Motor controller LTMR TeSys T - 100..240 V AC 27 A for Modbus

Motor controller LTMR TeSys T - 100..240 V AC 27 A for Modbus

SQDLTMR27MFM LTMR27MFM 785901498575
600.66 / EACH
  • Certifications: ABS, ATEX, BV, CCC, CSA, C-tick, DNV, EAC, GL, KERI, LROS (Lloyds Register Of Shipping), NOM, RINA, RMRoS, UL
  • Country of Origin: China
  • Current: 8-62.8 mA
  • Depth: 122.5 mm, 4.82 in
  • Height: 2.40 in, 61 mm
  • Operating Cycles: 1800 cyc/h
  • Standard: CSA C22.2 No 14, EN 60947-4-1, IACS E10, IEC 60947-4-1, UL 508
  • Warranty Length: 18 mth
  • Weight: 0.53 kg, 1.17 lb
  • Width: 3.58 in, 91 mm
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. It manages most critical processes while reducing downtime and increasing productivity as well as predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This motor management system is also a flexible system that supports six communication protocols which are Modbus™, CANopen, DeviceNet™, Profibus™, Ethernet/IP, and Modbus/TCP. TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories. The LTMR controller is the main component of the system that manages the basic functions. This includes the measurement of the ground current, motor temperature, three phase current of the motor, the controller also includes logic inputs and outputs which is used in fault management. The expansion module is directly connected to the controller and provides additional inputs as well as measure the voltage between the phases which allow the controller the monitor additional functions. TeSys T is highly reliable and has a very long product life thanks to a state-of-the-art component selection, to the all in one design and to the advanced electronic protection. TeSys T can be integrated in many different types of harsh environment such as dusty atmospheres, marine applications, high vibration applications and corrosive atmospheres and is used in Metal/Mining/Mineral, Oil & Gas, Water Wastewater. This is a TeSys T LTMR controller that measure current range of 1.35-27A with a supply voltage of 100-240 Vac and uses CANopen as the communication protocol. This controller measures temperature, phase current, imbalance current, average current and earth-fault current. The dimensions of this device are 61 mm (H) X 91 mm (W) X 122.5 mm (D) and it weighs 0.53 kg.
  • Product Description
  • Specifications
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. It manages most critical processes while reducing downtime and increasing productivity as well as predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This motor management system is also a flexible system that supports six communication protocols which are Modbus™, CANopen, DeviceNet™, Profibus™, Ethernet/IP, and Modbus/TCP. TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories. The LTMR controller is the main component of the system that manages the basic functions. This includes the measurement of the ground current, motor temperature, three phase current of the motor, the controller also includes logic inputs and outputs which is used in fault management. The expansion module is directly connected to the controller and provides additional inputs as well as measure the voltage between the phases which allow the controller the monitor additional functions. TeSys T is highly reliable and has a very long product life thanks to a state-of-the-art component selection, to the all in one design and to the advanced electronic protection. TeSys T can be integrated in many different types of harsh environment such as dusty atmospheres, marine applications, high vibration applications and corrosive atmospheres and is used in Metal/Mining/Mineral, Oil & Gas, Water Wastewater. This is a TeSys T LTMR controller that measure current range of 1.35-27A with a supply voltage of 100-240 Vac and uses CANopen as the communication protocol. This controller measures temperature, phase current, imbalance current, average current and earth-fault current. The dimensions of this device are 61 mm (H) X 91 mm (W) X 122.5 mm (D) and it weighs 0.53 kg.
  • Offer Sustainability
    • Mercury Free : Yes
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Halogen Content Performance : Halogen free plastic parts product
    • Green Premium Status : Green Premium product
    • Pvc Free : Yes
    • EU RoHs Directive : Compliant
  • Environment
    • Product Certifications : RMRoS || LROS (Lloyds register of shipping) || RINA || ABS || CCC || EAC || UL || GL || NOM || DNV || KERI || ATEX || BV || CSA || C-tick
    • Operating Altitude : <= 6561.68 ft (2000 m) without derating
    • Standards : CSA C22.2 No 14 || UL 508 || EN 60947-4-1 || IEC 60947-4-1 || IACS E10
    • Mechanical Robustness : Vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || Vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || Shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
    • Fire Resistance : 1202 °F (650 °C) EN/IEC 60695-2-12 || 1760 °F (960 °C) UL 94
    • IP Degree Of Protection : IP20
    • Protective Treatment : 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
    • Ambient Air Temp For Op : -4…140 °F (-20…60 °C)
    • Ambient Air Temp For Storage : -40…176 °F (-40…80 °C)
  • Contractual Warranty
    • Warranty : 18 months
  • Complementary
    • Height : 2.40 in (61 mm)
    • Measurement Accuracy : 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
    • Permissible Power : 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
    • Depth : 4.82 in (122.5 mm)
    • Connections - Terminals : Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible with cable end || Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)solid without cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)flexible with cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 2 0.00…0.00 in² (0.5…1.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)solid without cable end
    • Pollution Degree : 3
    • Electromagnetic Compatibility : Electrostatic discharge, 3 8 kV air, 6 kV contact)EN/IEC 61000-4-2) || Radiated RF fields, 3 10 V/m)EN/IEC 61000-4-3) || Fast transients immunity test, level 3 2 kV)EN/IEC 61000-4-4) || Fast transients immunity test, level 4 4 kV)EN/IEC 61000-4-4) || Voltage dips and interruptions immunity test 70 %, 500 ms)EN/IEC 61000-4-11) || Conducted RF disturbances 10 V)EN/IEC 61000-4-6) || Surges 0.5 kV)EN/IEC 61000-4-5) || Surges 1 kV)EN/IEC 61000-4-5) || Surges 1 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5) || Surges 4 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5)
    • Current State 0 Guaranteed : Logic input 0...40 V <= 15 mA 25 ms
    • Web Services : Web server
    • Protection Type : Reverse polarity protection || Overload (long time) || Earth-leakage protection || Phase unbalance || Overload || Load fluctuation || Phase failure || Power factor variation || Thermal protection || Locked rotor || Thermal overload protection
    • Load Current : 5 A 250 V AC logic output || 5 A 30 V DC logic output
    • Product Weight : 1.17 lb(US) (0.53 kg)
    • Contacts Type And Composition : 1 NO + 1 NC fault signal || 3 NO
    • Short-Circuit Withstand : 100 kA EN/IEC 60947-4-1
    • Overvoltage Category : III
    • Ntw And Machine Diagnosis Type : Fault recording || Starting current and time || Remaining operating time before overload tripping || Waiting time after overload tripping || Motor control command recording || Event recording || Trip history information || Running hours counter/operating time || Phase fault and earth fault trip counters || Trip context information
    • Maximum Output Switching Frequency : 2 Hz
    • Tightening Torque : Control circuit 4.43…5.31 lbf.in (0.5…0.6 N.m) flat 0.12 in (3 mm)
    • Current State 1 Guaranteed : Logic input 79...264 V >= 2 mA 25 ms
    • Uimp Rated Imp Wstd Voltage : 4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1
    • Compatibility Code : LTMR
    • Metering Type : Temperature || Phase current I1, I2, I3 RMS || Average current Iavg || Earth-fault current || Imbalance current
    • Operating Rate : 1800 cyc/h
    • Logic Input Number : 6
    • Input Current : 3.1 mA 100 V || 7.5 mA 240 V
    • Width : 3.58 in (91 mm)
    • Associated Fuse Rating : 4 A gG output || 0.5 A gG control circuit
    • Connection Pitch : 0.20 in (5.08 mm)
    • Ui Rated Insulation Voltage : 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
  • Main
    • Measurement Current : 1.35…27 A
    • Current Consumption : 8...62.8 mA
    • Product Name : TeSys T
    • Product Or Component Type : Motor controller
    • Bus Type : Modbus 2-wire RS 485 1...247 1.2...19.2 kbit/s, RJ45 2 shielded twisted pairs || Modbus 2-wire RS 485 1...247 1.2...19.2 kbit/s, terminal block 2 shielded twisted pairs
    • Device Application : Equipment monitoring and control
    • Supply Voltage Limits : 93.5…264 V AC
    • Communication Port Protocol : Modbus
    • Range : TeSys
    • Device Short Name : LTMR
    • [Us] Rated Supply Voltage : 100...240 V AC 50/60 Hz
  • Ordering And Shipping Details
    • Country Of Origin : CN
    • GTIN : 00785901498575
    • Nbr. Of Units In Pkg. : 1
    • Returnability : Yes
    • Discount Schedule : I12
    • Category : 22338 - SOLID STATE OVERLOAD RELAYS