IEC contactor, TeSys D, nonreversing, 32A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

IEC contactor, TeSys D, nonreversing, 32A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, 24VDC coil, open style

SQDLC1D323BD LC1D323BD 785901807773
235.18 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 101 mm
  • Height: 99 mm
  • Impedance: 2 MOhm - Ith 50 A 50 Hz Power Circuit
  • Net Weight: 0.535 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.90 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 24 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.90 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Complementary
    • Minimum Switching Current : 5 mA signalling circuit
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Voltage : 17 V signalling circuit
    • Time Constant : 28 ms
    • Inrush Power In W : 5.4-5.4 W 20 °C)
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Hold-In Power Consumption In W : 5.4-5.4 W 20 °C
    • Signalling Circuit Frequency : 25...400 Hz
    • Control Circuit Voltage Limits : 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Product Name : TeSys D
  • Overvoltage Category : III
  • Contactor Application : resistive load || motor control
  • Mechanical Durability : 30 Mcycles
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Product Or Component Type : contactor
  • Rated Breaking Capacity : 550 A 440 V power circuit IEC 60947
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Pole Contact Composition : 3 NO
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 550 A 440 V power circuit IEC 60947
  • [Uc] Control Circuit Voltage : 24 V DC
  • Poles Description : 3P
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 63 A gG <= 690 V type 2 power circuit
  • Mounting Support : plate || rail
  • Power Dissipation Per Pole : 2 W AC-3 || 5 W AC-1
  • Motor Power Kw : 7.5 kW 220...230 V AC 50/60 Hz AC-3) || 15 kW 380...400 V AC 50/60 Hz AC-3) || 15 kW 415...440 V AC 50/60 Hz AC-3) || 18.5 kW 500 V AC 50/60 Hz AC-3) || 18.5 kW 660...690 V AC 50/60 Hz AC-3) || 7.5 kW 400 V AC 50/60 Hz AC-4)
  • Utilisation Category : AC-4 || AC-1 || AC-3
  • Electrical Durability : 1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V
  • Product Certifications : CSA || UL || CCC || RINA || BV || LROS (Lloyds register of shipping) || GOST || DNV || GL || UKCA
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • [Ie] Rated Operational Current : 40 A 60 °C) <= 440 V AC AC-1 power circuit || 32 A 60 °C) <= 440 V AC AC-3 power circuit
  • Range : TeSys
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Protective Cover : with
  • Control Circuit Type : DC standard
  • [Icw] Rated Short-Time Withstand Current : 260 A 40 °C - 10 s power circuit || 430 A 40 °C - 1 s power circuit || 60 A 40 °C - 10 min power circuit || 138 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Average Impedance : 2 mOhm - Ith 50 A 50 Hz power circuit
  • Device Short Name : LC1D
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 50 A 60 °C power circuit
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Maximum Horse Power Rating : 2 hp 115 V at AC 50/60 Hz for 1 phase || 5 hp 230/240 V at AC 50/60 Hz for 1 phase || 7.5 hp 200/208 V at AC 50/60 Hz for 3 phase || 10 hp 230/240 V at AC 50/60 Hz for 3 phase || 20 hp 460/480 V at AC 50/60 Hz for 3 phase || 30 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Operating Time : 53.55...72.45 ms closing || 16...24 ms opening
  • Connections - Terminals : control circuit spring terminals 1 2.5-2.5 mm²flexible without cable end || control circuit spring terminals 2 2.5-2.5 mm²flexible without cable end || power circuit spring terminals 1 4-4 mm²flexible without cable end || power circuit spring terminals 2 4-4 mm²flexible without cable end
  • Offer Sustainability
    • Environmental Disclosure : ENVPEP110229EN
    • Mercury Free : Yes
    • Eu Rohs Directive : Compliant
    • Sustainable Offer Status : Green Premium product
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Rohs Exemption Information : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Toxic Heavy Metal Free : Yes
    • Circularity Profile : ENVEOLI1102029EN
    • Pvc Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Reach Free Of Svhc : Yes
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Net Weight : 0.535 kg
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Pollution Degree : 3
    • Ambient Air Temperature For Storage : -60-80 °C
    • Maximum Width : 45 mm
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Flame Retardance : V1 conforming to UL 94
    • Maximum Height : 99 mm
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Maximum Depth : 101 mm
    • Protective Treatment : TH IEC 60068-2-30