IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

SQDLC1D65A3BD LC1D65A3BD 785901772668
440.82 / EA
  • Certifications: CCC, CSA, GOST, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 80 A 50 Hz Power Circuit
  • Net Weight: 0.935 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • Environmental Disclosure : ENVPEP1503009EN
    • Sustainable Offer Status : Green Premium product
    • Circularity Profile : ENVEOLI1503009EN
    • Toxic Heavy Metal Free : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Pvc Free : Yes
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Eu Rohs Directive : Compliant
  • Contractual warranty
    • Warranty : 18 months
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1000 A 440 V power circuit IEC 60947
  • Utilisation Category : AC-3 || AC-1 || AC-4
  • Product Certifications : CSA || UL || GOST || CCC || UKCA
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • [Uc] Control Circuit Voltage : 24 V DC
  • Protective Cover : with
  • Electrical Durability : 0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V
  • Maximum Horse Power Rating : 40 hp 460/480 V at AC 50/60 Hz for 3 phase || 5 hp 115 V at AC 50/60 Hz for 1 phase || 10 hp 230/240 V at AC 50/60 Hz for 1 phase || 20 hp 200/208 V at AC 50/60 Hz for 3 phase || 20 hp 230/240 V at AC 50/60 Hz for 3 phase || 50 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Connections - Terminals : control circuit spring terminals 1 2.5-2.5 mm²flexible without cable end || control circuit spring terminals 2 2.5-2.5 mm²flexible without cable end || power circuit spring clamp terminal 1 1-35 mm²flexible without cable end || power circuit spring clamp terminal 2 1-25 mm²flexible without cable end || power circuit spring clamp terminal 1 1-35 mm²flexible with cable end || power circuit spring clamp terminal 2 1-25 mm²flexible with cable end || power circuit spring clamp terminal 1 1-35 mm²solid without cable end || power circuit spring clamp terminal 2 1-25 mm²solid without cable end
  • Product Or Component Type : contactor
  • Pole Contact Composition : 3 NO
  • Control Circuit Type : DC standard
  • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz power circuit
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 80 A 60 °C power circuit
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Range : TeSys
  • Mechanical Durability : 10 Mcycles
  • Rated Breaking Capacity : 1000 A 440 V power circuit IEC 60947
  • Poles Description : 3P
  • [Ie] Rated Operational Current : 80 A 60 °C) <= 440 V AC AC-1 power circuit || 65 A 60 °C) <= 440 V AC AC-3 power circuit
  • Motor Power Kw : 11 kW 400 V AC 50/60 Hz AC-4) || 18.5 kW 220...230 V AC 50/60 Hz AC-3) || 30 kW 380...400 V AC 50/60 Hz AC-3) || 37 kW 500 V AC 50/60 Hz AC-3) || 37 kW 660...690 V AC 50/60 Hz AC-3)
  • Mounting Support : rail || plate
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Device Short Name : LC1D
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 125 A gG <= 690 V type 1 power circuit || 125 A gG <= 690 V type 2 power circuit
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Contactor Application : motor control || resistive load
  • Product Name : TeSys D
  • Power Dissipation Per Pole : 9.6 W AC-1 || 6.3 W AC-3
  • [Icw] Rated Short-Time Withstand Current : 520 A 40 °C - 10 s power circuit || 900 A 40 °C - 1 s power circuit || 110 A 40 °C - 10 min power circuit || 260 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Overvoltage Category : III
  • Tightening Torque : power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm || power circuit 5 N.m screw clamp terminals 2.5-25 mm² hexagonal 4 mm
  • Operating Time : 42.5...57.5 ms closing || 16...24 ms opening
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Complementary
    • Hold-In Power Consumption In W : 7.4-7.4 W 20 °C
    • Time Constant : 34 ms
    • Inrush Power In W : 19-19 W 20 °C)
    • Minimum Switching Current : 5 mA signalling circuit
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.75...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Minimum Switching Voltage : 17 V signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Signalling Circuit Frequency : 25...400 Hz
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
  • Environment
    • Flame Retardance : V1 conforming to UL 94
    • Net Weight : 0.935 kg
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Pollution Degree : 3
    • Height : 122 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Ambient Air Temperature For Storage : -60-80 °C
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Depth : 120 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Width : 55 mm