TeSys GV2 Manual Starter and Protector, thermal magnetic circuit protector, toggle switch, 0.40…0.63 A, screw clamp terminals

MANUAL STARTER 600VAC 0.63AMP

SQDGV2RT04 GV2RT04 3389110520606
189.18 / EA
http://schema.org/OutOfStock
  • Depth: 78.5 mm
  • Warranty Length: 18 mth
TeSys GV motor circuit breaker, 3 poles (3P), 0.63A/690V, for high starting current peak motor applications 0.12-0.18kW@400V. It provides a thermal-magnetic protection with a thermal setting range 0.40-0.63A, a magnetic tripping level at 20xIn, high breaking capacity Icu 100kA. Connection by screw clamp terminals. Start-stop control by toggle guaranteed for 100 000 cycles AC-3. It can be used for protection of 3-phase transformer applications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine).
QTY
  • Product Description
  • Features
  • Specifications
TeSys GV motor circuit breaker, 3 poles (3P), 0.63A/690V, for high starting current peak motor applications 0.12-0.18kW@400V. It provides a thermal-magnetic protection with a thermal setting range 0.40-0.63A, a magnetic tripping level at 20xIn, high breaking capacity Icu 100kA. Connection by screw clamp terminals. Start-stop control by toggle guaranteed for 100 000 cycles AC-3. It can be used for protection of 3-phase transformer applications. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine).
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Complementary Attributes
    • Line Rated Current : 0.63 A
    • Maximum Operating Rate : 25 cyc/h
    • Rated Duty : uninterrupted IEC 60947-4-1
    • Ue Rated Operational Voltage : 690 V AC 50/60 Hz IEC 60947-2
    • Ui Rated Insulation Voltage : 690 V AC 50/60 Hz IEC 60947-2
    • Uimp Rated Impulse Withstand Voltage : 6 kV IEC 60947-2
  • Important Information Attributes
    • Persona Type Ids : EU, LC, OM, OM8, PB, SC
    • Persona Type Names : End User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder, Electrician
    • Market Segmentation Id : COMMERCIAL, INDUSTRIAL
    • Market Segmentation : Commercial, Industrial
    • Control Type : toggle
    • Device Application : motor protection, transformer
    • Electrical Durability : 100000 cycles AC-3 415 V In, 100000 cycles AC-3e 415 V In
    • Fixing Mode : 35 mm symmetrical DIN rail clipped, panel screwed with adaptor plate)
    • Mechanical Robustness : shocks 30 Gn for 11 ms, vibrations 5 Gn, 5...150 Hz
    • Motor Power Kw : 0.12-0.12 kW 400/415 V AC 50/60 Hz motor protection high peak current, 0.18-0.18 kW 400/415 V AC 50/60 Hz motor protection high peak current, 0.18-0.18 kW 440 V AC 50/60 Hz motor protection high peak current, 0.37-0.37 kW 690 V AC 50/60 Hz motor protection high peak current
    • Mounting Position : horizontal, vertical
    • Poles Description : 3P
    • Product Or Component Type : motor circuit breaker
    • Range : TeSys Deca
    • Range Of Product : TeSys GV2, TeSys Deca
    • Tightening Torque : 1.7 N.m screw clamp terminal
    • Trip Unit Technology : thermal-magnetic
    • Utilisation Category : category A IEC 60947-2, AC-3 IEC 60947-4-1, AC-3e IEC 60947-4-1
    • Connections Terminals : power circuit: screw clamp terminal 2 cable(s) 1-6 mm² - solid, power circuit: screw clamp terminal 2 cable(s) 1.5-6 mm² - flexible without cable end, power circuit: screw clamp terminal 2 cable(s) 1-4 mm² - flexible with cable end
    • Carbon Footprint Of The Distribution Phase A4 : 0.10422048542264055, 0.1 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 0.5730413800864925, 0.6 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase A5 : 0.1 kg CO2 eq., 0.05212458121202044
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 2 kg CO2 eq., 2.069590396794914
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 9 kg CO2 eq., 8.86395212531129
    • Certificate Agency : CCC, UL, CSA, EAC, LROS (Lloyds register of shipping), BV, UKCA
    • Local Data Status : Publishable
    • Local Publishable Date : 2026-02-25
    • Return Indicator : N
    • Stocking Flag : Y
    • Stock Policy : 1
    • Device Type : LV equipment - Low voltage circuit breaker
    • Serviceability : No
    • Traceability : No
    • Field Service Division : PPIBS
    • Average Life Duration : 15 year(s)
    • Weee Scope : In
    • Weee Product Category : 5
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI121004
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 2538
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : No
    • China Rohs Label : 3
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Tier Id : 1
    • Tier : 1
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Product Kit Identifier : N
    • Compatibility Code : GV2RT
    • Device Short Name : GV2RT
    • Fire Resistance : 960 °C IEC 60695-2-11
    • Magnetic Tripping Current : 13-13 A
    • Mechanical Durability : 100000 cycles
    • Network Frequency : 50/60 Hz IEC 60947-2
    • Network Type : AC
    • Power Dissipation Per Pole : 2.5 W
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Name : TeSys GV2
    • Returnability : No
    • Software Version : v6.2.4
    • Suitability For Isolation : yes IEC 60947-1
    • Sustainable Packaging : Yes
    • Thermal Protection Adjustment Range : 0.4-0.63 A IEC 60947-2
    • Total Lifecycle Carbon Footprint : 12 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Ith Conventional Free Air Thermal Current : 0.63 A IEC 60947-2
    • Warranty In Months : 18
    • R Thermal Protection Adj Range 3 : 0.4-0.63 A
    • Pep Code : ENVPEP1210004EN
    • Database Version : 2024-01
    • Pep Verification Date : 2026-03-30
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed3-2023 06 06
    • Type Of Verification For The Pep : Independent internal review
    • Data Source : extrapolated product
    • Functional-unit Description : Protect the installation from overloads and short circuits in a circuit with rated voltage Ue, rated current In, with Np poles, a rated breaking capacity Icu, and, if applicable, the specific specifications, in the Industrial application area, according to the appropriate use scenario, and during the reference service life of the product of 20 years.
    • Functional-unit Quantity : 1
    • Functional-unit Unit : unit
    • Reference Lifetime, In Y : 20
    • Energy Consumption On Product Lifetime, In Kwh : 98.55
    • Energy Model - Manufacturing [A1-a3] : Electricity Mix; Low voltage; 2020; France, FR
    • Energy Model - Installation [A5] : No energy used
    • Energy Model - Use [B6] : Electricity Mix; Low voltage; 2020; France, FR
    • Energy Model - End Of Life [C1-c4] : Global, European and French datasets are used.
    • Recyclability Potential, In % : 49
    • Offer Owner Code : 190788
    • Pn : 1
    • Height Nominal : 89 mm
    • Width Nominal : 45 mm
  • Environment Attributes Main
    • China Rohs Regulation : Product out of China RoHS scope , Product out of China RoHS scope. Substance declaration for your information.
    • Ambient Air Temperature For Storage : -40-80 °C, -40-80 °C
    • Take Back : No
    • Recycled Metal Content At Cr Level : 0 %
    • Mercury Free : Yes
    • Carbon Footprint : 11.662928968827357
    • Ambient Air Temperature For Operation : -20-60 °C-20-60 °C
    • Circularity Profile : ENVEOLI121004
    • Climatic Withstand : IACS E10
    • Environmental Disclosure : ENVPEP1210004EN
    • Eu Rohs Directive : Compliant By Exemption
    • Ip Degree Of Protection : IP20 IEC 60529
    • Operating Altitude : <= 6561.68 ft (2000 m)<= 6561.68 ft (2000 m)
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Pep Code : ENVPEP1210004EN
    • Pep Verification Date : 2026-03-30
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed3-2023 06 06
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : motor circuit breaker
    • Range Of Product : TeSys GV2, TeSys Deca
  • ETIM
    • ETIM 8 : EC000074
    • ETIM 9 : EC000074
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months
  • Specifications
    • Country of Origin : Brazil, France
    • Depth : 78.5 mm