  • Country of Origin: Latvia
  • Depth: 219 mm
  • Display Type: LCD 480 X 272 Pixels
  • Height: 6.93 in
  • Number of Outputs: 7 DO, 1 Watchdog
  • Warranty Length: 10 yr, 2 yr
  • Width: 5.98 in
QTY
  • Features
  • Specifications
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Communications & Management Attributes
    • Communication Port Protocol : IEC 61850 ed. 1, IEC 61850 ed. 2, DNP3 over ethernet, Modbus TCP, EtherNet/IP
    • Redundancy Communication Port Protocol : RSTP
  • Physical Attributes
    • Mounting Case Size : 30TE
  • Complementary Attributes
    • Integrated Connection Type : rear RJ45 2, rear extension port 1 with backup memory, front USB port 2
  • Important Information Attributes
    • Control Type : switchgear control and monitoring, programmable switchgear interlocking, local/remote control, 2 function keys, programmable logic
    • Cybersecurity : port hardening, firmware signature, client IP address filter, secured communication with assciated tools, security policy management, role-based access control, security log, LDAP, RADIUS based user authentication, IEC 62443-4-2 SL1
    • Electromagnetic Compatibility : EMC immunity IACS E10emission tests class A CISPR 11, emission tests class A CISPR 32, emission tests IACS E10, EMC immunity class 4 IEC 61000-4-2, EMC immunity class 4 ANSI C37.90.3, EMC immunity level 3 IEC 61000-4-3, EMC immunity ANSI C37.90.2, EMC immunity GOST 32137, EMC immunity GOST 30804.4.3, EMC immunity level 5 IEC 61000-4-8, EMC immunity level 5 IEC 61000-4-9, EMC immunity level 5 IEC 61000-4-10, EMC immunity level 3 IEC 61000-4-6, EMC immunity level 3 IEC 61000-4-18, EMC immunity ANSI C37.90.1, EMC immunity IEC 61000-4-12, EMC immunity GOST 30804.4.12, EMC immunity level 4 IEC 61000-4-16, EMC immunity level 4 IEC 61000-4-4, EMC immunity level 4 IEC 61000-4-5
    • Environmental Characteristic : influence of corrosion/gas test 4 IEC 60721-3-3exposure to cold IEC 60068-2-1, exposure to dry heat IEC 60068-2-2, exposure to damp heat in service IEC 60068-2-78, exposure to damp heat in service IEC 60068-2-30, temperature variation IEC 60068-2-14, salt mist IEC 60068-2-52, influence of corrosion/gas test 2 IEC 60068-2-60, influence of corrosion/gas test 4 IEC 60068-2-60, influence of corrosion/gas test 2 IEC 60721-3-3
    • Local Signalling : 4 x LED, 10 x LED tri-colour programmable
    • Mechanical Robustness : vibrations class 2) IEC 60255-21-1, vibrations GOST 17516.1, vibrations IACS E10, shocks class 2) IEC 60255-21-2, earthquakes class 2) IEC 60255-21-3
    • Monitoring Function : trip circuit supervision 74, circuit breaker monitoring, relay self-monitoring
    • Network And Machine Diagnosis Type : event recording, disturbance recording, tripping context, relay maintenance
    • Protection Type : phase overcurrent 50/51, directional phase overcurrent 67, earth fault overcurrent 50N/51N, directional earth fault 67N, transient earth fault 67NI, capacitor bank unbalance 51C, broken conductor 46 I2/I1, cold load pick-up 64REF, switch ON to fault (SOTF) 51C, breaker failure 50BF, directional active underpower 37P, fault locator 21FL, recloser 79, restricted earth fault 64REF, earth fault wattmetric 32N, neutral admittance 21YN, negative sequence overcurrent 46, overvoltage 59, undervoltage 27, earth fault overvoltage 59N, overfrequency 81/81N, underfrequency 81/81N, rate of change of frequency 81R, synchro-check 25, lockout relay 86, CT supervision 60, VT supervision 60, H2 detection 68H2, H5 detection 68H5, negative sequence overcurrent 47, programmable stages 99, programmable curve 99, programmable logic
    • Protective Treatment : conformal coating conforming to IEC 60068-2-52:Kb/1, conformal coating conforming to IEC 60068-2-60:Ke, conformal coating conforming to IEC 60721-3-3:3C2
    • Switchgear Diagnosis Type : CT supervision 60, VT supervision 60, trip circuit supervision 74
    • Type Of Measurement : voltage positive sequence, voltage negative sequence, voltage 3-phase, current phasor diagram viewcurrent 3-phase, current zero sequence, current positive sequence, current negative sequence, current ratio of negative and positive, voltage zero sequence, voltage residual, frequency, voltage phasor diagram view, current 2nd, 15th harmonics with THD
    • Connections - Terminals : pin terminal (digital input/output), ring lugs (analog inputs and outputs)
    • Carbon Footprint Of The Distribution Phase [A4] : 0.580604602, 0.6 kg CO2 eq.
    • Carbon Footprint Of The End-of-life Phase [C1 To C4] : 2 kg CO2 eq., 2.1163418643
    • Carbon Footprint Of The Installation Phase [A5] : 0.0528905846, 0.1 kg CO2 eq.
    • Carbon Footprint Of The Manufacturing Phase [A1 To A3] : 171 kg CO2 eq., 171.1458088753
    • Carbon Footprint Of The Use Phase [B2, B3, B4, B6] : 5 kg CO2 eq., 4.9552928333
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-11-13
    • Pre Comm Date : 2025-02-20
    • Return Indicator : N
    • Stocking Flag : Y
    • Stock Policy : 2
    • Device Type : Relay, Control & Measurement - Protection relay
    • Serviceability : Yes
    • Traceability : Yes
    • Field Service Division : DPIBS
    • Average Life Duration : 15 year(s)
    • Weee Scope : In
    • Weee Product Category : 4
    • Scope Perimeter : At least in Europe
    • Eoli Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI1901010_V2
    • Reach Full Compliance Status : Reference contains Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : CONTAINS_SVHC
    • Reach Compliance Directive : Reference contains Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant By Exemption
    • Rohs Eur Conformity Date : 2448
    • Rohs Eur Full Compliance Status : Compliant By Exemption
    • China Rohs In Scope : Yes
    • China Rohs Label : 4
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : No
    • Product Contributes To Saved And Avoided Emissions : No
    • Product Kit Identifier : N
    • Arc Flash Protection : no
    • Device Short Name : P5F30-AADB-GABAH-BAFK
    • Display Type : LCD 480 x 272 pixels
    • Energy Efficiency Optimized : False
    • Mounting Mode : withdrawable
    • Number Of Key : 7 customizable
    • Number Of Sensors : 0 temperature sensor(s)
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Or Component Type : protection and control relay
    • Range Of Product : PowerLogic P5
    • Relay Application : feeder - directional over current
    • Returnability : No
    • Setting : 4
    • Single Line Diagram : 6 controlled + 2 monitored objects
    • Software Name : eSetup Easergy Pro virtual simulation test
    • Software Version : EIME v5.6.0.1
    • Sustainable Packaging : No
    • Time Synchronisation Protocol : SNTP
    • Total Lifecycle Carbon Footprint : 179 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Pep Code : ENVPEP1901010EN
    • Database Version : 2016-11
    • Pep Verification Date : 2022-08-01
    • Pcr Version : PCR-ed3-EN-2015 04 02
    • Psr Version : PSR-0005-ed2-EN-2016 03 29
    • Type Of Verification For The Pep : Independent internal review
    • Data Source : extrapolated product
    • Functional-unit Description : Protect distribution and transmission networks and high voltage equipment (typically from 1 to 500 KV) like feeder, transformer, motor and generator against faults, (short circuit, over load …) 24h per day, 7 days on 7.& 10Calculations done in this document for LCA use a period of 10 years of operations, in Europe environmental conditions. This time is not representative of the effective lifetime of PowerLogic P5 protection relays, which is more than 10 years.
    • Functional-unit Quantity : 1
    • Functional-unit Unit : unit
    • Reference Lifetime, In Y : 10
    • Energy Model - Manufacturing [A1-a3] : Energy model used: France
    • Energy Model - Installation [A5] : Electricity mix; AC; < 1kV; EU-27
    • Energy Model - Use [B6] : Electricity mix; AC; < 1kV; EU-27
    • Energy Model - End Of Life [C1-c4] : Electricity mix; AC; < 1kV; EU-27
    • Recyclability Potential, In % : 27
    • Height Nominal : 176 mm
    • Height Useful : 176 mm
    • Width Nominal : 152 mm
    • Width Real : 152 mm
    • [Us] Rated Supply Voltage : 24...48 V DC
    • Nbr. Of Units In Pkg. : 1
    • Package Weight(Lbs) : 4.0 kg
    • Take-back : No
    • Warranty (In Months) : 24
    • Customs Code : 8537109170
  • Environment Attributes Main
    • Ambient Air Temperature For Operation : -40-85 °C 16 h ), -40-85 °C 16 h ), -40-70 °C 96 h ), -40-70 °C 96 h )-40-85 °C 16 h ), -40-85 °C 16 h ), -40-70 °C 96 h )
    • Relative Humidity : 0-93 % at 40-40 °C, without condensation, 56 days, 93-95 % at 25-55 °C, 6 cycles, 12 + 12 hours
    • Take Back : No
    • Recycled Metal Content At Cr Level : 0 %
    • China Rohs Regulation : X
    • Mercury Free : Yes
    • Carbon Footprint : 178.8509387596
    • Ambient Air Temperature For Storage : -40-85 °C-40-85 °C
    • Circularity Profile : ENVEOLI1901010_V2
    • Environmental Disclosure : ENVPEP1901010EN
    • Eu Rohs Directive : Compliant By Exemption
    • Ip Degree Of Protection : IP54 IEC 60529
    • Operating Altitude : 6561.68 ft (2000 m)
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : No
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Pep Code : ENVPEP1901010EN
    • Pep Verification Date : 2022-08-01
    • Pcr Version : PCR-ed3-EN-2015 04 02
    • Psr Version : PSR-0005-ed2-EN-2016 03 29
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : protection and control relay
    • Range Of Product : PowerLogic P5
  • Output Attributes
    • Number Of Outputs : 7 DO, 1 watchdog
    • Analogue Output Number : 0
  • Contractual Warranty Attributes
    • Warranty Period : up to 10 years (Standard warranty 2 years. Please check with your local SE representative for extended warranty availability and conditions)
    • Warranty : up to 10 years (Standard warranty 2 years. Please check with your local SE representative for extended warranty availability and conditions)
  • Input Attributes
    • Input Type : 3 1/5 A CT phase current, 1 1 A CT, 1 1/5 A CT residual current, 4 voltage input VT voltage
    • Analogue Input Number : 0
    • Digital Input Number : 10
  • Specifications
    • Country of Origin : Latvia
    • Height : 6.93 in
    • Width : 5.98 in