IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 12VDC coil, open style

IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 12VDC coil, open style

SQDLC1D65AJD LC1D65AJD 785901565581
440.82 / EACH
  • Certifications: CCC, CSA, GOST, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 80 A 50 Hz Power Circuit
  • Net Weight: 0.935 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.06 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Environment
    • Maximum Depth : 120 mm
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Net Weight : 0.935 kg
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Protective Treatment : TH IEC 60068-2-30
    • Maximum Height : 122 mm
    • Maximum Width : 55 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ambient Air Temperature For Storage : -60-80 °C
    • Flame Retardance : V1 conforming to UL 94
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Pollution Degree : 3
    • Ip Degree Of Protection : IP20 front face IEC 60529
  • Offer Sustainability
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Eu Rohs Directive : Compliant
    • Sustainable Offer Status : Green Premium product
    • Rohs Exemption Information : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Mercury Free : Yes
    • Reach Free Of Svhc : Yes
    • Pvc Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Environmental Disclosure : ENVPEP1503009EN
    • Toxic Heavy Metal Free : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Circularity Profile : ENVEOLI1503009EN
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 80 A 60 °C power circuit
  • [Icw] Rated Short-Time Withstand Current : 520 A 40 °C - 10 s power circuit || 900 A 40 °C - 1 s power circuit || 110 A 40 °C - 10 min power circuit || 260 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • [Ie] Rated Operational Current : 80 A 60 °C) <= 440 V AC AC-1 power circuit || 65 A 60 °C) <= 440 V AC AC-3 power circuit
  • Mounting Support : rail || plate
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Overvoltage Category : III
  • Power Dissipation Per Pole : 9.6 W AC-1 || 6.3 W AC-3
  • Device Short Name : LC1D
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm
  • Rated Breaking Capacity : 1000 A 440 V power circuit IEC 60947
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Product Certifications : CCC || GOST || CSA || UL
  • Product Name : TeSys D
  • Pole Contact Composition : 3 NO
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Operating Time : 42.5...57.5 ms closing || 16...24 ms opening
  • Protective Cover : with
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²solid without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²solid without cable end
  • Poles Description : 3P
  • Motor Power Kw : 11 kW 400 V AC 50/60 Hz AC-4) || 18.5 kW 220...230 V AC 50/60 Hz AC-3) || 30 kW 380...400 V AC 50/60 Hz AC-3) || 37 kW 500 V AC 50/60 Hz AC-3) || 37 kW 660...690 V AC 50/60 Hz AC-3)
  • Mechanical Durability : 10 Mcycles
  • Range : TeSys
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1000 A 440 V power circuit IEC 60947
  • Maximum Horse Power Rating : 40 hp 460/480 V at AC 50/60 Hz for 3 phase || 5 hp 115 V at AC 50/60 Hz for 1 phase || 10 hp 230/240 V at AC 50/60 Hz for 1 phase || 20 hp 200/208 V at AC 50/60 Hz for 3 phase || 20 hp 230/240 V at AC 50/60 Hz for 3 phase || 50 hp 575/600 V at AC 50/60 Hz for 3 phase
  • [Uc] Control Circuit Voltage : 12 V DC
  • Electrical Durability : 0.5 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V
  • Utilisation Category : AC-3 || AC-1 || AC-4
  • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz power circuit
  • Control Circuit Type : DC standard
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 125 A gG <= 690 V type 1 power circuit || 125 A gG <= 690 V type 2 power circuit
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Contactor Application : resistive load || motor control
  • Product Or Component Type : contactor
  • Contractual warranty
    • Warranty : 18 months
  • Complementary
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Hold-In Power Consumption In W : 7.4-7.4 W 20 °C
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.75...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Minimum Switching Voltage : 17 V signalling circuit
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Time Constant : 34 ms
    • Inrush Power In W : 19-19 W 20 °C)