IEC contactor, TeSys Deca, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style

TESYS D CTR, 65A, 24VDC LOW C

SQDLC1D65ABBE LC1D65ABBE 3606480987830
489.81 / EA
http://schema.org/OutOfStock
  • Country of Origin: USA
  • Depth: 120 mm
  • Height: 122 mm
  • Net Weight: 1.002 kg
  • Warranty Length: 18 mth
  • Weight: 1.002 kg
  • Width: 55 mm
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 65A/690V AC-3/3e (30kW@400V). They can be used to create motor starters for almost any type of application. It provides a low consumption 24V DC coil with electronic control, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by EverLink BTR screw connectors, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (55mm width), DIN-rail mounting or screw fixing. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic 24V DC coil, low consumption, for a direct control by a PLC output 24V DC / 500mA. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.21 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.
QTY
  • Product Description
  • Specifications
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 65A/690V AC-3/3e (30kW@400V). They can be used to create motor starters for almost any type of application. It provides a low consumption 24V DC coil with electronic control, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by EverLink BTR screw connectors, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (55mm width), DIN-rail mounting or screw fixing. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic 24V DC coil, low consumption, for a direct control by a PLC output 24V DC / 500mA. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.21 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.
  • Environment
    • Product Certifications : CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
    • Height : 122 mm
    • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
    • Climatic Withstand : IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
    • Net Weight : 1.002 kg
    • Flame Retardance : V1 conforming to UL 94
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Mechanical Robustness : vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor open 10 Gn for 11 ms) || shocks contactor closed 15 Gn for 11 ms)
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Width : 55 mm
    • Depth : 120 mm
    • Permissible Ambient Air Temperature Around The Device : -40-60 °C || 60-70 °C with derating
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP1607010EN
    • Halogen Content Performance : Halogen free plastic parts and cables product
    • Packaging Without Single Use Plastic : Yes
    • Scip Number : 9bb0b51e-73b5-4128-a86b-723dbbccfe86
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Circularity Profile : ENVEOLI1607010EN
    • Take-Back : No
    • Eu Rohs Directive : Compliant with Exemptions
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 39.312745204668914
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Current : 5 mA for signalling circuit
    • Power Dissipation Per Pole : 9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
    • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz for power circuit
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • [Ith] Conventional Free Air Thermal Current : 80 A (at 60 °C) for power circuit || 10 A (at 60 °C) for signalling circuit
    • Control Circuit Voltage Limits : <= 0.1 Uc (-40-70 °C):drop-out DC || 0.8...1.2 Uc (-40-60 °C):operational DC || 1...1.2 Uc (60-70 °C):operational DC
    • Mounting Support : rail || plate
    • Control Circuit Type : DC DC low consumption
    • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Pollution Degree : 3
    • Hold-In Power Consumption In W : 0.5-0.5 W 20 °C
    • Insulation Resistance : > 10 MOhm for signalling circuit
    • Rated Breaking Capacity : 1000 A at 440 V for power circuit conforming to IEC 60947
    • Irms Rated Making Capacity : 1000 A at 440 V for power circuit conforming to IEC 60947 || 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1
    • Associated Fuse Rating : 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit || 10 A gG for signalling circuit conforming to IEC 60947-5-1
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
    • Pole Contact Composition : 3 NO
    • Connections - Terminals : control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible without cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible without cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: solid
    • Coil Technology : built-in bidirectional peak limiting
    • Operating Time : 55...65 ms closing || 20...120 ms opening >= 17221) || 20...80 ms opening >= 18011)
    • Minimum Switching Voltage : 17 V for signalling circuit
    • Maximum Operating Rate : 3600 cyc/h at 60 °C
    • Signalling Circuit Frequency : 25...400 Hz
    • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || power circuit 5 N.m pozidriv No 2 || control circuit 1.7 N.m pozidriv No 2
    • Electrical Durability : 1.8 Mcycles 57 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V || 1.8 Mcycles 57 A AC-3e <= 440 V
    • Mechanical Durability : 6 Mcycles
    • Inrush Power In W : 11-11 W 20 °C)
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Compatibility Code : LC1D
    • Overvoltage Category : III
    • Maximum Horse Power Rating : 5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp at 575/600 V AC 60 Hz for 3 phase motors
    • Motor Power Kw : 18.5 kW at 220...230 V AC 50 Hz (AC-3) || 30 kW at 380...400 V AC 50 Hz (AC-3) || 37 kW at 415 V AC 50 Hz (AC-3) || 37 kW at 440 V AC 50 Hz (AC-3) || 37 kW at 500 V AC 50 Hz (AC-3) || 37 kW at 660...690 V AC 50 Hz (AC-3) || 18.5 kW at 220...230 V AC 50 Hz (AC-3e) || 30 kW at 380...400 V AC 50 Hz (AC-3e) || 37 kW at 415 V AC 50 Hz (AC-3e) || 37 kW at 440 V AC 50 Hz (AC-3e) || 37 kW at 500 V AC 50 Hz (AC-3e) || 37 kW at 660...690 V AC 50 Hz (AC-3e)
    • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
    • [Icw] Rated Short-Time Withstand Current : 110 A 40 °C - 10 min for power circuit || 260 A 40 °C - 1 min for power circuit || 640 A 40 °C - 10 s for power circuit || 900 A 40 °C - 1 s for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
    • Heat Dissipation : 0.5-0.5 W
    • Protective Cover : with
  • Specifications
    • Country of Origin : United States
    • Width : 55 mm
    • Height : 122 mm
    • Weight : 1.002 kg
    • [Uc] Control Circuit Voltage : 24 V DC
    • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz
    • Range Of Product : TeSys Deca
    • Contactor Application : motor control || resistive load
    • Product Or Component Type : contactor
    • Range : TeSys || TeSys Deca
    • Utilisation Category : AC-3 || AC-1 || AC-3e
    • [Ie] Rated Operational Current : 80 A (at <60 °C) at <= 440 V AC-1 for power circuit || 65 A (at <60 °C) at <= 440 V AC-3 for power circuit || 65 A (at <60 °C) at <= 440 V AC-3e for power circuit
    • Poles Description : 3P
    • Device Short Name : LC1D