IEC contactor, TeSys D, nonreversing, 115A, 75HP at 480VAC, 3 phase, 3 pole, 3 NO, 200VAC 50/60Hz coil, open style

IEC contactor, TeSys D, nonreversing, 115A, 75HP at 480VAC, 3 phase, 3 pole, 3 NO, 200VAC 50/60Hz coil, open style

SQDLC1D1156L7 LC1D1156L7 785901555223
523.95 / EA
  • Certifications: BV, CCC, CSA, DNV, GL, GOST, LROS (Lloyds Register Of Shipping), RINA, UKCA, UL
  • Contact Configuration: 3 NO
  • Contact Configuration: 1 NO + 1 NC
  • Depth: 136 mm
  • Height: 158 mm
  • Impedance: 0.6 MOhm - Ith 200 A 50 Hz Power Circuit
  • Net Weight: 2.5 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 508
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 120 mm
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. Contactor is supplied with a 200 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 115A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 30HP at 200 to 208VAC, 40HP at 240VAC, 75HP at 480VAC and 100HP at 600VAC three phase. Contactor is supplied with a 200 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Ring-lug screw terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 6.22 inches tall, 4.72 inches wide and 5.35 inches deep. It weighs 5.51 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Contractual warranty
    • Warranty : 18 months
  • Environment
    • Maximum Width : 120 mm
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor closed15 Gn for 11 ms || shocks contactor open6 Gn for 11 ms
    • Ambient Air Temperature For Storage : -60-80 °C
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Flame Retardance : V1 conforming to UL 94
    • Maximum Depth : 136 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Pollution Degree : 3
    • Net Weight : 2.5 kg
    • Maximum Height : 158 mm
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Fire Resistance : 850 °C IEC 60695-2-1
  • Offer Sustainability
    • Eu Rohs Directive : Compliant
    • Circularity Profile : ENVEOLI100405EN
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Rohs Exemption Information : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
    • Sustainable Offer Status : Green Premium product
    • Environmental Disclosure : ENVPEP060301EN
    • Pvc Free : Yes
    • Mercury Free : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
  • Complementary
    • Signalling Circuit Frequency : 25...400 Hz
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Inrush Power In Va : 280-350 VA 60 Hz 0.8 20 °C) || 280-350 VA 50 Hz 0.8 20 °C)
    • Coil Technology : built-in bidirectional peak limiting diode suppressor
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Hold-In Power Consumption In Va : 2-18 VA 60 Hz 0.3 20 °C) || 2-18 VA 50 Hz 0.3 20 °C)
    • Minimum Switching Voltage : 17 V signalling circuit
    • Minimum Switching Current : 5 mA signalling circuit
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Control Circuit Voltage Limits : 0.3...0.5 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.15 Uc -40-55 °C operational AC 50/60 Hz || 1...1.15 Uc 55-70 °C operational AC 50/60 Hz
    • Heat Dissipation : 3-8 W 50/60 Hz
  • Motor Power Kw : 30 kW 220...230 V AC 50/60 Hz AC-3) || 55 kW 380...400 V AC 50/60 Hz AC-3) || 59 kW 415...440 V AC 50/60 Hz AC-3) || 75 kW 500 V AC 50/60 Hz AC-3) || 80 kW 660...690 V AC 50/60 Hz AC-3) || 65 kW 1000 V AC 50/60 Hz AC-3) || 18.5 kW 400 V AC 50/60 Hz AC-4)
  • Associated Fuse Rating : 250 A gG <= 690 V type 1 power circuit || 200 A gG <= 690 V type 2 power circuit || 10 A gG signalling circuit
  • [Icw] Rated Short-Time Withstand Current : 250 A 40 °C - 10 min power circuit || 550 A 40 °C - 1 min power circuit || 950 A 40 °C - 10 s power circuit || 1100 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Overvoltage Category : III
  • Mounting Support : plate || rail
  • Mechanical Durability : 8 Mcycles
  • Control Circuit Type : AC 50/60 Hz
  • Device Short Name : LC1D
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Product Or Component Type : contactor
  • Irms Rated Making Capacity : 1260 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Utilisation Category : AC-3 || AC-4 || AC-1
  • Tightening Torque : control circuit 1.2 N.m lugs-ring terminals flat Ø 6 mm M3.5 || control circuit 1.2 N.m lugs-ring terminals Philips No 2 M3.5 || power circuit 12 N.m lugs-ring terminals hexagonal 13 mm M8 || power circuit 12 N.m bars hexagonal 13 mm M8
  • Maximum Operating Rate : 2400 cyc/h 60 °C
  • Pole Contact Composition : 3 NO
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Operating Time : 6...20 ms opening || 20...50 ms closing
  • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947
  • Product Certifications : CSA || DNV || UL || RINA || GL || GOST || BV || LROS (Lloyds register of shipping) || CCC || UKCA
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || UL 508
  • [Ue] Rated Operational Voltage : power circuit <= 1000 V AC 25...400 Hz || power circuit <= 300 V DC
  • Product Name : TeSys D
  • Protective Cover : with
  • Contactor Application : motor control || resistive load
  • Range : TeSys
  • Rated Breaking Capacity : 1100 A 440 V power circuit IEC 60947
  • [Ith] Conventional Free Air Thermal Current : 200 A 60 °C power circuit
  • [Ie] Rated Operational Current : 200 A 60 °C) <= 440 V AC AC-1 power circuit || 115 A 60 °C) <= 440 V AC AC-3 power circuit
  • Connections - Terminals : control circuit lugs-ring terminals 8 mm) || power circuit lugs-ring terminals 25 mm) || power circuit bars 1 5 x 25 mm
  • Electrical Durability : 0.8 Mcycles 200 A AC-1 <= 440 V || 0.95 Mcycles 115 A AC-3 <= 440 V
  • Power Dissipation Per Pole : 24 W AC-1 || 7.9 W AC-3
  • Maximum Horse Power Rating : 30 hp 200/208 V at AC 50/60 Hz for 3 phase || 40 hp 230/240 V at AC 50/60 Hz for 3 phase || 75 hp 460/480 V at AC 50/60 Hz for 3 phase || 100 hp 575/600 V at AC 50/60 Hz for 3 phase
  • [Ui] Rated Insulation Voltage : power circuit 600 V CSA || power circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1 || signalling circuit 600 V CSA || signalling circuit 600 V UL
  • Average Impedance : 0.6 mOhm - Ith 200 A 50 Hz power circuit
  • Poles Description : 3P
  • [Uc] Control Circuit Voltage : 200 V AC 50/60 Hz