IEC contactor, TeSys D Green, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style

IEC contactor, TeSys D Green, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24VDC coil, open style

SQDLC1D65ABBE LC1D65ABBE 785901765318
177.20 / EA
  • Certifications: CCC, CSA, DNV-GL, EAC, KC, LROS (Lloyds Register Of Shipping), UKCA, UL
  • Color: Gray SE GREY 6), Green SE GREEN 2)
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 80 A 50 Hz Power Circuit
  • Net Weight: 1.002 kg
  • Standard: CSA C22.2 No 60947-4-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic 24V DC coil, low consumption, for a direct control by a PLC output 24V DC / 500mA. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.21 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic 24V DC coil, low consumption, for a direct control by a PLC output 24V DC / 500mA. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.21 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Complementary
    • Inrush Power In W : 11-11 W 20 °C
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Current : 5 mA signalling circuit
    • Control Circuit Voltage Limits : <= 0.1 Uc -40-70 °C drop-out DC || 0.8...1.2 Uc -40-60 °C operational DC || 1...1.2 Uc 60-70 °C operational DC
    • Heat Dissipation : 0.5-0.5 W
    • Hold-In Power Consumption In W : 0.5-0.5 W 20 °C
    • Minimum Switching Voltage : 17 V signalling circuit
    • Coil Technology : built-in bidirectional peak limiting
    • Signalling Circuit Frequency : 25...400 Hz
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
  • Environment
    • Color : Gray SE GREY 6) || Green SE GREEN 2)
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Ambient Air Temperature For Storage : -60-80 °C
    • Flame Retardance : V1 conforming to UL 94
    • Net Weight : 1.002 kg
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Depth : 120 mm
    • Width : 55 mm
    • Protective Treatment : TH IEC 60068-2-30
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Pollution Degree : 3
    • Height : 122 mm
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Environmental Disclosure : ENVPEP1607010EN
    • Mercury Free : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Eu Rohs Directive : Compliant
    • Halogen Content Performance : Halogen free plastic parts & cables product
    • Sustainable Offer Status : Green Premium product
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Circularity Profile : ENVEOLI1607010EN
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
  • Mounting Support : rail || plate
  • Electrical Durability : 1.8 Mcycles 57 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz
  • [Uc] Control Circuit Voltage : 24 V DC
  • Product Certifications : CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping) || UKCA
  • Associated Fuse Rating : 125 A gG <= 690 V type 1 power circuit || 125 A gG <= 690 V type 2 power circuit || 10 A gG signalling circuit IEC 60947-5-1
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Mechanical Durability : 6 Mcycles
  • Product Name : TeSys D Green
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²solid || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²solid
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • Poles Description : 3P
  • Irms Rated Making Capacity : 1000 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • [Icw] Rated Short-Time Withstand Current : 110 A 40 °C - 10 min power circuit || 260 A 40 °C - 1 min power circuit || 520 A 40 °C - 10 s power circuit || 900 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Overvoltage Category : III
  • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
  • [Ith] Conventional Free Air Thermal Current : 80 A 60 °C power circuit || 10 A 60 °C signalling circuit
  • Motor Power Kw : 18.5 kW 220...230 V AC 50 Hz AC-3) || 30 kW 380...400 V AC 50 Hz AC-3) || 37 kW 415 V AC 50 Hz AC-3) || 37 kW 440 V AC 50 Hz AC-3) || 37 kW 500 V AC 50 Hz AC-3) || 37 kW 660...690 V AC 50 Hz AC-3)
  • Device Short Name : LC1D
  • Protective Cover : with
  • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz power circuit
  • Contactor Application : motor control || resistive load
  • Utilisation Category : AC-3 || AC-1
  • Product Or Component Type : contactor
  • Power Dissipation Per Pole : 9.6 W AC-1 || 6.3 W AC-3
  • Rated Breaking Capacity : 1000 A 440 V power circuit IEC 60947
  • Pole Contact Composition : 3 NO
  • Maximum Horse Power Rating : 5 hp 115 V at AC 60 Hz for 1 phase || 10 hp 230/240 V at AC 60 Hz for 1 phase || 20 hp 200/208 V at AC 60 Hz for 3 phase || 20 hp 230/240 V at AC 60 Hz for 3 phase || 40 hp 460/480 V at AC 60 Hz for 3 phase || 50 hp 575/600 V at AC 60 Hz for 3 phase
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm
  • Coil Type : DC low consumption
  • Operating Time : 55...65 ms closing || 20...120 ms opening >= 17221) || 20...80 ms opening >= 18011)
  • Range : TeSys
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
  • [Ie] Rated Operational Current : 80 A 60 °C) <= 440 V AC-1 power circuit || 65 A 60 °C) <= 440 V AC-3 power circuit
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Contractual warranty
    • Warranty : 18 months