TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. When used with a 480VAC up to 250A circuit breaker, this contactor can have a SCCR up to 100kA. When used with a 600VAC up to 250A circuit breaker, this contactor can have a SCCR up to 50kA. When used with 600VAC Class J or CC fuses up to 250A, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 480 VAC 60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
- Environment
- Product Certifications : UL || CSA || CCC || UKCA || CE || EAC || Marine
- Height : 158 mm
- Standards : CSA C22.2 No 14 || EN 60947-4-1 || IEC 60947-4-1 || IEC 60335-1:Clause 30.2 || IEC 60335-2-40:Annex JJ || UL 60335-2-40:Annex JJ || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || JIS C8201-4-1
- Climatic Withstand : IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
- Net Weight : 2.5 kg
- Flame Retardance : V1 conforming to UL 94
- Protective Treatment : THIEC 60068-2-30
- Ip Degree Of Protection : IP20 front face IEC 60529
- Mechanical Robustness : vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 6 Gn for 11 ms)
- Operating Altitude : 0...9842.52 ft (0...3000 m)
- Fire Resistance : 850 °C IEC 60695-2-1
- Width : 120 mm
- Depth : 136 mm
- Permissible Ambient Air Temperature Around The Device : -40-60 °C || 60-70 °C with derating
- Contractual warranty
- Offer Sustainability
- Rohs Exemption Information : Yes
- Mercury Free : Yes
- Environmental Disclosure : ENVPEP060301EN
- Sustainable Offer Status : Green Premium product
- Pvc Free : Yes
- Reach Regulation : Reference contains Substances of Very High Concern above the threshold
- California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile : ENVEOLI100405EN
- Sustainable Packaging : Yes
- Eu Rohs Directive : Compliant with Exemptions
- Complementary
- Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
- Minimum Switching Current : 5 mA for signalling circuit
- Power Dissipation Per Pole : 24 W AC-1 || 7.9 W AC-3 || 7.9 W AC-3e
- Average Impedance : 0.6 mOhm - Ith 200 A 50 Hz for power circuit
- Auxiliary Contact Composition : 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current : 200 A (at 60 °C) for power circuit
- Control Circuit Voltage Limits : 0.85...1.1 Uc -40-55 °C operational AC 60 Hz || 0.3...0.6 Uc -40-70 °C drop-out AC 60 Hz || 1...1.1 Uc 55-70 °C operational AC 60 Hz
- Mounting Support : rail || plate
- Control Circuit Type : AC 60 Hz
- Safety Reliability Level : B10d = 684932 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 10000000 cycles contactor with mechanical load EN/ISO 13849-1
- Pollution Degree : 3
- Insulation Resistance : > 10 MOhm for signalling circuit
- Rated Breaking Capacity : 1100 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity : 1260 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
- Associated Fuse Rating : 250 A gG at <= 690 V coordination type 1 for power circuit || 200 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for signalling circuit
- Inrush Power In Va : 300-300 VA 60 Hz cos phi 0.8 (at 20 °C)
- [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947
- Pole Contact Composition : 3 NO
- Connections - Terminals : control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: solid without cable end || power circuit: connector 1 10-120 mm² - cable stiffness: flexible without cable end || power circuit: connector 2 10-50 mm² - cable stiffness: flexible without cable end || power circuit: connector 1 10-120 mm² - cable stiffness: flexible with cable end || power circuit: connector 2 10-50 mm² - cable stiffness: flexible with cable end || power circuit: connector 1 10-120 mm² - cable stiffness: solid without cable end || power circuit: connector 2 10-50 mm² - cable stiffness: solid without cable end
- Coil Technology : without built-in suppressor module
- Operating Time : 6...20 ms opening || 20...50 ms closing
- Minimum Switching Voltage : 17 V for signalling circuit
- Maximum Operating Rate : 2400 cyc/h at 60 °C
- Signalling Circuit Frequency : 25...400 Hz
- Tightening Torque : control circuit 1.2 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.2 N.m screw clamp terminals Philips No 2 || power circuit 12 N.m connector hexagonal 4 mm || control circuit 1.2 N.m screw clamp terminals pozidriv No 2
- Electrical Durability : 0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V || 0.95 Mcycles 115 A AC-3e <= 440 V
- Mechanical Durability : 8 Mcycles
- Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
- Compatibility Code : LC1D
- Hold-In Power Consumption In Va : 22-22 VA 60 Hz cos phi 0.3 (at 20 °C)
- Overvoltage Category : III
- Maximum Horse Power Rating : 30 hp at 200/208 V AC 50/60 Hz for 3 phase motors || 40 hp at 230/240 V AC 50/60 Hz for 3 phase motors || 75 hp at 460/480 V AC 50/60 Hz for 3 phase motors || 100 hp at 575/600 V AC 50/60 Hz for 3 phase motors
- Motor Power Kw : 30 kW at 220...230 V AC 50/60 Hz (AC-3) || 55 kW at 380...400 V AC 50/60 Hz (AC-3) || 59 kW at 415...440 V AC 50/60 Hz (AC-3) || 75 kW at 500 V AC 50/60 Hz (AC-3) || 80 kW at 660...690 V AC 50/60 Hz (AC-3) || 65 kW at 1000 V AC 50/60 Hz (AC-3) || 18.5 kW at 400 V AC 50/60 Hz (AC-4) || 30 kW at 220...230 V AC 50/60 Hz (AC-3e) || 55 kW at 380...400 V AC 50/60 Hz (AC-3e) || 59 kW at 415...440 V AC 50/60 Hz (AC-3e) || 75 kW at 500 V AC 50/60 Hz (AC-3e) || 80 kW at 660...690 V AC 50/60 Hz (AC-3e) || 65 kW at 1000 V AC 50/60 Hz (AC-3e)
- [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
- [Icw] Rated Short-Time Withstand Current : 250 A 40 °C - 10 min for power circuit || 550 A 40 °C - 1 min for power circuit || 950 A 40 °C - 10 s for power circuit || 1100 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
- Heat Dissipation : 3-8 W at 60 Hz
- Protective Cover : with
- Specifications
- Country of Origin : Czechia
- Width : 120 mm
- Height : 158 mm
- Weight : 2.5 kg
- [Uc] Control Circuit Voltage : 480 V AC 60 Hz
- [Ue] Rated Operational Voltage : power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
- Range Of Product : TeSys Deca
- Contactor Application : motor control || resistive load
- Product Or Component Type : contactor
- Range : TeSys
- Utilisation Category : AC-3 || AC-1 || AC-4 || AC-3e
- [Ie] Rated Operational Current : 200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit || 115 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 115 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
- Poles Description : 3P
- Device Short Name : LC1D