PowerLogic P5T30 48-250V 6CT 2Io 1VT 28DI-12DO Eth HSR/PRP 2*LC RS485 Backup ANSI

PowerLogic P5T30 48-250V 6CT 2Io 1VT 28DI-12DO Eth HSR/PRP 2*LC RS485 Backup ANSI

SQDREL50536 REL50536 3606487713678
11142.31 / EA
http://schema.org/OutOfStock
  • Depth: 219 mm
  • Display Type: Colour LCD 480 X 272 Pixels
  • Height: 6.93 in
  • Input Voltage: ...230 V, ...240 V
  • Number of Outputs: 11 DO1 Watchdog
  • Warranty Length: 10 yr, 2 yr
  • Width: 5.98 in
QTY
  • Features
  • Specifications
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Communications & Management Attributes
    • Communication Port Protocol : IEC 61850 ed. 1, IEC 61850 ed. 2, DNP3 over ethernet, Modbus TCP, EtherNet/IP, Modbus RTU, DNP3 RTU, IEC 60870-5-103, IEC 60870-5-101
    • Redundancy Communication Port Protocol : HSR, PRP
  • Physical Attributes
    • Mounting Case Size : 30TE
  • Complementary Attributes
    • Integrated Connection Type : rear RJ45 2, rear extension port 1 with backup memoryfront USB port 2, rear LC 2
  • Important Information Attributes
    • Control Type : switchgear control and monitoring, programmable switchgear interlocking, local/remote control
    • Cybersecurity : port hardening, firmware signature, client IP address filter, secured communication with assciated tools, security policy management, role-based access control, security log, LDAP, RADIUS based user authentication, IEC 62443-4-2 SL1
    • Electromagnetic Compatibility : EMC immunity IACS E10emission tests class A CISPR 11, emission tests class A CISPR 32, emission tests IACS E10, EMC immunity class 4 IEC 61000-4-2, EMC immunity class 4 ANSI C37.90.3EMC immunity level 3 IEC 61000-4-3, EMC immunity ANSI C37.90.2, EMC immunity GOST 32137, EMC immunity GOST 30804.4.3EMC immunity level 5 IEC 61000-4-8, EMC immunity level 5 IEC 61000-4-9, EMC immunity level 5 IEC 61000-4-10, EMC immunity level 3 IEC 61000-4-6, EMC immunity level 3 IEC 61000-4-18, EMC immunity ANSI C37.90.1, EMC immunity IEC 61000-4-12, EMC immunity GOST 30804.4.12EMC immunity level 4 IEC 61000-4-16, EMC immunity level 4 IEC 61000-4-4, EMC immunity level 4 IEC 61000-4-5
    • Environmental Characteristic : influence of corrosion/gas test 4 IEC 60721-3-3, exposure to cold IEC 60068-2-1exposure to dry heat IEC 60068-2-2exposure to damp heat in service IEC 60068-2-78, exposure to damp heat in service IEC 60068-2-30temperature variation IEC 60068-2-14salt mist IEC 60068-2-52influence of corrosion/gas test 2 IEC 60068-2-60, influence of corrosion/gas test 4 IEC 60068-2-60, influence of corrosion/gas test 2 IEC 60721-3-3
    • Local Signalling : 4 x LED, 10 x LED tri-colour programmable
    • Mechanical Robustness : vibrations class 2) IEC 60255-21-1, vibrations GOST 17516.1, vibrations IACS E10shocks class 2) IEC 60255-21-2earthquakes class 2) IEC 60255-21-3
    • Monitoring Function : trip circuit supervision 74, circuit breaker monitoring, relay self-monitoring
    • Network And Machine Diagnosis Type : event recording, disturbance recording, tripping context, relay maintenance
    • Protection Type : two-winding transformer differential 87Toverfluxing (V/Hz) 24phase overcurrent 50/51earth fault overcurrent 50N/51Ndirectional earth fault 67Nthermal overload for transformer 49Fthermostat / buchholz 26/63restricted earth fault 64REFcurrent unbalance 46BC, broken conductor 46BC, H2 detectionbreaker failure 50BFnegative sequence overcurrent 46earth fault overvoltage 59Nlockout relay 86programmable stages 99, programmable logic, programmable curve
    • Time Synchronisation Protocol : SNTP, PTP
    • Type Of Measurement : current 3-phase, current zero sequence, current positive sequence, current negative sequence, current ratio of negative and positive, current phasor diagram view, current 2nd, 15th harmonics with THDvoltage 1-phase, voltage residual, frequency
    • Carbon Footprint Of The Distribution Phase [A4] : 0.6322139, 0.6 kg CO2 eq.
    • Carbon Footprint Of The End-of-life Phase [C1 To C4] : 2 kg CO2 eq., 2.3044611411
    • Carbon Footprint Of The Installation Phase [A5] : 0.0575919699, 0.1 kg CO2 eq.
    • Carbon Footprint Of The Manufacturing Phase [A1 To A3] : 186 kg CO2 eq., 186.3587696642
    • Carbon Footprint Of The Use Phase [B2, B3, B4, B6] : 329 kg CO2 eq., 329.4131313014
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-11-13
    • Pre Comm Date : 2025-06-06
    • Return Indicator : N
    • Stocking Flag : Y
    • Stock Policy : 2
    • Device Type : Relay, Control & Measurement - Protection relay
    • Weee Scope : In
    • Weee Product Category : 5
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI1901010_V2
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 2448
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : Yes
    • China Rohs Label : 4
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : No
    • Product Contributes To Saved And Avoided Emissions : No
    • Product Kit Identifier : N
    • Arc Flash Protection : no
    • Device Short Name : P5T30-EACE-JAHHH-BAEK
    • Display Type : colour LCD 480 x 272 pixels
    • Mounting Mode : withdrawable
    • Number Of Key : 7 customizable
    • Number Of Sensors : 0 temperature sensor(s)
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Or Component Type : protection and control relay
    • Protective Treatment : conformal coating conforming to IEC 60068-2-52:Kb/1conformal coating conforming to IEC 60068-2-60:Keconformal coating conforming to IEC 60721-3-3:3C2
    • Range Of Product : PowerLogic P5
    • Relay Application : transformer differential
    • Returnability : No
    • Setting : 4
    • Single Line Diagram : 8 controlled + 2 monitored objects
    • Software Name : eSetup Easergy Pro virtual simulation testEcoStruxure Power Device configuration
    • Software Version : EIME v5.6.0.1
    • Sustainable Packaging : No
    • Switchgear Diagnosis Type : CT supervision 60
    • Total Lifecycle Carbon Footprint : 519 kg CO2 eq.
    • Web Server : embedded web page
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Pep Code : ENVPEP1901010EN
    • Database Version : 2016-11
    • Pep Verification Date : 2022-08-01
    • Pcr Version : PCR-ed3-EN-2015 04 02
    • Psr Version : PSR-0005-ed2-EN-2016 03 29
    • Type Of Verification For The Pep : Independent internal review
    • Data Source : extrapolated product
    • Functional-unit Description : Protect distribution and transmission networks and high voltage equipment (typically from 1 to 500 KV) like feeder, transformer, motor and generator against faults, (short circuit, over load …) 24h per day, 7 days on 7.& 10Calculations done in this document for LCA use a period of 10 years of operations, in Europe environmental conditions. This time is not representative of the effective lifetime of PowerLogic P5 protection relays, which is more than 10 years.
    • Functional-unit Quantity : 1
    • Functional-unit Unit : unit
    • Reference Lifetime, In Y : 10
    • Energy Model - Manufacturing [A1-a3] : Energy model used: France
    • Energy Model - Installation [A5] : Electricity mix; AC; < 1kV; EU-27
    • Energy Model - Use [B6] : Electricity mix; AC; < 1kV; EU-27
    • Energy Model - End Of Life [C1-c4] : Electricity mix; AC; < 1kV; EU-27
    • Recyclability Potential, In % : 27
    • Height Nominal : 176 mm
    • Height Useful : 176 mm
    • Width Nominal : 152 mm
    • Width Real : 152 mm
    • [Us] Rated Supply Voltage : 48...250 V DC100...230 V AC
    • Connections - Terminals : pin terminal (digital input/output)ring lugs (analog inputs and outputs)
    • Nbr. Of Units In Pkg. : 1
    • Package Weight(Lbs) : 4.9 kg
    • Take-back : No
    • Warranty (In Months) : 18
    • Customs Code : 8537109170
  • Environment Attributes Main
    • Ambient Air Temperature For Operation : -40-85 °C 16 h ), -40-85 °C 16 h ), -40-70 °C 96 h ), -40-70 °C 96 h )-40-85 °C 16 h ), -40-85 °C 16 h ), -40-70 °C 96 h )
    • Take Back : No
    • Recycled Metal Content At Cr Level : 0 %
    • China Rohs Regulation : X
    • Mercury Free : Yes
    • Carbon Footprint : 518.7661679766
    • Ambient Air Temperature For Storage : -40-85 °C-40-85 °C
    • Circularity Profile : ENVEOLI1901010_V2
    • Environmental Disclosure : ENVPEP1901010EN
    • Eu Rohs Directive : Compliant By Exemption
    • Ip Degree Of Protection : IP54 IEC 60529
    • Operating Altitude : 6561.68 ft (2000 m)
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : No
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Relative Humidity : 0-93 % at 40-40 °C, without condensation, 56 days93-95 % at 25-55 °C, 6 cycles, 12 + 12 hours
    • Pep Code : ENVPEP1901010EN
    • Pep Verification Date : 2022-08-01
    • Pcr Version : PCR-ed3-EN-2015 04 02
    • Psr Version : PSR-0005-ed2-EN-2016 03 29
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : protection and control relay
    • Range Of Product : PowerLogic P5
  • Output Attributes
    • Analogue Output Number : 0
    • Number Of Outputs : 11 DO1 watchdog
  • Contractual Warranty Attributes
    • Warranty Period : up to 10 years (Standard warranty 2 years. Please check with your local SE representative for extended warranty availability and conditions)
    • Warranty : up to 10 years (Standard warranty 2 years. Please check with your local SE representative for extended warranty availability and conditions)
  • Input Attributes
    • Input Type : 6 1/5 A CT phase current2 1/5 A CT residual current, 1 VT voltage
    • Analogue Input Number : 0
    • Digital Input Number : 28
    • Input Voltage : digital input 24...240 V DCdigital input 100...230 V AC
  • Specifications
    • Country of Origin : France, Latvia
    • Height : 6.93 in
    • Width : 5.98 in
    • Depth : 219 mm