IEC contactor, TeSys D Green, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24/60VAC/VDC coil, open

IEC contactor, TeSys D Green, nonreversing, 65A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 24/60VAC/VDC coil, open

SQDLC1D65ABNE LC1D65ABNE 785901765325
177.20 / EA
  • Certifications: CCC, CSA, DNV-GL, EAC, KC, LROS (Lloyds Register Of Shipping), UL
  • Color: Gray SE GREY 6), Green SE GREEN 2)
  • Contact Configuration: 1 NO + 1 NC
  • Contact Configuration: 3 NO
  • Depth: 120 mm
  • Height: 122 mm
  • Impedance: 1.5 MOhm - Ith 80 A 50 Hz Power Circuit
  • Net Weight: 1.002 kg
  • Standard: CSA C22.2 No 60947-4-1, EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1
  • Storage Temperature: -60-80 °C
  • Warranty Length: 18 mth
  • Width: 55 mm
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 24-60V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.21 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Product Description
  • Specifications
TeSys D Green contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Equipped with an electronic coil, wide band voltage 24-60V, AC/DC compatible, low consumption. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 2.21 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Complementary
    • Coil Technology : built-in bidirectional peak limiting
    • Minimum Switching Current : 5 mA signalling circuit
    • Inrush Power In W : 16-16 W 20 °C
    • Control Circuit Voltage Limits : <= 0.1 Uc -40-70 °C drop-out AC/DC || 0.85...1.1 Uc -40-60 °C operational AC || 0.8...1.1 Uc -40-60 °C operational DC || 1...1.1 Uc 60-70 °C operational AC/DC
    • Signalling Circuit Frequency : 25...400 Hz
    • Insulation Resistance : > 10 MOhm signalling circuit
    • Minimum Switching Voltage : 17 V signalling circuit
    • Heat Dissipation : 0.7-0.7 W 50/60 Hz
    • Hold-In Power Consumption In W : 0.7-0.7 W 20 °C
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Hold-In Power Consumption In Va : 1-1 VA 20 °C) 50/60 Hz
    • Inrush Power In Va : 15-15 VA 50/60 Hz 20 °C)
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
  • Protective Cover : with
  • Mounting Support : rail || plate
  • Connections - Terminals : control circuit screw clamp terminals 1 1-4 mm²flexible without cable end || control circuit screw clamp terminals 2 1-4 mm²flexible without cable end || control circuit screw clamp terminals 1 1-4 mm²flexible with cable end || control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end || control circuit screw clamp terminals 1 1-4 mm²solid || control circuit screw clamp terminals 2 1-4 mm²solid || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible without cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²flexible with cable end || power circuit EverLink BTR screw connectors 1 1-35 mm²solid || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible without cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²flexible with cable end || power circuit EverLink BTR screw connectors 2 1-25 mm²solid
  • Mechanical Durability : 6 Mcycles
  • Maximum Operating Rate : 3600 cyc/h 60 °C
  • Overvoltage Category : III
  • Coil Type : AC/DC electronic
  • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
  • [Ui] Rated Insulation Voltage : power circuit 690 V IEC 60947-4-1 || signalling circuit 690 V IEC 60947-1
  • Product Certifications : CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping)
  • Power Dissipation Per Pole : 9.6 W AC-1 || 6.3 W AC-3
  • Operating Time : 55...65 ms closing || 20...120 ms opening >= 17221) || 20...80 ms opening >= 18011)
  • Pole Contact Composition : 3 NO
  • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm
  • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz power circuit
  • Utilisation Category : AC-3 || AC-1
  • Contactor Application : motor control || resistive load
  • [Icw] Rated Short-Time Withstand Current : 110 A 40 °C - 10 min power circuit || 260 A 40 °C - 1 min power circuit || 520 A 40 °C - 10 s power circuit || 900 A 40 °C - 1 s power circuit || 100 A - 1 s signalling circuit || 120 A - 500 ms signalling circuit || 140 A - 100 ms signalling circuit
  • Range : TeSys
  • Auxiliary Contact Composition : 1 NO + 1 NC
  • Associated Fuse Rating : 125 A gG <= 690 V type 1 power circuit || 125 A gG <= 690 V type 2 power circuit || 10 A gG signalling circuit IEC 60947-5-1
  • [Ith] Conventional Free Air Thermal Current : 80 A 60 °C power circuit || 10 A 60 °C signalling circuit
  • Product Name : TeSys D Green
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
  • [Uc] Control Circuit Voltage : 24...60 V AC 50/60 Hz || 24...60 V DC
  • Irms Rated Making Capacity : 1000 A 440 V power circuit IEC 60947 || 140 A AC signalling circuit IEC 60947-5-1 || 250 A DC signalling circuit IEC 60947-5-1
  • Product Or Component Type : contactor
  • Poles Description : 3P
  • [Ue] Rated Operational Voltage : power circuit <= 690 V AC 25...400 Hz
  • Maximum Horse Power Rating : 5 hp 115 V at AC 60 Hz for 1 phase || 10 hp 230/240 V at AC 60 Hz for 1 phase || 20 hp 200/208 V at AC 60 Hz for 3 phase || 20 hp 230/240 V at AC 60 Hz for 3 phase || 40 hp 460/480 V at AC 60 Hz for 3 phase || 50 hp 575/600 V at AC 60 Hz for 3 phase
  • [Ie] Rated Operational Current : 80 A 60 °C) <= 440 V AC-1 power circuit || 65 A 60 °C) <= 440 V AC-3 power circuit
  • Motor Power Kw : 18.5 kW 220...230 V AC 50 Hz AC-3) || 30 kW 380...400 V AC 50 Hz AC-3) || 37 kW 415 V AC 50 Hz AC-3) || 37 kW 440 V AC 50 Hz AC-3) || 37 kW 500 V AC 50 Hz AC-3) || 37 kW 660...690 V AC 50 Hz AC-3)
  • Rated Breaking Capacity : 1000 A 440 V power circuit IEC 60947
  • Electrical Durability : 1.8 Mcycles 57 A AC-3 <= 440 V || 0.5 Mcycles 80 A AC-1 <= 440 V
  • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
  • Device Short Name : LC1D
  • Environment
    • Color : Gray SE GREY 6) || Green SE GREEN 2)
    • Maximum Depth : 120 mm
    • Net Weight : 1.002 kg
    • Ambient Air Temperature For Operation : -40-60 °C || 60-70 °C with derating
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Ambient Air Temperature For Storage : -60-80 °C
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
    • Flame Retardance : V1 conforming to UL 94
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Protective Treatment : TH IEC 60068-2-30
    • Maximum Height : 122 mm
    • Pollution Degree : 3
    • Maximum Width : 55 mm
  • Offer Sustainability
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Eu Rohs Directive : Compliant
    • Rohs Exemption Information : Yes
    • Halogen Content Performance : Halogen free plastic parts & cables product
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1607010EN
    • Circularity Profile : ENVEOLI1607010EN
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Sustainable Offer Status : Green Premium product
  • Contractual warranty
    • Warranty : 18 months