PowerPact B Circuit Breaker, 40A, 3P, 600Y/347V AC, 14kA at 600Y/347 UL, I-Line

PowerPact B Circuit Breaker, 40A, 3P, 600Y/347V AC, 14kA at 600Y/347 UL, I-Line

SQDBDA36040 BDA36040 3606481152596
1012.00 / EA
  • Amperage: 40 A
  • Certifications: CCC, CSA, EAC, IEC, NOM, UL
  • Country of Origin: Mexico
  • Depth: 3.50 in, 89 mm
  • Height: 137 mm, 5.39 in
  • Mounting Type: I-Line
  • Number of Poles: 3
  • Standard: CSA C22.2 No 5, EN/IEC 60947-2, EN/IEC 60947-5-1, GB 14048.2, NEMA AB1, NMX J-266, UL 489
  • Voltage: 525 V
  • Weight: 1.315 kg, 2.90 lb
  • Width: 3.19 in, 81 mm
PowerPact B-frame circuit breaker, offers proven performance, flexibility, and reliability. This PowerPact Molded Case Circuit Breaker feature new innovations such as the patented EverLink™ connections. PowerPact B-frame circuit breakers provides economical thermal magnetic circuit protection with a breaking capacity of 25kA at 220/240 VAC, 50/60 Hz. PowerPact B-frame circuit breakers come in 1 to 4-pole unit mount construction also 1 to 3-pole I-Line construction. This PowerPact B, 40 A, 3P, circuit breaker has a breaking capacity of 14kA@600Y/347VAC@50/60 Hz per UL 489 standards. This circuit breaker has a thermal-magnetic trip unit technology with a mechanical service life of 20000 cycles and an electrical service life of 10000 cycles@440V. This I-Line breaker has a presence of auxiliary contacts green signaling function. The I-Line lug can accept an AWG gauge AWG 14 / AWG 2/0, aluminum/copper. This breaker complies to UL, IEC, CCC, EAC, CSA, NOM standards Powerpact B-Frame breakers have an operating altitude test condition of 2000 m without derating and a 5000 m with derating. Dimensions for this product are 137 mm (H),81 mm (W),89 mm (D) and a weight of 1.315kg. This breaker has a continuous current rating of 80% with an ABC phase connection.
  • Product Description
  • Specifications
PowerPact B-frame circuit breaker, offers proven performance, flexibility, and reliability. This PowerPact Molded Case Circuit Breaker feature new innovations such as the patented EverLink™ connections. PowerPact B-frame circuit breakers provides economical thermal magnetic circuit protection with a breaking capacity of 25kA at 220/240 VAC, 50/60 Hz. PowerPact B-frame circuit breakers come in 1 to 4-pole unit mount construction also 1 to 3-pole I-Line construction. This PowerPact B, 40 A, 3P, circuit breaker has a breaking capacity of 14kA@600Y/347VAC@50/60 Hz per UL 489 standards. This circuit breaker has a thermal-magnetic trip unit technology with a mechanical service life of 20000 cycles and an electrical service life of 10000 cycles@440V. This I-Line breaker has a presence of auxiliary contacts green signaling function. The I-Line lug can accept an AWG gauge AWG 14 / AWG 2/0, aluminum/copper. This breaker complies to UL, IEC, CCC, EAC, CSA, NOM standards Powerpact B-Frame breakers have an operating altitude test condition of 2000 m without derating and a 5000 m with derating. Dimensions for this product are 137 mm (H),81 mm (W),89 mm (D) and a weight of 1.315kg. This breaker has a continuous current rating of 80% with an ABC phase connection.
  • Ordering And Shipping Details
    • Nbr. Of Units In Pkg. : 1
    • Discount Schedule : DE2
    • GTIN : 03606481152596
    • Category : 01133 - BDA I-LINE BREAKER
    • Country Of Origin : MX
    • Returnability : Yes
  • Main
    • Product Name : PowerPact B
    • Device Short Name : BD 040
    • Range : PowerPact
    • Product Or Component Type : Circuit breaker
    • Device Application : Distribution
  • Environment
    • IK Degree Of Protection : IK07 conforming to IEC 62262
    • Operating Altitude : < 6561.68 ft (2000 m) without derating || 5000 m with derating
    • Ambient Air Temp For Op : -13…158 °F (-25…70 °C)
    • Quality Labels : CE
    • Product Certifications : UL || IEC || CCC || EAC || CSA || NOM
    • Pollution Degree : 3 conforming to IEC 60947-1
    • IP Degree Of Protection : Front cover IP40 IEC 60529
    • Ambient Air Temp For Storage : -58…185 °F (-50…85 °C)
    • Standards : EN/IEC 60947-5-1 || NMX J-266 || GB 14048.2 || NEMA AB1 || EN/IEC 60947-2 || UL 489 || CSA C22.2 No 5
  • Complementary
    • Connection Pitch : 1.06 in (27 mm)
    • Trip Unit Technology : Thermal-magnetic
    • Power Wire Stripping Length : 0.79 in (20 mm)
    • Product Weight : 2.90 lb(US) (1.315 kg)
    • Number Of Slots : 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in) || 1 alarm switch SD plug-in)
    • Breaking Capacity : 25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600Y/347 V AC 50/60 Hz UL 489 || 10 kA 250 V DC UL 489
    • Phase Connection : ABC
    • Tightening Torque : 31.86…38.94 lbf.in (3.6…4.4 N.m) 0.00…0.01 in² (2.5…6 mm²) AWG 14...AWG 10) || 44.25…54.87 lbf.in (5…6.2 N.m) 0.02…0.11 in² (10…70 mm²) AWG 8...AWG 2/0)
    • Local Signalling : Presence of auxiliary contacts flag green)
    • Mechanical Durability : 20000 cycles IEC 947-1 Annex K ed 5.2
    • Ui Rated Insulation Voltage : 800 V conforming to IEC 60947-2
    • 9 mm Pitches : 9
    • Utilisation Category : Category A
    • Mounting Height : 4.49 in (114 mm)
    • Uimp Rated Imp Wstd Voltage : 8 kV IEC 60947-2
    • Color : Grey (RAL 7016)
    • Mounting Mode : I-Line
    • Number Of Poles : 3P
    • Rating Code : D
    • Electrical Connection : I-Line connection line || Lugs load
    • Electrical Durability : 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
    • Height : 5.39 in (137 mm)
    • Suitability For ISOlation : Yes conforming to IEC 60947-2
    • Awg Gauge : AWG 14...AWG 2/0 aluminium/copper
    • Depth : 3.50 in (89 mm)
    • Width : 3.19 in (81 mm)
    • Continuous Current Rating : 80 %
    • In Rated Current : 40 A
    • Quantity Per Set : Set of 1
    • Ue Rated Operational Voltage : 525 V AC 50/60 Hz UL 489
    • Ics Rated Service Breaking Cap : 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 || 18 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    • Control Type : Toggle
  • Offer Sustainability
    • Pvc Free : Yes
    • Green Premium Status : Green Premium product
    • EU RoHs Directive : Compliant
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Mercury Free : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Halogen Content Performance : Halogen free product