IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 120VAC 50/60Hz coil, open style

SQDLC1D65A6G7 LC1D65A6G7 785901341826
352.22 / EA
  • Certifications: CCC, CSA, GOST, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 80 A 50 Hz Power Circuit
  • Net Weight: 0.86 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 120 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • Mercury Free : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Eu Rohs Directive : Compliant
    • Reach Free Of Svhc : Yes
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Circularity Profile : ENVEOLI1503009EN
    • Rohs Exemption Information : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Environmental Disclosure : ENVPEP1503009EN
    • Toxic Heavy Metal Free : Yes
  • Environment
    • Maximum Width : 55 mm
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Pollution Degree : 3
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Flame Retardance : V1 conforming to UL 94
    • Protective Treatment : TH IEC 60068-2-30
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Maximum Height : 122 mm
    • Ambient Air Temperature For Storage : -60-80 °C
    • Net Weight : 0.86 kg
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Maximum Depth : 120 mm
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Current : 5 mA signalling circuit
    • Minimum Switching Voltage : 17 V signalling circuit
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Coil Technology : without built-in suppressor module
    • Inrush Power In Va : 140-140 VA 60 Hz 0.75 20 °C)
    • Heat Dissipation : 4-5 W 60 Hz
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 60 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 60 Hz
    • Hold-In Power Consumption In Va : 13-13 VA 60 Hz 0.3 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Signalling Circuit Frequency : 25...400 Hz
  • Contractual warranty
    • Warranty : 18 months
  • Operating Time : 4...19 ms opening || 12...26 ms closing
  • Product Name : TeSys D
  • Maximum Horse Power Rating : 40 hp 460/480 V at AC 50/60 Hz for 3 phase || 5 hp 115 V at AC 50/60 Hz for 1 phase || 10 hp 230/240 V at AC 50/60 Hz for 1 phase || 20 hp 200/208 V at AC 50/60 Hz for 3 phase || 20 hp 230/240 V at AC 50/60 Hz for 3 phase || 50 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Device Short Name : LC1D
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Uc] Control Circuit Voltage : 120 V AC 60 Hz
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 16.5 mm)
  • Overvoltage Category : III
  • Power Dissipation Per Pole : 9.6 W AC-1 || 6.3 W AC-3
  • Product Or Component Type : contactor
  • Range : TeSys
  • Pole Contact Composition : 3 NO
  • Mounting Support : rail || plate
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • [Ie] Rated Operational Current : 80 A 60 °C) <= 440 V AC AC-1 power circuit || 65 A 60 °C) <= 440 V AC AC-3 power circuit
  • Rated Breaking Capacity : 1000 A 440 V power circuit IEC 60947
  • Control Circuit Type : AC 60 Hz
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz power circuit
  • Utilisation Category : AC-1 || AC-3 || AC-4
  • Electrical Durability : 1.4 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V
  • Motor Power Kw : 11 kW 400 V AC 50/60 Hz AC-4) || 18.5 kW 220...230 V AC 50/60 Hz AC-3) || 30 kW 380...400 V AC 50/60 Hz AC-3) || 37 kW 500 V AC 50/60 Hz AC-3) || 37 kW 660...690 V AC 50/60 Hz AC-3)
  • Contactor Application : motor control || resistive load
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 80 A 60 °C power circuit
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Protective Cover : with
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1000 A 440 V power circuit IEC 60947
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 125 A gG <= 690 V type 1 power circuit || 125 A gG <= 690 V type 2 power circuit
  • [Icw] Rated Short-Time Withstand Current : 520 A 40 °C - 10 s power circuit || 900 A 40 °C - 1 s power circuit || 110 A 40 °C - 10 min power circuit || 260 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Mechanical Durability : 6 Mcycles
  • Product Certifications : CSA || GOST || CCC || UL
  • Tightening Torque : control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Poles Description : 3P
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1