Motor circuit breaker, TeSys GV4, 3P, 3.5A, Icu 100kA, thermal magnetic, multifunction, UL489

Motor circuit breaker, TeSys GV4, 3P, 3.5A, Icu 100kA, thermal magnetic, multifunction, UL489

SQDGV4PB03S GV4PB03S 360648986864
0.00 / EA
  • Amperage: 3.5 A
  • Certifications: CSA, IEC, UL
  • Country of Origin: USA
  • Depth: 116 mm, 4.57 in
  • Height: 171 mm, 6.73 in
  • Mounting Type: By Screws
  • Standard: CSA C22.2 No 5, EN/IEC 60947-1, EN/IEC 60947-2, EN/IEC 60947-4-1, UL 489
  • Strip Length: 0.79 in, 20 mm
  • Trip Point: 60 A
  • Voltage: 347 V, 690 V
  • Warranty Length: 18 mth
  • Weight: 1.45 kg, 3.20 lb
  • Width: 3.19 in, 81 mm
TeSys GV motor circuit breaker, 3 poles (3P), 3.5A/690V, for protection of 3-phase motors 0.55-1.5kW@400V. Multifunction circuit breaker UL489 compliant, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 1.4-3.5A, a selectable tripping class 10 or 20, rated tripping current 125%, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL 489, CSA C22.2 N°5), Green Premium compliant (RoHS/REACh).
  • Product Description
  • Specifications
TeSys GV motor circuit breaker, 3 poles (3P), 3.5A/690V, for protection of 3-phase motors 0.55-1.5kW@400V. Multifunction circuit breaker UL489 compliant, it provides thermal magnetic protection and advanced motor protection, breaking capacity Icu 100kA@400V, start-stop control by toggle, connection by Everlink BTR screw terminals. Thermal protection adjustable by dials with a setting current Ir in range 1.4-3.5A, a selectable tripping class 10 or 20, rated tripping current 125%, magnetic protection at 17 In. Advanced protections are adjustable with a smartphone using wireless NFC and include short time delay protection Isd with a setting range 5-13 Ir, phase unbalance and loss protection, ground fault protection, locked rotor (jam), long start. It makes internal locations available for additional auxiliary contact blocks (OF, SD), and voltage trip units (MN, MX). It can be equiped externally with 1 or 2 auxiliary SDx modules in order to have alarming and fault differentiation. Multi standards certified (IEC, UL 489, CSA C22.2 N°5), Green Premium compliant (RoHS/REACh).
  • Contractual Warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Green Premium Status : Green Premium product
    • EU RoHs Directive : Compliant
    • Pvc Free : Yes
    • Mercury Free : Yes
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Halogen Content Performance : Halogen free plastic parts product
  • Ordering And Shipping Details
    • Discount Schedule : I11
    • GTIN : 03606489868642
    • Country Of Origin : US
    • Category : 22365 - TESYS GV4 MOTOR CIRCUIT BREAKERS
    • Returnability : Yes
    • Nbr. Of Units In Pkg. : 1
  • Environment
    • IK Degree Of Protection : IK07 IEC 62262
    • IP Degree Of Protection : IP40 front face conforming to IEC 60529
    • Operating Altitude : 0...2000 m without derating || 2000...5000 m with derating
    • Pollution Degree : 3 conforming to IEC 60947-1
    • Ambient Air Temp For Op : -13…158 °F (-25…70 °C)
    • Ambient Air Temp For Storage : -58…185 °F (-50…85 °C)
    • Tropicalisation : 2 conforming to IEC 68-2
    • Mechanical Robustness : Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 || Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 || Shocks: 15 gn 11 ms conforming to IEC 60068-2-27
  • Complementary
    • Depth : 4.57 in (116 mm)
    • Wire Stripping Length : 0.79 in (20 mm)
    • Connections - Terminals : Top 1 EverLink BTR screw connectors 0.00…0.11 in² (1.5…70 mm²), rigid || Top 1 EverLink BTR screw connectors 0.00…0.08 in² (1.5…50 mm²), flexible || Bottom 1 EverLink BTR screw connectors 0.00…0.15 in² (2.5…95 mm²), rigid || Bottom 1 EverLink BTR screw connectors 0.00…0.11 in² (2.5…70 mm²), flexible
    • Standards : EN/IEC 60947-1 || EN/IEC 60947-2 || EN/IEC 60947-4-1 || UL 489 || CSA C22.2 No 5
    • Product Weight : 3.20 lb(US) (1.45 kg)
    • Tightening Torque : 79.66 lbf.in (9 N.m) 0.02…0.15 in² (16…95 mm²) || 44.25 lbf.in (5 N.m) 0.00…0.02 in² (1.5…10 mm²)
    • Connection Pitch : 1.06 in (27 mm) with spreader)
    • Local Signalling : Flashing LED (green) for ready || LED (red) for alarm (T° >95%) || Green indicator for presence of auxiliary contacts
    • Colour : Grey (RAL 7016)
    • Product Certifications : IEC || UL || CSA
    • Communication Port Protocol : NFC
    • Width : 3.19 in (81 mm)
    • Mounting Support : Plate || 35 mm symmetrical DIN rail || 75 mm symmetrical DIN rail
    • Mounting Mode : Clip-on || By screws
    • Control Type : Toggle
    • Height : 6.73 in (171 mm)
    • Number Of Slots : 1 alarm switch fault signalling contact, plug-in || 1 voltage release electrical remote tripping, plug-in || 1 auxiliary switch open/close contact, plug-in
    • Handle Padlocking : With a lock accessory
  • Main
    • Device Short Name : GV4PB
    • Continuous Current Rating : 100 %, minimum dimensions enclosure: 373 mm x 218 mm x 108 mm (H x W x D)
    • Poles Description : 3P
    • Mechanical Durability : 40000 cycles
    • Product Or Component Type : Multifunction circuit breaker
    • Range : TeSys
    • Suitability For ISOlation : Yes conforming to IEC 60947-1
    • Magnetic Tripping Current : 60 A
    • Trip Unit Technology : Electronic || Thermal-magnetic
    • Thermal Protection Adj Range : 1.4…3.5 A adjustable by rotary dial
    • Device Application : Motor protection
    • Breaking Capacity : SCCR 100 kA 240 V AC 60 Hz UL 489 || SCCR 65 kA 480Y/277 V AC 60 Hz UL 489 || SCCR 25 kA 600Y/347 V AC 60 Hz UL 489 || Icu 120 kA 220/240 V AC 50/60 Hz IEC 60947-2 || Icu 100 kA 380/415 V AC 50/60 Hz IEC 60947-2 || Icu 70 kA 440 V AC 50/60 Hz IEC 60947-2 || Icu 30 kA 500 V AC 50/60 Hz IEC 60947-2 || Icu 18 kA 525 V AC 50/60 Hz IEC 60947-2 || Icu 10 kA 660/690 V AC 50/60 Hz IEC 60947-2
    • Utilisation Category : Category A
    • Isd Short-Time Pick-Up Adj : 5...13 x Ir adjustable with EcoStruxure Power
    • Phase Failure Sensitivity : Yes conforming to IEC 60947-4-1
    • Electrical Durability : 40000 cycles AC-3 440 V In/2 || 40000 cycles AC-3 440 V In
    • Uimp Rated Imp Wstd Voltage : 8 kV IEC 60947-2
    • Ics Rated Ser Sc Brking Cap : 100 % 220/240 V AC 50/60 Hz IEC 60947-2 || 100 % 380/415 V AC 50/60 Hz IEC 60947-2 || 100 % 440 V AC 50/60 Hz IEC 60947-2 || 100 % 500 V AC 50/60 Hz IEC 60947-2 || 100 % 525 V AC 50/60 Hz IEC 60947-2 || 25 % 660/690 V AC 50/60 Hz IEC 60947-2
    • In Rated Current : 3.5 A
    • Motor Tripping Class : UL 489 || UL 489 || CSA C22.2 No 5 || CSA C22.2 No 5
    • Product Name : TeSys GV4
    • Ui Rated Insulation Voltage : 800 V IEC 60947-2
    • Protection Type : Overload protection || Short-circuit protection || Short time short-circuit protection || Ground fault protection || Phase unbalance || Phase loss || Locked rotor || Long start || Jam
    • Ue Rated Operational Voltage : 690 V AC 50/60 Hz conforming to IEC 60947-2 || 600Y/347 V AC 60 Hz UL 489