IEC contactor, TeSys D, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 480VAC 50/60Hz coil, open

IEC contactor, TeSys D, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 480VAC 50/60Hz coil, open

SQDLC1D50AT7 LC1D50AT7 785901565291
269.09 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 80 A 50 Hz Power Circuit
  • Net Weight: 0.855 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 480 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 50A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 15HP at 200 to 208VAC, 15HP at 240VAC, 40HP at 480VAC and 40HP at 600VAC three phase. Contactor is also rated for 3HP at 115VAC and 7.5HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 110A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 480 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.87 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 100 A gG <= 690 V type 1 power circuit || 100 A gG <= 690 V type 2 power circuit
  • Mounting Support : plate || rail
  • Electrical Durability : 1.45 Mcycles 50 A AC-3 <= 440 V || 1.1 Mcycles 80 A AC-1 <= 440 V
  • Power Dissipation Per Pole : 3.7 W AC-3 || 9.6 W AC-1
  • [Icw] Rated Short-Time Withstand Current : 400 A 40 °C - 10 s power circuit || 810 A 40 °C - 1 s power circuit || 84 A 40 °C - 10 min power circuit || 208 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Poles Description : 3P
  • Operating Time : 4...19 ms opening || 12...26 ms closing
  • Control Circuit Type : AC 60 Hz
  • Mechanical Durability : 6 Mcycles
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 80 A 60 °C power circuit
  • Protective Cover : with
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Utilisation Category : AC-3 || AC-4 || AC-1
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Product Name : TeSys D
  • Range : TeSys
  • Motor Power Kw : 15 kW 220...230 V AC 50/60 Hz AC-3) || 22 kW 380...400 V AC 50/60 Hz AC-3) || 30 kW 500 V AC 50/60 Hz AC-3) || 33 kW 660...690 V AC 50/60 Hz AC-3) || 25 kW 415 V AC 50/60 Hz AC-3) || 30 kW 440 V AC 50/60 Hz AC-3) || 11 kW 400 V AC 50/60 Hz AC-4)
  • Rated Breaking Capacity : 900 A 440 V power circuit IEC 60947
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Device Short Name : LC1D
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 690 V IEC 60947-4-1
  • [Uc] Control Circuit Voltage : 480 V AC 60 Hz
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Product Or Component Type : contactor
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm
  • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz power circuit
  • Pole Contact Composition : 3 NO
  • Connections - Terminals : control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²solid without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²solid without cable end
  • Contactor Application : resistive load || motor control
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Overvoltage Category : III
  • Product Certifications : DNV || GL || UL || BV || CCC || RINA || GOST || LROS (Lloyds register of shipping) || CSA
  • Maximum Horse Power Rating : 3 hp 115 V at AC 50/60 Hz for 1 phase || 7.5 hp 230/240 V at AC 50/60 Hz for 1 phase || 15 hp 200/208 V at AC 50/60 Hz for 3 phase || 15 hp 230/240 V at AC 50/60 Hz for 3 phase || 40 hp 460/480 V at AC 50/60 Hz for 3 phase || 40 hp 575/600 V at AC 50/60 Hz for 3 phase
  • [Ie] Rated Operational Current : 50 A 60 °C) <= 440 V AC AC-3 power circuit || 80 A 60 °C) <= 440 V AC AC-1 power circuit
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 900 A 440 V power circuit IEC 60947
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Ambient Air Temperature For Storage : -60-80 °C
    • Maximum Depth : 120 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Maximum Width : 55 mm
    • Pollution Degree : 3
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Flame Retardance : V1 conforming to UL 94
    • Net Weight : 0.855 kg
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open10 Gn for 11 ms
    • Maximum Height : 122 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Fire Resistance : 850 °C IEC 60695-2-1
  • Offer Sustainability
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Mercury Free : Yes
    • Circularity Profile : ENVEOLI1503009EN
    • Reach Free Of Svhc : Yes
    • Rohs Exemption Information : Yes
    • Environmental Disclosure : ENVPEP1503009EN
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Pvc Free : Yes
    • Eu Rohs Directive : Compliant
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Toxic Heavy Metal Free : Yes
  • Complementary
    • Coil Technology : without built-in suppressor module
    • Inrush Power In Va : 140-140 VA 60 Hz 0.75 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Hold-In Power Consumption In Va : 13-13 VA 60 Hz 0.3 20 °C)
    • Heat Dissipation : 4-5 W 60 Hz
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Minimum Switching Voltage : 17 V signalling circuit
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 60 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 60 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Signalling Circuit Frequency : 25...400 Hz