IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 72VDC coil, open style

IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 72VDC coil, open style

SQDLC1D65A6SD LC1D65A6SD 338911940921
0.00 / EA
  • Certifications: CCC, CSA, GOST, UL
  • Contact Configuration: 3 NO
  • Contact Configuration: 1 NO + 1 NC
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 80 A 50 Hz Power Circuit
  • Net Weight: 0.935 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 72 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Complementary
    • Minimum Switching Current : 5 mA signalling circuit
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.75...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Signalling Circuit Frequency : 25...400 Hz
    • Inrush Power In W : 19-19 W 20 °C)
    • Hold-In Power Consumption In W : 7.4-7.4 W 20 °C
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Minimum Switching Voltage : 17 V signalling circuit
    • Time Constant : 34 ms
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Pollution Degree : 3
    • Maximum Width : 55 mm
    • Ambient Air Temperature For Storage : -60-80 °C
    • Protective Treatment : TH IEC 60068-2-30
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Flame Retardance : V1 conforming to UL 94
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Net Weight : 0.935 kg
    • Maximum Depth : 120 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Maximum Height : 122 mm
  • [Uc] Control Circuit Voltage : 72 V DC
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Product Or Component Type : contactor
  • Device Short Name : LC1D
  • Contactor Application : motor control || resistive load
  • [Icw] Rated Short-Time Withstand Current : 520 A 40 °C - 10 s power circuit || 900 A 40 °C - 1 s power circuit || 110 A 40 °C - 10 min power circuit || 260 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Tightening Torque : control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6
  • Pole Contact Composition : 3 NO
  • Utilisation Category : AC-1 || AC-4 || AC-3
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Electrical Durability : 0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V
  • Control Circuit Type : DC standard
  • Operating Time : 42.5...57.5 ms closing || 16...24 ms opening
  • Mechanical Durability : 10 Mcycles
  • Mounting Support : plate || rail
  • Range : TeSys
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 125 A gG <= 690 V type 1 power circuit || 125 A gG <= 690 V type 2 power circuit
  • Protective Cover : with
  • Power Dissipation Per Pole : 9.6 W AC-1 || 6.3 W AC-3
  • Rated Breaking Capacity : 1000 A 440 V power circuit IEC 60947
  • [Ie] Rated Operational Current : 80 A 60 °C) <= 440 V AC AC-1 power circuit || 65 A 60 °C) <= 440 V AC AC-3 power circuit
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Maximum Horse Power Rating : 40 hp 460/480 V at AC 50/60 Hz for 3 phase || 5 hp 115 V at AC 50/60 Hz for 1 phase || 10 hp 230/240 V at AC 50/60 Hz for 1 phase || 20 hp 200/208 V at AC 50/60 Hz for 3 phase || 20 hp 230/240 V at AC 50/60 Hz for 3 phase || 50 hp 575/600 V at AC 50/60 Hz for 3 phase
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Product Name : TeSys D
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1000 A 440 V power circuit IEC 60947
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 16.5 mm)
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Poles Description : 3P
  • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz power circuit
  • Product Certifications : UL || CCC || GOST || CSA
  • Motor Power Kw : 11 kW 400 V AC 50/60 Hz AC-4) || 18.5 kW 220...230 V AC 50/60 Hz AC-3) || 30 kW 380...400 V AC 50/60 Hz AC-3) || 37 kW 500 V AC 50/60 Hz AC-3) || 37 kW 660...690 V AC 50/60 Hz AC-3)
  • Overvoltage Category : III
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 80 A 60 °C power circuit
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Offer Sustainability
    • Toxic Heavy Metal Free : Yes
    • Environmental Disclosure : ENVPEP1503009EN
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Mercury Free : Yes
    • Rohs Exemption Information : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Reach Free Of Svhc : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Eu Rohs Directive : Compliant
    • Circularity Profile : ENVEOLI1503009EN