IEC contactor, TeSys D, nonreversing, 32A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, 125VDC coil, open style

IEC contactor, TeSys D, nonreversing, 32A, 20HP at 480VAC, 3 phase, 3 pole, 3 NO, 125VDC coil, open style

SQDLC1D326GD LC1D326GD 785901957188
293.97 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 101 mm
  • Height: 85 mm
  • Impedance: 2 MOhm - Ith 50 A 50 Hz Power Circuit
  • Net Weight: 0.535 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. Contactor is supplied with a 125 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • Circularity Profile : ENVEOLI1102029EN
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP110229EN
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Sustainable Offer Status : Green Premium product
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Rohs Exemption Information : Yes
    • Pvc Free : Yes
    • Eu Rohs Directive : Compliant
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Toxic Heavy Metal Free : Yes
  • Environment
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Maximum Height : 85 mm
    • Maximum Width : 45 mm
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ambient Air Temperature For Storage : -60-80 °C
    • Flame Retardance : V1 conforming to UL 94
    • Net Weight : 0.535 kg
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Pollution Degree : 3
    • Protective Treatment : TH IEC 60068-2-30
    • Maximum Depth : 101 mm
  • Contractual warranty
    • Warranty : 18 months
  • Product Certifications : RINA || BV || CSA || LROS (Lloyds register of shipping) || UL || GOST || DNV || GL || CCC || UKCA
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Average Impedance : 2 mOhm - Ith 50 A 50 Hz power circuit
  • Rated Breaking Capacity : 550 A 440 V power circuit IEC 60947
  • [Icw] Rated Short-Time Withstand Current : 260 A 40 °C - 10 s power circuit || 430 A 40 °C - 1 s power circuit || 60 A 40 °C - 10 min power circuit || 138 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Tightening Torque : control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 2.5 N.m lugs-ring terminals flat Ø 8 mm M4 || power circuit 2.5 N.m lugs-ring terminals Philips No 2 M4
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Product Name : TeSys D
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 50 A 60 °C power circuit
  • Power Dissipation Per Pole : 2 W AC-3 || 5 W AC-1
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Electrical Durability : 1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V
  • Operating Time : 53.55...72.45 ms closing || 16...24 ms opening
  • Mechanical Durability : 30 Mcycles
  • Protective Cover : with
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Contactor Application : resistive load || motor control
  • [Uc] Control Circuit Voltage : 125 V DC
  • Device Short Name : LC1D
  • Motor Power Kw : 7.5 kW 220...230 V AC 50/60 Hz AC-3) || 15 kW 380...400 V AC 50/60 Hz AC-3) || 15 kW 415...440 V AC 50/60 Hz AC-3) || 18.5 kW 500 V AC 50/60 Hz AC-3) || 18.5 kW 660...690 V AC 50/60 Hz AC-3) || 7.5 kW 400 V AC 50/60 Hz AC-4)
  • Overvoltage Category : III
  • Product Or Component Type : contactor
  • Maximum Horse Power Rating : 2 hp 115 V at AC 50/60 Hz for 1 phase || 5 hp 230/240 V at AC 50/60 Hz for 1 phase || 7.5 hp 200/208 V at AC 50/60 Hz for 3 phase || 10 hp 230/240 V at AC 50/60 Hz for 3 phase || 20 hp 460/480 V at AC 50/60 Hz for 3 phase || 30 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Control Circuit Type : DC standard
  • Mounting Support : plate || rail
  • Utilisation Category : AC-1 || AC-4 || AC-3
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Pole Contact Composition : 3 NO
  • Range : TeSys
  • Poles Description : 3P
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 63 A gG <= 690 V type 2 power circuit
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 10 mm)
  • [Ie] Rated Operational Current : 32 A 60 °C) <= 440 V AC AC-3 power circuit || 50 A 60 °C) <= 440 V AC AC-1 power circuit
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 550 A 440 V power circuit IEC 60947
  • Complementary
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Time Constant : 28 ms
    • Minimum Switching Voltage : 17 V signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Inrush Power In W : 5.4-5.4 W 20 °C)
    • Control Circuit Voltage Limits : 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Signalling Circuit Frequency : 25...400 Hz
    • Hold-In Power Consumption In W : 5.4-5.4 W 20 °C
    • Minimum Switching Current : 5 mA signalling circuit