Motor circuit breaker, TeSys Deca, 3P, 7A, Icu 100kA, thermal magnetic, multifunction, UL489

TeSys GV UL489 Mtr Brkr 2.9-7A

SQDGV4PB07S GV4PB07S 3606489868659
581.59 / EA
http://schema.org/OutOfStock
  • Certifications: CSA, IEC, UL
  • Depth: 116 mm
  • Height: 171 mm
  • Line Rated Current: 7 A
  • Net Weight: 1.45 kg
  • Standard: CSA C22.2 No 5, EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-4-1, UL 489
  • Storage Temperature: -50-85 °C
  • Trip Point: 119-119 A
  • Warranty Length: 18 mth
  • Width: 81 mm
TeSys GV motor circuit breaker, 3 poles (3P), 7A/690V, for protection of 3-phase motors 1.5-3kW@400V. Multifunction circuit breaker UL489 compliant, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 2.9-7A, a selectable tripping class 10 or 20, rated tripping current 125%, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL 489, CSA C22.2 N°5), Green Premium compliant (RoHS/REACh).
QTY
  • Product Description
  • Specifications
TeSys GV motor circuit breaker, 3 poles (3P), 7A/690V, for protection of 3-phase motors 1.5-3kW@400V. Multifunction circuit breaker UL489 compliant, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 2.9-7A, a selectable tripping class 10 or 20, rated tripping current 125%, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL 489, CSA C22.2 N°5), Green Premium compliant (RoHS/REACh).
  • Environment
    • Product Certifications : IEC || UL || CSA
    • Ik Degree Of Protection : IK07 IEC 62262
    • Ambient Air Temperature For Operation : -25-70 °C
    • Standards : EN/IEC 60947-1 || EN/IEC 60947-2 || EN/IEC 60947-4-1 || UL 489 || CSA C22.2 No 5
    • Climatic Withstand : IACS E10
    • Pollution Degree : 3
    • Ambient Air Temperature For Storage : -50-85 °C
    • Ip Degree Of Protection : IP40 IEC 60529
    • Operating Altitude : 5000 m
    • Fire Resistance : 960 °C IEC 60695-2-11
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1704004EN
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Circularity Profile : ENVEOLI1704004EN
    • Eu Rohs Directive : Compliant with Exemptions
    • Halogen Content Performance : Halogen free plastic parts product
  • Complementary
    • Mechanical Robustness : vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
    • Line Rated Current : 7 A
    • [Ue] Rated Operational Voltage : 690 V AC 50/60 Hz IEC 60947-2 || 600Y/347 V AC 60 Hz UL 489
    • Height : 171 mm
    • Phase Failure Sensitivity : yes IEC 60947-4-1
    • Rated Duty : continuous IEC 60947-4-1
    • Magnetic Tripping Current : 119-119 A
    • [Ith] Conventional Free Air Thermal Current : 115 A IEC 60947-4-1
    • Maximum Operating Rate : 25 cyc/h
    • Operating Position : any position
    • Connections - Terminals : EverLink BTR screw connectors top) 1 1.5-70 mm² - rigid || EverLink BTR screw connectors top) 1 1.5-50 mm² - flexible || EverLink BTR screw connectors bottom) 1 2.5-95 mm² - rigid || EverLink BTR screw connectors bottom) 1 2.5-70 mm² - flexible
    • Utilisation Category : category A IEC 60947-2 || AC-3 IEC 60947-4-1
    • Net Weight : 1.45 kg
    • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947-2
    • [Ics] Rated Service Short-Circuit Breaking Capacity : 100 % 220/240 V AC 50/60 Hz IEC 60947-2 || 100 % 380/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 100 % 525 V AC 50/60 Hz IEC 60947-2 || 25 % 660/690 V AC 50/60 Hz IEC 60947-2
    • Control Type : toggle
    • Power Dissipation Per Pole : 4.6 W
    • Electrical Durability : 40000 cycles AC-3 440 V In/2 || 40000 cycles AC-3 440 V In
    • Breaking Capacity : 100 kA SCCR 240 V AC 60 Hz UL 489 || 65 kA SCCR 480Y/277 V AC 60 Hz UL 489 || 25 kA SCCR 600Y/347 V AC 60 Hz UL 489 || 120 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 || 70 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 30 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 18 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 10 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
    • Suitability For Isolation : yes IEC 60947-1
    • [Ui] Rated Insulation Voltage : 800 V AC 50/60 Hz IEC 60947-2
    • Tightening Torque : 9 N.m 16-95 mm² || 5 N.m 1.5-10 mm²
    • Mechanical Durability : 40000 cycles
    • Poles Description : 3P
    • Color : Gray RAL 7016)
    • Width : 81 mm
    • Depth : 116 mm
  • Specifications
    • Range Of Product : TeSys GV4
    • Product Or Component Type : motor circuit breaker
    • Product Name : TeSys GV4 || TeSys Deca
    • Range : TeSys Deca
    • Device Application : motor protection
    • Device Short Name : GV4PB
    • Trip Unit Technology : thermal-magnetic || electronic