SQUARE D

IEC contactor, TeSys D, nonreversing, 65A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 100VAC 50/60Hz coil, open style

TeSys D 3P Everlink AC CONTR A

SQDLC1D65A6K7 LC1D65A6K7 338911940083
0.00 / EA
  • Certifications: CCC, CSA, GOST, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 80 A 50 Hz Power Circuit
  • Net Weight: 0.86 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 100 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. Contactor is supplied with a 100 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Complementary
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Hold-In Power Consumption In Va : 13-13 VA 60 Hz 0.3 20 °C) || 15-15 VA 50 Hz 0.3 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Inrush Power In Va : 140-140 VA 60 Hz 0.75 20 °C) || 160-160 VA 50 Hz 0.75 20 °C)
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Coil Technology : without built-in suppressor module
    • Minimum Switching Voltage : 17 V signalling circuit
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Heat Dissipation : 4-5 W 50/60 Hz
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Pvc Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Sustainable Offer Status : Green Premium product
    • Reach Free Of Svhc : Yes
    • Eu Rohs Directive : Compliant
    • California Proposition 65 : WARNING: Cancer - www.P65Warnings.ca.gov
    • Environmental Disclosure : ENVPEP1503009EN
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Circularity Profile : ENVEOLI1503009EN
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Rohs Exemption Information : Yes
  • Environment
    • Height : 122 mm
    • Pollution Degree : 3
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ambient Air Temperature For Storage : -60-80 °C
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Width : 55 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Depth : 120 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Net Weight : 0.86 kg
    • Flame Retardance : V1 conforming to UL 94
  • Product Or Component Type : contactor
  • Device Short Name : LC1D
  • Power Dissipation Per Pole : 9.6 W AC-1 || 6.3 W AC-3
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Tightening Torque : control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 6 N.m lugs-ring terminals hexagonal 10 mm M6
  • [Icw] Rated Short-Time Withstand Current : 520 A 40 °C - 10 s power circuit || 900 A 40 °C - 1 s power circuit || 110 A 40 °C - 10 min power circuit || 260 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Mounting Support : plate || rail
  • Electrical Durability : 1.4 Mcycles 80 A AC-1 <= 440 V || 1.45 Mcycles 65 A AC-3 <= 440 V
  • Mechanical Durability : 6 Mcycles
  • Product Certifications : UL || GOST || CSA || CCC || UKCA
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 125 A gG <= 690 V type 1 power circuit || 125 A gG <= 690 V type 2 power circuit
  • Product Name : TeSys D
  • Motor Power Kw : 11 kW 400 V AC 50/60 Hz AC-4) || 18.5 kW 220...230 V AC 50/60 Hz AC-3) || 30 kW 380...400 V AC 50/60 Hz AC-3) || 37 kW 500 V AC 50/60 Hz AC-3) || 37 kW 660...690 V AC 50/60 Hz AC-3)
  • Overvoltage Category : III
  • Range : TeSys
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 1000 A 440 V power circuit IEC 60947
  • Control Circuit Type : AC 50/60 Hz
  • Maximum Horse Power Rating : 40 hp 460/480 V at AC 50/60 Hz for 3 phase || 5 hp 115 V at AC 50/60 Hz for 1 phase || 10 hp 230/240 V at AC 50/60 Hz for 1 phase || 20 hp 200/208 V at AC 50/60 Hz for 3 phase || 20 hp 230/240 V at AC 50/60 Hz for 3 phase || 50 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Contactor Application : resistive load || motor control
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 80 A 60 °C power circuit
  • Poles Description : 3P
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Protective Cover : with
  • [Uc] Control Circuit Voltage : 100 V AC 50/60 Hz
  • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz power circuit
  • Operating Time : 4...19 ms opening || 12...26 ms closing
  • Utilisation Category : AC-1 || AC-4 || AC-3
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Pole Contact Composition : 3 NO
  • Rated Breaking Capacity : 1000 A 440 V power circuit IEC 60947
  • [Ie] Rated Operational Current : 80 A 60 °C) <= 440 V AC AC-1 power circuit || 65 A 60 °C) <= 440 V AC AC-3 power circuit
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 16.5 mm)
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1