and conditions)
    • Warranty : up to 10 years (Standard warranty 2 years. Please check with your local SE representative for extended warranty availability and conditions)
  • Input Attributes
    • Input Type : 3 1/5 A CT phase current, 1 1/5 A CT residual current, 4 100 V/110 V VT voltage
    • Analogue Input Number : 0
    • Digital Input Number : 16
  • Specifications
    • Country of Origin : Germany, Latvia, United States
    • Depth : 205 mm