PowerPacT Q-Frame circuit breakers are used for overcurrent protection and switching on 240VAC systems. They are rated for 240VAC operational voltage and provide thermal magnetic trip protection. PowerPacT Q circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. This unit has terminal nuts on the line side and lugs on the load side. It has studs on line end with nuts and washers. This PowerPacT Q, 150A, 2 pole, circuit breaker has an interrupting rating of 10kA at 208Y/120VAC and 240VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT Q circuit breakers comply to UL, CSA, and NOM standards and are IEC certified.
- Environment
- Ambient Air Temperature For Operation : 40-70 °C
- Standards : UL || CSA || NEMA || NOM-003-SCFI-2000
- Product Certifications : UL || CSA || NOM
- Contractual warranty
- Offer Sustainability
- Rohs Exemption Information : Yes
- Mercury Free : Yes
- Environmental Disclosure : ENVPEP1406032EN
- Sustainable Offer Status : Green Premium product
- Pvc Free : Yes
- Reach Regulation : Reference contains Substances of Very High Concern above the threshold
- China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile : N/A
- Eu Rohs Directive : Compliant with Exemptions
- Halogen Content Performance : Halogen free product
- Complementary
- Mounting Mode : unit mount lug)
- Network Frequency : 50/60 Hz
- Trip Unit Technology : thermal-magnetic
- Height : 6.47 in
- [Ue] Rated Operational Voltage : 240 V AC 50/60 Hz UL
- Tightening Torque : 28-28 N.m 25-150 mm² (AWG 4...300 kcmil)
- Mounting Support : lug
- Breaking Capacity Code : B
- Magnetic Tripping Current : 2400-2400 A
- Local Signalling : 1 trip indicator green)
- Electrical Connection : terminal nut, line || lugs, load
- [Uimp] Rated Impulse Withstand Voltage : 8 kV UL
- Magnetic Hold Current : 1200 A
- Control Type : operating handle
- Circuit Breaker Application : HACR rated
- Wire Stripping Length : 22 mm
- Utilisation Category : category A
- Line Rated Current : 150-150 A
- Continuous Current Rating : 80 %
- Breaking Capacity : 10 kA 120/208 V AC 50/60 Hz UL || 10 kA 240 V AC 50/60 Hz UL
- Mechanical Durability : 1000 cycles loaded || 5000 cycles no load
- Poles Description : 2P
- Line Rated Current : 150 A
- Width : 3.00 in
- Depth : 3.93 in
- Specifications
- Product Or Component Type : circuit breaker
- Product Name : PowerPact Q
- Range : PowerPact
- Device Application : distribution