variable speed drive, Altivar Process ATV600, ATV630, cabinet Integration, IP20, 22kW, 380...480V, for US

ATV630 CAB.INT. 460V 30 HP

SQDATV630D22N4ZU ATV630D22N4ZU 3606489739942
3468.77 / EA
http://schema.org/OutOfStock
  • Connection Type: RJ45 On The Remote Graphic Terminal)Ethernet/Modbus TCP, RJ45 On The Remote Graphic Terminal)Modbus Serial
  • Country of Origin: India
  • Depth: 225.5 mm
  • Height: 480 mm
  • IsSustainable: Yes
  • Net Weight: 13.7 kg
  • Operating Position: Vertical +/- 10 Degree
  • Weight: 13.7 kg
  • Width: 195 mm
QTY
  • Features
  • Specifications
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Environmental data
    • Product Contributes To Saved And Avoided Emissions : Yes
    • Mercury Free : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Minimum Percentage Of Recycled Plastic Content : 0
    • Take-Back : No
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 20626
    • Rohs Exemption Information : Yes
    • Environmental Disclosure : ENVPEP2007011EN
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI2007011EN
    • Eu Rohs Directive : Pro-active compliance (Product out of EU RoHS legal scope)
  • Environment
    • Product Certifications : ATEX zone 2/22 || CSA || TÜV || DNV-GL || UL || ATEX INERIS
    • Maximum Deflection Under Vibratory Load (During Operation) : 1.5 mm at 2...13 Hz
    • Standards : UL 508C || IEC 61800-3 || IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
    • Insulation Resistance : > 1 MOhm 500 V DC for 1 minute to earth
    • Shock Resistance : 15 gn 11 ms IEC 60068-2-27
    • Vibration Resistance : 1.5 mm peak to peak (f= 2-13 Hz) conforming to IEC 60068-2-6 || 1 gn (f= 13-200 Hz) conforming to IEC 60068-2-6
    • Regulation Loop : adjustable PID regulator
    • Permitted Relative Humidity (During Operation) : class 3K5 according to EN 60721-3
    • Operating Altitude : <= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
    • Overvoltage Category : III
    • Environmental Class (During Operation) : class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3
    • Maximum Acceleration Under Shock Impact (During Operation) : 150 m/s² at 11 ms
    • Electromagnetic Compatibility : electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 || conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
    • Ambient Air Temperature For Operation : -15-50 °C (without derating) || 50-60 °C (with derating factor)
    • Volume Of Cooling Air : 215 m3/h
    • Marking : CE
    • Maximum Acceleration Under Vibrational Stress (During Operation) : 10 m/s² at 13...200 Hz
    • Pollution Degree : 2 IEC 61800-5-1
    • Noise Level : 59.5 dB
    • Ambient Air Temperature For Storage : -40-70 °C
    • Relative Humidity : 5-95 % without condensation IEC 60068-2-3
    • Assembly Style : with heat sink
    • Operating Position : vertical +/- 10 degree
    • Maximum Thdi : <48 % from 80...100 % of load IEC 61000-3-12
    • Ambient Air Transport Temperature : -40-70 °C
  • Specifications
    • Country of Origin : India
    • Width : 195 mm
    • Height : 480 mm
    • Weight : 13.7 kg
    • Product Destination : asynchronous motors || synchronous motors
    • Line Current : 39.6 A 380 V normal duty) || 34.4 A 480 V normal duty) || 34.1 A 380 V heavy duty) || 29.9 A 480 V heavy duty)
    • Emc Filter : integrated 10 m IEC 61800-3 category C2 || integrated 50 m IEC 61800-3 category C3 || with EMC plate option
    • Variant : standard version
    • Product Or Component Type : variable speed drive
    • Relative Symmetric Network Frequency Tolerance : 5 %
    • Relative Symmetric Mains Voltage Tolerance : 10 %
    • Communication Port Protocol : Modbus TCP || Ethernet || Modbus serial
    • Nominal Output Current : 46.3 A
    • Product Specific Application : process and utilities
    • Safety Function : STO (safe torque off) SIL 3
    • Maximum Horse Power Rating : 30 hp normal duty || 25 hp heavy duty
    • Supply Frequency : 50...60 Hz - 5...5 %
    • Option Card : slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A communication module, CANopen SUB-D 9 || slot A communication module, CANopen screw terminals || slot A/slot B digital and analog I/O extension module || slot A/slot B output relay extension module || slot A communication module, Ethernet IP/Modbus TCP/MD-Link || communication module, BACnet MS/TP || communication module, Ethernet Powerlink
    • Range Of Product : Altivar Process ATV600
    • Speed Drive Output Frequency : 0.1-500 Hz
    • Ip Degree Of Protection : IP20IEC 61800-5-1 || IP20IEC 60529
    • Motor Power Kw : 22 kW normal duty) || 18.5 kW heavy duty)
    • [Us] Rated Supply Voltage : 380...480 V - 15...10 %
    • Mounting Mode : cabinet mount
    • Type Of Cooling : forced convection
    • Continuous Output Current : 46.3 A 4 kHz normal duty || 39.2 A 4 kHz heavy duty
    • Device Short Name : ATV630
  • Complementary
    • Prospective Line Isc : 50 kA
    • Network Frequency : 50-60 Hz
    • Power Dissipation In W : natural convection 68 W 380 V 4 kHz || forced convection 505 W 380 V 4 kHz
    • Analogue Output Type : software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
    • Discrete Output Type : relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V DC 5000 mA
    • Asynchronous Motor Control Profile : optimized torque mode || constant torque standard || variable torque standard
    • Maximum Switching Current : relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
    • 4 Quadrant Operation Possible : false
    • Exchange Mode : half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
    • Apparent Power : 28.6 kVA 480 V normal duty) || 24.9 kVA 480 V heavy duty)
    • Power Range : 15-25 kW 380-440 V 3 phase || 15-25 kW 480-500 V 3 phase
    • Phase : 3 phase
    • Net Weight : 13.7 kg
    • With Safety Function Safe Direction (Sdi) : false
    • Type Of Polarization : no impedance
    • Frequency Resolution : display unit 0.1 Hz || analog input 0.012/50 Hz
    • Relay Output Type : configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
    • Switching Frequency : 2...12 kHz adjustable || 4...12 kHz with derating factor
    • Maximum Transient Current : 50.9 A 60 s normal duty) || 58.8 A 60 s heavy duty)
    • Analogue Input Number : 3
    • Motor Slip Compensation : adjustable || not available in permanent magnet motor law || automatic whatever the load || can be suppressed
    • Discrete Output Number : 0
    • With Safety Function Safe Position (Sp) : false
    • Method Of Access : slave Modbus TCP
    • With Safety Function Safely Limited Position (Slp) : false
    • With Safety Function Safe Operating Stop (Sos) : false
    • Discrete Input Number : 8
    • Local Signalling : for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
    • Linearity Error : AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
    • Number Of Addresses : 1-247 Modbus serial
    • With Sft Fct Safe Stop 2 (Ss2) : false
    • With Safety Function Safe Stop 1 (Ss1) : false
    • Width : 195 mm
    • Transmission Rate : 10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
    • Depth : 225.5 mm
    • Analogue Input Type : AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
    • Discrete And Process Manufacturing : building - HVAC compressor centrifugal || food and beverage processing other application || mining mineral and metal fan || mining mineral and metal pump || oil and gas fan || water and waste water other application || building - HVAC screw compressor || food and beverage processing pump || food and beverage processing fan || food and beverage processing atomization || oil and gas electro submersible pump (ESP) || oil and gas water injection pump || oil and gas jet fuel pump || oil and gas compressor for refinery || water and waste water centrifuge pump || water and waste water positive displacement pump || water and waste water electro submersible pump (ESP) || water and waste water screw pump || water and waste water lobe compressor || water and waste water screw compressor || water and waste water compressor centrifugal || water and waste water fan || water and waste water conveyor || water and waste water mixer
    • Sampling Duration : 2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
    • Electrical Connection : control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || motor screw terminal 16 mm² AWG 6 || line side screw terminal 10...16 mm² AWG 8...AWG 6
    • Maximum Output Frequency : 500 kHz
    • With Safety Function Safe Brake Management (Sbc/Sbt) : false
    • Height : 480 mm
    • Acceleration And Deceleration Ramps : linear adjustable separately from 0.01...9999 s
    • Maximum Output Voltage : 480.0 V
    • Base Load Current At High Overload : 39.2 A
    • Transmission Frame : RTU
    • With Safety Function Safe Speed Monitor (Ssm) : false
    • Relay Output Number : 3
    • With Safety Function Safe Torque Off (Sto) : true
    • Data Format : 8 bits, configurable odd, even or no parity
    • Base Load Current At Low Overload : 46.3 A
    • Accuracy : +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
    • Connector Type : RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
    • Input Compatibility : DI1...DI6 discrete input level 1 PLC IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
    • Permissible Temporary Current Boost : 1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
    • Analogue Output Number : 2
    • Physical Interface : Ethernet || 2-wire RS 485
    • Minimum Switching Current : relay output R1, R2, R3 5 mA 24 V DC
    • Discrete Input Logic : 16 preset speeds
    • Refresh Time : relay output R1, R2, R3)5 ms +/- 0.5 ms)
    • Enclosure Mounting : with heat sink
    • Isolation : between power and control terminals
    • With Safety Function Safe Programmable Logic : false
    • Brake Chopper Integrated : false
    • Output Voltage : <= power supply voltage
    • Nominal Switching Frequency : 4 kHz
    • Quantity Per Set : 1
    • Braking To Standstill : by DC injection
    • Discrete Input Type : DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
    • Protection Type : thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-circuit protection drive || motor phase break drive || overvoltages on the DC bus drive || line supply overvoltage drive || line supply undervoltage drive || line supply phase loss drive || overspeed drive || break on the control circuit drive
    • Supply : external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection
    • With Safety Function Safely Limited Speed (Sls) : false
    • Synchronous Motor Control Profile : permanent magnet motor || synchronous reluctance motor