IEC contactor, TeSys D, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, low consumption 12VDC coil

IEC contactor, TeSys D, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, low consumption 12VDC coil

SQDLC1D32JL LC1D32JL 785901755449
235.18 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 101 mm
  • Height: 85 mm
  • Impedance: 2 MOhm - Ith 50 A 50 Hz Power Circuit
  • Net Weight: 0.535 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a low consumption 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 32A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200 to 208VAC, 10HP at 240VAC, 20HP at 480VAC and 30HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 5HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 80A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a low consumption 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.98 inches deep. It weighs 1.18 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Pvc Free : Yes
    • Rohs Exemption Information : Yes
    • Sustainable Offer Status : Green Premium product
    • Toxic Heavy Metal Free : Yes
    • Environmental Disclosure : ENVPEP110229EN
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Mercury Free : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Circularity Profile : ENVEOLI1102029EN
    • Reach Free Of Svhc : Yes
    • Eu Rohs Directive : Compliant
  • Environment
    • Ambient Air Temperature For Storage : -60-80 °C
    • Pollution Degree : 3
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Net Weight : 0.535 kg
    • Maximum Depth : 101 mm
    • Maximum Width : 45 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Maximum Height : 85 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Flame Retardance : V1 conforming to UL 94
    • Ip Degree Of Protection : IP20 front face IEC 60529
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Inrush Power In W : 2.4-2.4 W 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Voltage : 17 V signalling circuit
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Hold-In Power Consumption In W : 2.4-2.4 W 20 °C
    • Minimum Switching Current : 5 mA signalling circuit
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.8...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Time Constant : 40 ms
    • Signalling Circuit Frequency : 25...400 Hz
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Contactor Application : motor control || resistive load
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 550 A 440 V power circuit IEC 60947
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 50 A 60 °C power circuit
  • Utilisation Category : AC-3 || AC-1 || AC-4
  • Overvoltage Category : III
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Mounting Support : rail || plate
  • Average Impedance : 2 mOhm - Ith 50 A 50 Hz power circuit
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Electrical Durability : 1.65 Mcycles 32 A AC-3 <= 440 V || 1.4 Mcycles 50 A AC-1 <= 440 V
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2
  • Product Or Component Type : contactor
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Range : TeSys
  • Protective Cover : with
  • Poles Description : 3P
  • Rated Breaking Capacity : 550 A 440 V power circuit IEC 60947
  • Maximum Horse Power Rating : 2 hp 115 V at AC 50/60 Hz for 1 phase || 5 hp 230/240 V at AC 50/60 Hz for 1 phase || 7.5 hp 200/208 V at AC 50/60 Hz for 3 phase || 10 hp 230/240 V at AC 50/60 Hz for 3 phase || 20 hp 460/480 V at AC 50/60 Hz for 3 phase || 30 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Motor Power Kw : 7.5 kW 220...230 V AC 50/60 Hz AC-3) || 15 kW 380...400 V AC 50/60 Hz AC-3) || 15 kW 415...440 V AC 50/60 Hz AC-3) || 18.5 kW 500 V AC 50/60 Hz AC-3) || 18.5 kW 660...690 V AC 50/60 Hz AC-3) || 7.5 kW 400 V AC 50/60 Hz AC-4)
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 63 A gG <= 690 V type 2 power circuit
  • [Uc] Control Circuit Voltage : 12 V DC
  • Power Dissipation Per Pole : 2 W AC-3 || 5 W AC-1
  • Product Certifications : BV || CCC || RINA || LROS (Lloyds register of shipping) || CSA || DNV || UL || GL || GOST || UKCA
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Mechanical Durability : 30 Mcycles
  • Control Circuit Type : DC low consumption
  • Device Short Name : LC1D
  • Product Name : TeSys D
  • [Icw] Rated Short-Time Withstand Current : 260 A 40 °C - 10 s power circuit || 430 A 40 °C - 1 s power circuit || 60 A 40 °C - 10 min power circuit || 138 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • [Ie] Rated Operational Current : 32 A 60 °C) <= 440 V AC AC-3 power circuit || 50 A 60 °C) <= 440 V AC AC-1 power circuit
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit screw clamp terminals 1 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 2 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 1 1-10 mm²flexible with cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm²solid without cable end || power circuit screw clamp terminals 2 2.5-10 mm²solid without cable end
  • Pole Contact Composition : 3 NO
  • Operating Time : 65.45...88.55 ms closing || 20...30 ms opening