IEC contactor, TeSys D, nonreversing, 12A, 7.5HP at 480VAC, 3 phase, 3 pole, 3 NO, 230VAC 50/60Hz coil, open style

IEC contactor, TeSys D, nonreversing, 12A, 7.5HP at 480VAC, 3 phase, 3 pole, 3 NO, 230VAC 50/60Hz coil, open style

SQDLC1D123P7 LC1D123P7 338911080301
0.00 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 86 mm
  • Height: 99 mm
  • Impedance: 2.5 MOhm - Ith 16 A 50 Hz Power Circuit
  • Net Weight: 0.325 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200 to 208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.90 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200 to 208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Spring terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.90 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Complementary
    • Coil Technology : without built-in suppressor module
    • Minimum Switching Current : 5 mA signalling circuit
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Voltage : 17 V signalling circuit
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Heat Dissipation : 2-3 W 50/60 Hz
  • Environment
    • Pollution Degree : 3
    • Flame Retardance : V1 conforming to UL 94
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ambient Air Temperature For Storage : -60-80 °C
    • Depth : 86 mm
    • Width : 45 mm
    • Net Weight : 0.325 kg
    • Height : 99 mm
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Protective Treatment : TH IEC 60068-2-30
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
  • Contractual warranty
    • Warranty : 18 months
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • [Icw] Rated Short-Time Withstand Current : 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Motor Power Kw : 3 kW 220...230 V AC 50/60 Hz AC-3) || 5.5 kW 380...400 V AC 50/60 Hz AC-3) || 5.5 kW 415...440 V AC 50/60 Hz AC-3) || 7.5 kW 500 V AC 50/60 Hz AC-3) || 7.5 kW 660...690 V AC 50/60 Hz AC-3) || 3.7 kW 400 V AC 50/60 Hz AC-4)
  • Average Impedance : 2.5 mOhm - Ith 16 A 50 Hz power circuit
  • Utilisation Category : AC-3 || AC-4 || AC-1
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • [Ie] Rated Operational Current : 16 A 60 °C) <= 440 V AC AC-1 power circuit || 12 A 60 °C) <= 440 V AC AC-3 power circuit
  • Pole Contact Composition : 3 NO
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Rated Breaking Capacity : 250 A 440 V power circuit IEC 60947
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Control Circuit Type : AC 50/60 Hz
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • Irms Rated Making Capacity : 250 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Operating Time : 12...22 ms closing || 4...19 ms opening
  • Power Dissipation Per Pole : 0.36 W AC-3 || 1.56 W AC-1
  • Product Certifications : LROS (Lloyds register of shipping) || GL || BV || UL || CSA || CCC || DNV || RINA || GOST || UKCA
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Maximum Horse Power Rating : 0.5 hp 115 V at AC 50/60 Hz for 1 phase || 2 hp 230/240 V at AC 50/60 Hz for 1 phase || 3 hp 200/208 V at AC 50/60 Hz for 3 phase || 3 hp 230/240 V at AC 50/60 Hz for 3 phase || 7.5 hp 460/480 V at AC 50/60 Hz for 3 phase || 10 hp 575/600 V at AC 50/60 Hz for 3 phase
  • Product Or Component Type : contactor
  • Mechanical Durability : 15 Mcycles
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 40 A gG <= 690 V type 1 power circuit || 25 A gG <= 690 V type 2 power circuit
  • Product Name : TeSys D
  • Connections - Terminals : power circuit spring terminals 1 2.5-2.5 mm²flexible without cable end || power circuit spring terminals 2 2.5-2.5 mm²flexible without cable end || control circuit spring terminals 1 2.5-2.5 mm²flexible without cable end || control circuit spring terminals 2 2.5-2.5 mm²flexible without cable end
  • Overvoltage Category : III
  • Mounting Support : plate || rail
  • Device Short Name : LC1D
  • Poles Description : 3P
  • [Uc] Control Circuit Voltage : 230 V AC 50/60 Hz
  • Range : TeSys
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Electrical Durability : 2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V
  • [Ith] Conventional Free Air Thermal Current : 10 A 60 °C signalling circuit || 16 A 60 °C power circuit
  • Contactor Application : resistive load || motor control
  • Protective Cover : with
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Reach Free Of Svhc : Yes
    • Toxic Heavy Metal Free : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Sustainable Offer Status : Green Premium product
    • Circularity Profile : ENVEOLI1501004EN
    • Pvc Free : Yes
    • Eu Rohs Directive : Compliant
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Environmental Disclosure : ENVPEP1501004EN
    • Mercury Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.