                                        Certifications:
                                        
CSA, GOST, UL
                                        
                                    
 
                                    - 
                                        Depth:
                                        
67.5 mm
                                        
                                    
 
                                    - 
                                        Height:
                                        
67.5 mm
                                        
                                    
 
                                    - 
                                        Net Weight:
                                        
0.172 kg
                                        
                                    
 
                                    - 
                                        Standard:
                                        
IEC 60255-6, IEC 60947
                                        
                                    
 
                                    - 
                                        Storage Temperature:
                                        
-30-80 °C
                                        
                                    
 
                                    - 
                                        Warranty Length:
                                        
18 mth
                                        
                                    
 
                                    - 
                                        Width:
                                        
45 mm
                                        
                                    
 
                            
                        TeSys LR97D electronic overcurrent relay, 1.5A/690V, to be supplied with 24V AC/DC, for protection of motors with a rated current 0.3-1.3A. It provides 3 dials to adjust the protection, LOAD (0.3-1.5A) for the overcurrent level, O-TIME (0.3-10sec) for the acceptable duration of the overcurrent, D-TIME (0.5-30sec) for the starting duration. In addition, the device trips when the current is higher than 3 x LOAD during more than 0.5sec in steady state and if there is a missing phase during more than 3sec. The settings include selectors for 1-phase/3-phase motors and manual/automatic reset, and the device has a reset button, a test/stop button, 2 LED indicators (Run/Trip), 2 auxiliary contacts 1NO/NC for fault signalling. Settings can be locked by sealing the transparent cover. For direct attachement to the bottom terminals of a 3-pole contactor LC1D09-D38, with screw clamp terminals on bottom, the separate mounting from the contactor is possible using the terminal block LAD7B106 (to be ordered separately). Multi-standards certified (IEC, UL, CSA, CCC, EAC), compliant RoHs/Reach.