IEC contactor, TeSys D, nonreversing, 25A, 15HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 250VDC coil, open style

CONTACTOR 575VAC 25AMP IEC +OP

SQDLC1D25UD LC1D25UD 785901670438
206.74 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 3 NO
  • Depth: 101 mm
  • Height: 85 mm
  • Impedance: 2 MOhm - Ith 40 A 50 Hz Power Circuit
  • Net Weight: 0.53 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200-208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 60A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 250 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200-208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 60A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 250 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Control Circuit Type : DC standard
  • Rated Breaking Capacity : 450 A 440 V power circuit IEC 60947
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Range : TeSys || TeSys Deca
  • Overvoltage Category : III
  • Mounting Support : plate || rail
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 450 A 440 V power circuit IEC 60947
  • Poles Description : 3P
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 40 A 60 °C power circuit
  • Power Dissipation Per Pole : 3.2 W AC-1 || 1.25 W AC-3
  • Maximum Horse Power Rating : 3 hp 230/240 V at AC 50/60 Hz for 1 phase || 2 hp 115 V at AC 50/60 Hz for 1 phase || 7.5 hp 230/240 V at AC 50/60 Hz for 3 phase || 15 hp 460/480 V at AC 50/60 Hz for 3 phase || 20 hp 575/600 V at AC 50/60 Hz for 3 phase || 7.5 hp 200/208 V at AC 50/60 Hz for 3 phase
  • Product Or Component Type : contactor
  • Electrical Durability : 1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V
  • Protective Cover : with
  • Mechanical Durability : 30 Mcycles
  • Pole Contact Composition : 3 NO
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit screw clamp terminals 1 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 2 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 1 1-10 mm²flexible with cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm²solid without cable end || power circuit screw clamp terminals 2 2.5-10 mm²solid without cable end
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Average Impedance : 2 mOhm - Ith 40 A 50 Hz power circuit
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Operating Time : 53.55...72.45 ms closing || 16...24 ms opening
  • [Ie] Rated Operational Current : 25 A 60 °C) <= 440 V AC AC-3 power circuit || 40 A 60 °C) <= 440 V AC AC-1 power circuit
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Product Name : TeSys D || TeSys Deca
  • Utilisation Category : AC-1 || AC-4 || AC-3
  • [Icw] Rated Short-Time Withstand Current : 240 A 40 °C - 10 s power circuit || 380 A 40 °C - 1 s power circuit || 50 A 40 °C - 10 min power circuit || 120 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Product Certifications : GOST || GL || LROS (Lloyds register of shipping) || RINA || UL || CSA || DNV || CCC || BV || UKCA
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Uc] Control Circuit Voltage : 250 V DC
  • Device Short Name : LC1D
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 40 A gG <= 690 V type 2 power circuit
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • Contactor Application : resistive load || motor control
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
  • Motor Power Kw : 5.5 kW 220...230 V AC 50/60 Hz AC-3) || 11 kW 380...400 V AC 50/60 Hz AC-3) || 11 kW 415...440 V AC 50/60 Hz AC-3) || 15 kW 500 V AC 50/60 Hz AC-3) || 15 kW 660...690 V AC 50/60 Hz AC-3) || 5.5 kW 400 V AC 50/60 Hz AC-4)
  • Offer Sustainability
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Circularity Profile : ENVEOLI1102029EN
    • Environmental Disclosure : ENVPEP110229EN
    • Rohs Exemption Information : Yes
    • Eu Rohs Directive : Compliant
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Pvc Free : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Mercury Free : Yes
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Height : 85 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Width : 45 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Net Weight : 0.53 kg
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Pollution Degree : 3
    • Flame Retardance : V1 conforming to UL 94
    • Depth : 101 mm
    • Ambient Air Temperature For Storage : -60-80 °C
  • Complementary
    • Control Circuit Voltage Limits : 0.1...0.25 Uc -40-70 °C drop-out DC || 0.7...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Signalling Circuit Frequency : 25...400 Hz
    • Time Constant : 28 ms
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Current : 5 mA signalling circuit
    • Inrush Power In W : 5.4-5.4 W 20 °C)
    • Minimum Switching Voltage : 17 V signalling circuit
    • Hold-In Power Consumption In W : 5.4-5.4 W 20 °C