Motor Management, TeSys T, motor controller, Ethernet/IP, Modbus/TCP, 6 inputs, 3 logic outputs, 1.35 to 27A, 24 VDC

Motor Management, TeSys T, motor controller, Ethernet/IP, Modbus/TCP, 6 inputs, 3 logic outputs, 1.35 to 27A, 24 VDC

SQDLTMR27EBD LTMR27EBD 785901633754
805.33 / EACH
  • Certifications: ABS, ATEX, BV, CCC, CSA, C-tick, DNV, EAC, GL, KERI, LROS (Lloyds Register Of Shipping), NOM, RINA, RMRoS, UL
  • Current: 56-127 mA
  • Depth: 122.5 mm
  • Height: 61 mm
  • Net Weight: 0.53 kg
  • Standard: CSA C22.2 No 14, EN 60947-4-1, IACS E10, IEC 60947-4-1, UL 508
  • Storage Temperature: -40-80 °C
  • Width: 91 mm
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. Ethernet/IP and Modbus/TCP protocol is used by this controller. Ethernet TCP/IP communication is used. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 1.35 to 27 amperes. 24 VDC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
  • Product Description
  • Specifications
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. Ethernet/IP and Modbus/TCP protocol is used by this controller. Ethernet TCP/IP communication is used. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 1.35 to 27 amperes. 24 VDC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
  • Compatibility Code : LTMR
  • [Uimp] Rated Impulse Withstand Voltage : 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1 || 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
  • Maximum Depth : 122.5 mm
  • Maximum Operating Frequency : 2 Hz
  • Maximum Operating Rate : 1800 cyc/h
  • Ambient Air Temperature For Storage : -40-80 °C
  • Operating Altitude : <= 6561.68 ft (2000 m) without derating
  • Pollution Degree : 3
  • Product Certifications : CCC || BV || KERI || C-tick || GL || ATEX || RINA || CSA || EAC || UL || NOM || DNV || LROS (Lloyds register of shipping) || ABS || RMRoS
  • Connections - Terminals : control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)solid without cable end
  • Maximum Width : 91 mm
  • Ip Degree Of Protection : IP20
  • [Us] Rated Supply Voltage : 24 V DC
  • Communication Port Protocol : Modbus TCP/EtherNet/IP
  • Network And Machine Diagnosis Type : remaining operating time before overload tripping || running hours counter/operating time || waiting time after overload tripping || phase fault and earth fault trip counters || fault recording || trip context information || trip history information || motor control command recording || starting current and time || event recording
  • Device Short Name : LTMR
  • Product Or Component Type : motor controller
  • Current State 0 Guaranteed : logic input < 5 V <= 15 mA 5 ms
  • Web Services : web server
  • Measurement Current : 1.35-27 A
  • Electromagnetic Compatibility : electrostatic discharge, 3 8 kV air, 6 kV contact)EN/IEC 61000-4-2 || surges 1 kV)EN/IEC 61000-4-5 || surges 2 kV)EN/IEC 61000-4-5 || surges 2 kV)EN/IEC 61000-4-5 || surges 4 kV)EN/IEC 61000-4-5 || radiated RF fields, 3 10 V/m)EN/IEC 61000-4-3 || fast transients immunity test, level 3 2 kV)EN/IEC 61000-4-4 || fast transients immunity test, level 4 4 kV)EN/IEC 61000-4-4 || voltage dips and interruptions immunity test 70 %, 500 ms)EN/IEC 61000-4-11 || conducted RF disturbances 10 V)EN/IEC 61000-4-6 || surges 0.5 kV)EN/IEC 61000-4-5 || surges 1 kV)EN/IEC 61000-4-5 || surges 1 kV)EN/IEC 61000-4-5
  • Protective Treatment : 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
  • Device Application : equipment monitoring and control
  • Overvoltage Category : III
  • Bus Type : Ethernet IEEE 802.3 0...159 10...100 Mbit/s, RJ45 2 shielded twisted pairs
  • Current State 1 Guaranteed : logic input < 15 V 2...15 mA 15 ms
  • Maximum Height : 61 mm
  • Logic Input Number : 6
  • Standards : CSA C22.2 No 14 || EN 60947-4-1 || IACS E10 || IEC 60947-4-1 || UL 508
  • Fire Resistance : 650 °C EN/IEC 60695-2-12 || 960 °C UL 94
  • Contacts Type And Composition : 1 NO + 1 NC fault signal || 3 NO
  • [Ui] Rated Insulation Voltage : 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
  • Associated Fuse Rating : 4 A gG output || 0.5 A gG control circuit
  • Tightening Torque : control circuit 0.5-0.6 N.m flat 3 mm
  • Current Consumption : 56...127 mA
  • Protection Type : earth-leakage protection || phase failure || thermal protection || overload || overload (long time) || reverse polarity protection || power factor variation || phase unbalance || thermal overload protection || load fluctuation || locked rotor
  • Ambient Air Temperature For Operation : -20-60 °C
  • Measurement Accuracy : 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
  • Short-Circuit Withstand : 100 kA EN/IEC 60947-4-1
  • Connection Pitch : 5.08 mm
  • Product Name : TeSys T
  • Range : TeSys
  • Net Weight : 0.53 kg
  • Permissible Power : 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
  • Load Current : 5 A 250 V AC logic output || 5 A 30 V DC logic output
  • Mechanical Robustness : vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
  • Input Current : 7 mA
  • Supply Voltage Limits : 20.4-26.24 V DC
  • Metering Type : phase current I1, I2, I3 RMS || average current Iavg || imbalance current || earth-fault current || temperature