SQUARE D

IEC contactor, TeSys D, nonreversing, 12A, 7.5HP at 480VAC, 3 phase, 3 pole, 3 NO, 220VAC 50/60Hz coil, open style

CONTACTOR 600VAC 12AMP IEC +OP

SQDLC1D126M7 LC1D126M7 785901676300
130.17 / EACH
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 86 mm
  • Height: 77 mm
  • Impedance: 2.5 MOhm - Ith 25 A 50 Hz Power Circuit
  • Net Weight: 0.325 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 45 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200 to 208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. Contactor is supplied with a 480 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 12A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 3HP at 200 to 208VAC, 3HP at 240VAC, 7.5HP at 480VAC and 10HP at 600VAC three phase. Contactor is also rated for 0.5HP at 115VAC and 2HP at 240VAC single phase. Contactor is supplied with a 480 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.03 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.72 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Eu Rohs Directive : Compliant
    • Reach Free Of Svhc : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Mercury Free : Yes
    • Rohs Exemption Information : Yes
    • Environmental Disclosure : ENVPEP1501004EN
    • Circularity Profile : ENVEOLI1501004EN
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Toxic Heavy Metal Free : Yes
  • Irms Rated Making Capacity : 250 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Power Dissipation Per Pole : 0.36 W AC-3 || 1.56 W AC-1
  • Average Impedance : 2.5 mOhm - Ith 25 A 50 Hz power circuit
  • Control Circuit Type : AC 50/60 Hz
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Overvoltage Category : III
  • Range : TeSys
  • Tightening Torque : control circuit 1.7 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 1.7 N.m lugs-ring terminals flat Ø 8 mm M3.5 || power circuit 1.7 N.m lugs-ring terminals Philips No 2 M3.5
  • Product Name : TeSys D
  • Device Short Name : LC1D
  • [Uc] Control Circuit Voltage : 220 V AC 50/60 Hz
  • [Ith] Conventional Free Air Thermal Current : 25 A 60 °C power circuit || 10 A 60 °C signalling circuit
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Poles Description : 3P
  • Maximum Horse Power Rating : 0.5 hp 115 V at AC 50/60 Hz for 1 phase || 2 hp 230/240 V at AC 50/60 Hz for 1 phase || 3 hp 200/208 V at AC 50/60 Hz for 3 phase || 3 hp 230/240 V at AC 50/60 Hz for 3 phase || 7.5 hp 460/480 V at AC 50/60 Hz for 3 phase || 10 hp 575/600 V at AC 50/60 Hz for 3 phase
  • [Ie] Rated Operational Current : 25 A 60 °C) <= 440 V AC AC-1 power circuit || 12 A 60 °C) <= 440 V AC AC-3 power circuit
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • [Icw] Rated Short-Time Withstand Current : 105 A 40 °C - 10 s power circuit || 210 A 40 °C - 1 s power circuit || 30 A 40 °C - 10 min power circuit || 61 A 40 °C - 1 min power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Motor Power Kw : 3 kW 220...230 V AC 50/60 Hz AC-3) || 5.5 kW 380...400 V AC 50/60 Hz AC-3) || 5.5 kW 415...440 V AC 50/60 Hz AC-3) || 7.5 kW 500 V AC 50/60 Hz AC-3) || 7.5 kW 660...690 V AC 50/60 Hz AC-3) || 3.7 kW 400 V AC 50/60 Hz AC-4)
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz || power circuit <= 300 V DC
  • Mounting Support : plate || rail
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Contactor Application : resistive load || motor control
  • Associated Fuse Rating : 10 A gG signalling circuit IEC 60947-5-1 || 40 A gG <= 690 V type 1 power circuit || 25 A gG <= 690 V type 2 power circuit
  • Electrical Durability : 2 Mcycles 12 A AC-3 <= 440 V || 0.8 Mcycles 25 A AC-1 <= 440 V
  • Utilisation Category : AC-3 || AC-1 || AC-4
  • Rated Breaking Capacity : 250 A 440 V power circuit IEC 60947
  • Product Or Component Type : contactor
  • Protective Cover : with
  • Mechanical Durability : 15 Mcycles
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Product Certifications : GOST || CSA || RINA || DNV || LROS (Lloyds register of shipping) || UL || BV || CCC || GL || UKCA
  • Pole Contact Composition : 3 NO
  • Operating Time : 12...22 ms closing || 4...19 ms opening
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 8 mm)
  • Environment
    • Ambient Air Temperature For Storage : -60-80 °C
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Net Weight : 0.325 kg
    • Height : 77 mm
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Flame Retardance : V1 conforming to UL 94
    • Width : 45 mm
    • Pollution Degree : 3
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Depth : 86 mm
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Protective Treatment : TH IEC 60068-2-30
    • Fire Resistance : 850 °C IEC 60695-2-1
  • Complementary
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Minimum Switching Voltage : 17 V signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Heat Dissipation : 2-3 W 50/60 Hz
    • Inrush Power In Va : 70-70 VA 60 Hz 0.75 20 °C) || 70-70 VA 50 Hz 0.75 20 °C)
    • Signalling Circuit Frequency : 25...400 Hz
    • Minimum Switching Current : 5 mA signalling circuit
    • Hold-In Power Consumption In Va : 7.5-7.5 VA 60 Hz 0.3 20 °C) || 7-7 VA 50 Hz 0.3 20 °C)
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Coil Technology : without built-in suppressor module
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact