SIL interface module, TeSys island, 24VDC, Isolated switching input for safe stop

TeSys Island�SIL Interface

SQDTPRSM001 TPRSM001 3606489832872
348.16 / EA
http://schema.org/OutOfStock
  • Country of Origin: Indonesia
  • Depth: 114 mm
  • Height: 118 mm
  • Input Voltage: 28.8 V, 5 V
  • Net Weight: 0.159 kg
  • Warranty Length: 18 mth
  • Weight: 0.159 kg
  • Width: 25 mm
TeSys island SIL interface module, 2 inputs, 1 output. Connected to a TPRBC bus coupler, it allows integration into safety related systems conforming to ISO 13849-1. It is used in connection to one or several SIL motor starter TPRSS. Two isolated switching inputs with common point, 0-24V DC. One relay type output, 1NO, instantaneous opening, potential free. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC).
QTY
  • Product Description
  • Features
  • Specifications
TeSys island SIL interface module, 2 inputs, 1 output. Connected to a TPRBC bus coupler, it allows integration into safety related systems conforming to ISO 13849-1. It is used in connection to one or several SIL motor starter TPRSS. Two isolated switching inputs with common point, 0-24V DC. One relay type output, 1NO, instantaneous opening, potential free. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC).
  • Prop 65
    • WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
  • Environment
    • Ambient Air Temperature For Operation : -10-60 °C
    • Shock Resistance : 15 gn 11 ms) IEC 60068-2-27
    • Vibration Resistance : 1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
    • Electromagnetic Compatibility : electrostatic discharge, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF fields, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test, level 3, 2 kV, conforming to EN/IEC 61000-4-4 || surge immunity test (common mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5
    • Pollution Degree : 2
    • Ambient Air Temperature For Storage : -25-70 °C
    • Protective Treatment : TC
    • Relative Humidity : 5-95 %
    • Ip Degree Of Protection : IP20
    • Operating Altitude : 0...6561.68 ft (0...2000 m) without derating
    • Fire Resistance : 960 °C UL 94
  • Contractual warranty
    • Warranty : 18 months
  • Environmental data
    • Rohs Exemption Information : Yes
    • Packaging Made With Recycled Cardboard : Yes
    • Mercury Free : Yes
    • Halogen Content Performance : Halogen free plastic parts product
    • Packaging Without Single Use Plastic : No
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Scip Number : b164c55a-185e-47e2-96d5-e03c25b77067
    • California Proposition 65 : WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
    • Circularity Profile : ENVEOLI1904009EN
    • Take-Back : No
    • Sustainable Packaging : No
    • Eu Rohs Directive : Compliant with Exemptions
  • Complementary
    • Mounting Mode : horizontal and vertical 35 mm symmetrical rail)
    • Current Consumption : 10 mA
    • [Us] Rated Supply Voltage : 24 V DC supplied by the bus coupler
    • Height : 118 mm
    • Product Certifications : UL || CSA || EAC (pending)
    • Standards : IEC 60947-5-1 || UL 60947-5-1
    • Connections - Terminals : control circuit removable spring terminal block 5 0.2-2.5 mm² AWG 24...AWG 14)rigid || control circuit removable spring terminal block 5 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit removable spring terminal block 5 0.25-2.5 mm² AWG 22...AWG 14)flexible with cable end
    • Power Dissipation In W : 0.7 W maximum
    • Net Weight : 0.159 kg
    • Safety Function : safe stop: category 0 conforming to IEC 60204-1 || safe stop: category 1 conforming to IEC 60204-1
    • Width : 25 mm
    • Depth : 114 mm
    • Safety Level : SIL 2 conforming to IEC 61508 in single channel system architecture || SILCL 2 conforming to IEC 62061 in single channel system architecture || PL = d category 2 conforming to ISO 13849-1 in single channel system architecture
  • Specifications
    • Country of Origin : Indonesia
    • Width : 25 mm
    • Height : 118 mm
    • Weight : 0.159 kg
    • [Ue] Rated Operational Voltage : input/output circuit 24 V DC
    • Output Thermal Current : 8 A relay output
    • Protection Type : external fuse, 8 A gG relay output
    • Product Or Component Type : SIL interface module
    • Product Name : TeSys island
    • Range : TeSys
    • Input Type : isolated switching input safe stop
    • Device Presentation : implementation of a safe stop function for SIL motor starters TPRSS || safe stop operable for safety-related system conforming to ISO 13849-1 || operational only when connected to a bus coupler TPRBC
    • Output Type : relay instantaneous opening, 1 NO, potential free
    • Product Compatibility : TPRBC bus coupler || TPRSS SIL motor starter
    • Input Voltage : 15...28.8 V DC state 1 || 0...5 V DC state 0
    • Local Signalling : 1 LED (green/red) for DS (device status) || 1 LED (green/red) for SS (safe stop status)
    • Input Protection Type : internal, electronic
    • Function Of Module : safe stop with 1NC or 2NC contacts monitoring
    • Overvoltage Category : III
    • [Uimp] Rated Impulse Withstand Voltage : 2 kV input/output circuit IEC 60947-1
    • [Ui] Rated Insulation Voltage : input/output circuit 50 V
    • Device Short Name : TPRSM