IEC contactor, TeSys D, nonreversing, 25A, 15HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 12VDC coil, open style

CONTACTOR 600VAC 25AMP IEC +OP

SQDLC1D25JL LC1D25JL 785901973591
206.74 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC, 3 NO
  • Depth: 101 mm
  • Height: 85 mm
  • Impedance: 2 MOhm - Ith 40 A 50 Hz Power Circuit
  • Net Weight: 0.53 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200-208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 60A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a low consumption 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200-208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 60A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a low consumption 12 VDC coil with transient suppressor module. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Offer Sustainability
    • Toxic Heavy Metal Free : Yes
    • Eu Rohs Directive : Compliant
    • Rohs Exemption Information : Yes
    • Circularity Profile : ENVEOLI1102029EN
    • Pvc Free : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Mercury Free : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Sustainable Offer Status : Green Premium product
    • Environmental Disclosure : ENVPEP110229EN
    • Reach Free Of Svhc : Yes
  • Complementary
    • Inrush Power In W : 2.4-2.4 W 20 °C)
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Time Constant : 40 ms
    • Minimum Switching Voltage : 17 V signalling circuit
    • Control Circuit Voltage Limits : 0.1...0.3 Uc -40-70 °C drop-out DC || 0.8...1.25 Uc -40-60 °C operational DC || 1...1.25 Uc 60-70 °C operational DC
    • Hold-In Power Consumption In W : 2.4-2.4 W 20 °C
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Signalling Circuit Frequency : 25...400 Hz
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Minimum Switching Current : 5 mA signalling circuit
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 63 A gG <= 690 V type 1 power circuit || 40 A gG <= 690 V type 2 power circuit
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508 || IEC 60335-1
  • Poles Description : 3P
  • Irms Rated Making Capacity : 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1 || 450 A 440 V power circuit IEC 60947
  • Control Circuit Type : DC low consumption
  • Maximum Horse Power Rating : 3 hp 230/240 V at AC 50/60 Hz for 1 phase || 2 hp 115 V at AC 50/60 Hz for 1 phase || 7.5 hp 230/240 V at AC 50/60 Hz for 3 phase || 15 hp 460/480 V at AC 50/60 Hz for 3 phase || 20 hp 575/600 V at AC 50/60 Hz for 3 phase || 7.5 hp 200/208 V at AC 50/60 Hz for 3 phase
  • [Uc] Control Circuit Voltage : 12 V DC
  • Product Name : TeSys D || TeSys Deca
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Utilisation Category : AC-3 || AC-4 || AC-1
  • Electrical Durability : 1.65 Mcycles 25 A AC-3 <= 440 V || 1.4 Mcycles 40 A AC-1 <= 440 V
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Rated Breaking Capacity : 450 A 440 V power circuit IEC 60947
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 2.5 N.m screw clamp terminals flat Ø 6 mm || power circuit 2.5 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
  • Operating Time : 65.45...88.55 ms closing || 20...30 ms opening
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Range : TeSys || TeSys Deca
  • Average Impedance : 2 mOhm - Ith 40 A 50 Hz power circuit
  • Mechanical Durability : 30 Mcycles
  • [Ie] Rated Operational Current : 25 A 60 °C) <= 440 V AC AC-3 power circuit || 40 A 60 °C) <= 440 V AC AC-1 power circuit
  • Overvoltage Category : III
  • Protective Cover : with
  • Power Dissipation Per Pole : 3.2 W AC-1 || 1.25 W AC-3
  • Product Or Component Type : contactor
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid without cable end || control circuit screw clamp terminals 2 1-4 mm²solid without cable end || power circuit screw clamp terminals 1 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 2 2.5-10 mm²flexible without cable end || power circuit screw clamp terminals 1 1-10 mm²flexible with cable end || power circuit screw clamp terminals 2 1.5-6 mm²flexible with cable end || power circuit screw clamp terminals 1 1.5-10 mm²solid without cable end || power circuit screw clamp terminals 2 2.5-10 mm²solid without cable end
  • Product Certifications : DNV || RINA || LROS (Lloyds register of shipping) || GL || BV || CCC || GOST || UL || CSA || UKCA
  • Pole Contact Composition : 3 NO
  • Device Short Name : LC1D
  • [Icw] Rated Short-Time Withstand Current : 240 A 40 °C - 10 s power circuit || 380 A 40 °C - 1 s power circuit || 50 A 40 °C - 10 min power circuit || 120 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Motor Power Kw : 5.5 kW 220...230 V AC 50/60 Hz AC-3) || 11 kW 380...400 V AC 50/60 Hz AC-3) || 11 kW 415...440 V AC 50/60 Hz AC-3) || 15 kW 500 V AC 50/60 Hz AC-3) || 15 kW 660...690 V AC 50/60 Hz AC-3) || 5.5 kW 400 V AC 50/60 Hz AC-4)
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 40 A 60 °C power circuit
  • Mounting Support : rail || plate
  • Contactor Application : resistive load || motor control
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Environment
    • Ambient Air Temperature For Storage : -60-80 °C
    • Pollution Degree : 3
    • Depth : 101 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Flame Retardance : V1 conforming to UL 94
    • Width : 45 mm
    • Height : 85 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open8 Gn for 11 ms
    • Net Weight : 0.53 kg
  • Contractual warranty
    • Warranty : 18 months