NEMA Motor Starter, Type S, nonreversing, Size 4, 135A, 100 HP at 460 VAC, 3 phase, 3 pole, melting alloy, 240 VAC coil, NEMA 1, 10 kA SSCR2

STARTER 600VAC 135AMP NEMA +OP

SQD8536SFA1V03 8536SFA1V03 785901549932
5308.72 / EACH
http://schema.org/OutOfStock
  • Certifications: CSA, NEMA, UL Listed
  • Contact Configuration: Without
  • Depth: 243 mm
  • Height: 800 mm
  • Line Rated Current: 135 A
  • NEMA: 4
  • Number of Phases: 3
  • Warranty Length: 18 mth
  • Width: 461 mm
Type S NEMA motor starters are used for full voltage starting and stopping of AC squirrel cage motors. Type S motor starters have ratings up to 810 amperes. This 3 pole NEMA Size 4 non-reversing starter has a 135 ampere rating. This NEMA Size 4 motor starter has 3 phase ratings of 40 HP at 200 VAC, 50 HP at 230 VAC and 100 HP at 460 and 575 VAC. This non-reversing NEMA motor starter has a melting alloy type overload relay that uses Type CC thermal units to sense over current conditions. This NEMA starter has a 10 kA maximum SCCR (Short Circuit Current Rating) per UL508A when protected by an appropriate circuit breaker or fuse. Type S motor starters are available with replaceable coils in a wide variety of voltages. This starter has a 220/240 VAC 50/60 Hz operating coil wired for common control. A painted sheet steel NEMA 12/3R dusttight and driptight industrial use enclosure is used to protect this starter. Enclosure is 31.50 inches tall, 18.16 inches wide and 9.56 inches deep. A wide variety of accessories are available for Type S starters. Type S non-reversing NEMA motor starters are UL listed and CSA certified.
QTY
  • Product Description
  • Specifications
Type S NEMA motor starters are used for full voltage starting and stopping of AC squirrel cage motors. Type S motor starters have ratings up to 810 amperes. This 3 pole NEMA Size 4 non-reversing starter has a 135 ampere rating. This NEMA Size 4 motor starter has 3 phase ratings of 40 HP at 200 VAC, 50 HP at 230 VAC and 100 HP at 460 and 575 VAC. This non-reversing NEMA motor starter has a melting alloy type overload relay that uses Type CC thermal units to sense over current conditions. This NEMA starter has a 10 kA maximum SCCR (Short Circuit Current Rating) per UL508A when protected by an appropriate circuit breaker or fuse. Type S motor starters are available with replaceable coils in a wide variety of voltages. This starter has a 220/240 VAC 50/60 Hz operating coil wired for common control. A painted sheet steel NEMA 12/3R dusttight and driptight industrial use enclosure is used to protect this starter. Enclosure is 31.50 inches tall, 18.16 inches wide and 9.56 inches deep. A wide variety of accessories are available for Type S starters. Type S non-reversing NEMA motor starters are UL listed and CSA certified.
  • Specifications
    • Motor Starter Type : non reversing
    • Range Of Product : S
    • Product Or Component Type : motor starter
  • Contractual warranty
    • Warranty : 18 months
  • Complementary
    • Local Signalling : without pilot light
    • Thermal Overload Type : melting alloy 3
    • Height : 800 mm
    • Auxiliary Contact Composition : without
    • Nema Size : 4
    • [Uc] Control Circuit Voltage : 220 V AC 50 Hz || 240 V AC 60 Hz
    • Poles Description : 3P
    • Rated Power In Hp : 40 HP 200 V AC || 50 HP 230 V AC || 100 HP 460 V AC || 100 HP 575 V AC
    • Electrical Connection : screw clamp terminals
    • Line Rated Current : 135 A
    • Control Type : no control units
    • Control Circuit : common control circuit
    • Width : 461 mm
    • Depth : 243 mm
    • Phase : 3 phase
    • [Ue] Rated Operational Voltage : 600 V AC
  • Offer Sustainability
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Eu Rohs Directive : Not compliant
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Environment
    • Product Certifications : UL Listed || CSA || NEMA
    • Nema Degree Of Protection : NEMA 12 painted sheet steel