TeSys Deca thermal overload relays , 17...25A , class 10A

BIMETALLIC OVERLOAD RELAY 600V

SQDLRD3322 LRD3322 3389110519822
211.81 / EA
http://schema.org/OutOfStock
  • Country of Origin: France
  • Depth: 115 mm
  • Dielectric Strength: 2.2 kV, 50 Hz
  • Height: 81 mm
  • Net Weight: 0.51 kg
  • Warranty Length: 18 mth
  • Weight: 0.51 kg
  • Width: 70 mm
LRD3322 is a TeSys LRD thermal overload relay from Schneider Electric to be used with a TeSys D contactor. It protects motors 9-11kW@400V thanks to a thermal range 17-25A, a tripping class 10A and phase unbalance protection. LRD3322 is a TeSys LRD thermal overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a thermal setting range 17-25A, a tripping class 10A and phase unbalance detection, it protects motors 11kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine). Thermal overload protection relay, bimetallic type, with phase unbalance protection (differential). Direct mounting on the bottom terminals of a Tesys contactor LC1D80 and D95 to form a compact starter. Light and compact, 70mm wide. Temperature compensated for a good accuracy of the protection. Manual control with test & reset buttons, manual / automatic reset selector. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. Can be completed with terminal blocks for separate mounting (LAD7B, LAD96) and remote control devices (LAD703, LA7D03).
QTY
  • Product Description
  • Features
  • Specifications
LRD3322 is a TeSys LRD thermal overload relay from Schneider Electric to be used with a TeSys D contactor. It protects motors 9-11kW@400V thanks to a thermal range 17-25A, a tripping class 10A and phase unbalance protection. LRD3322 is a TeSys LRD thermal overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a thermal setting range 17-25A, a tripping class 10A and phase unbalance detection, it protects motors 11kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine). Thermal overload protection relay, bimetallic type, with phase unbalance protection (differential). Direct mounting on the bottom terminals of a Tesys contactor LC1D80 and D95 to form a compact starter. Light and compact, 70mm wide. Temperature compensated for a good accuracy of the protection. Manual control with test & reset buttons, manual / automatic reset selector. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. Can be completed with terminal blocks for separate mounting (LAD7B, LAD96) and remote control devices (LAD703, LA7D03).
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Product Certifications : IEC || UL || CSA || CCC || EAC || ATEX INERIS || UKCA
    • Mechanical Robustness : vibrations6 Gn IEC 60068-2-6 || shocks15 Gn for 11 ms IEC 60068-2-7
    • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || UL 60947-5-1 || CSA C22.2 No 60947-4-1 || CSA C22.2 No 60947-5-1 || GB/T 14048.4 || GB/T 14048.5 || EN 50495
    • Climatic Withstand : IACS E10
    • Ambient Air Temperature For Operation : -20-60 °C without derating IEC 60947-4-1
    • Dielectric Strength : 2.2 kV 50 Hz IEC 60947-1
    • Ip Degree Of Protection : IP20 conforming to IEC 60529
    • Flame Retardance : V1 conforming to UL 94
    • Ambient Air Temperature For Storage : -60-70 °C
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP110101EN
    • Packaging Without Single Use Plastic : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI1101001
    • Take-Back : No
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 5.5372755241
  • Complementary
    • Network Frequency : 0...400 Hz
    • Height : 81 mm
    • [Ith] Conventional Free Air Thermal Current : 5 A signalling circuit
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • Connections - Terminals : power circuit screw clamp terminals 1 4-35 mm² flexible without cable end || power circuit screw clamp terminals 1 4-35 mm² flexible with cable end || power circuit screw clamp terminals 1 4-35 mm² solid without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible without cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm² solid without cable end
    • Phase Failure Sensitivity : tripping current 130 % of Ir on two phase, the last one at 0
    • [Ue] Rated Operational Voltage : 1000 V AC 0...400 Hz power circuit IEC 60947-4-1
    • Associated Fuse Rating : 4 A gG for signalling circuit || 4 A BS for signalling circuit
    • Net Weight : 0.51 kg
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947-1
    • Permissible Current : 0.72 A 500 V AC-15 signalling circuit || 0.06 A 440 V DC-13 signalling circuit
    • Tripping Threshold : 1.14 +/- 0.06 Ir IEC 60947-4-1
    • Tightening Torque : control circuit 1.7 N.m screw clamp terminals || power circuit 9 N.m screw clamp terminals
    • Control Type : Red push-button stop || Blue push-button reset
    • Mounting Support : plate, with specific accessories || rail, with specific accessories || under contactor
    • Width : 70 mm
    • Depth : 115 mm
    • Temperature Compensation : -20-60 °C
  • Specifications
    • Country of Origin : France
    • Width : 70 mm
    • Height : 81 mm
    • Weight : 0.51 kg
    • Network Type : DC || AC
    • Thermal Protection Adjustment Range : 17-25 A
    • Relay Application : motor protection
    • Product Or Component Type : differential thermal overload relay
    • Product Name : TeSys LRD || TeSys Deca
    • Thermal Overload Class : class 10A IEC 60947-4-1
    • Range : TeSys
    • [Ui] Rated Insulation Voltage : power circuit 1000 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL
    • Product Compatibility : LC1D80 || LC1D95
    • Device Short Name : LRD