Motor Management, TeSys T, motor controller, Modbus, 6 logic inputs, 3 logic outputs, 5 to 100A, 100 to 240 VAC

Motor Management, TeSys T, motor controller, Modbus, 6 logic inputs, 3 logic outputs, 5 to 100A, 100 to 240 VAC

SQDLTMR100MFM LTMR100MFM 785901502272
680.75 / EACH
  • Certifications: ABS, ATEX, BV, CCC, CSA, C-tick, DNV, EAC, GL, KERI, LROS (Lloyds Register Of Shipping), NOM, RINA, RMRoS, UL
  • Country of Origin: China
  • Current: 8-62.8 mA
  • Depth: 122.5 mm, 4.82 in
  • Height: 2.40 in, 61 mm
  • Operating Cycles: 1800 cyc/h
  • Standard: CSA C22.2 No 14, EN 60947-4-1, IACS E10, IEC 60947-4-1, UL 508
  • Warranty Length: 18 mth
  • Weight: 0.53 kg, 1.17 lb
  • Width: 3.58 in, 91 mm
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. It manages most critical processes while reducing downtime and increasing productivity as well as predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This motor management system is also a flexible system that supports six communication protocols which are Modbus™, CANopen, DeviceNet™, Profibus™, Ethernet/IP, and Modbus/TCP. TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories. The LTMR controller is the main component of the system that manages the basic functions. This includes the measurement of the ground current, motor temperature, three phase current of the motor, the controller also includes logic inputs and outputs which is used in fault management. The expansion module is directly connected to the controller and provides additional inputs as well as measure the voltage between the phases which allow the controller the monitor additional functions. TeSys T is highly reliable and has a very long product life thanks to a state-of-the-art component selection, to the all in one design and to the advanced electronic protection. TeSys T can be integrated in many different types of harsh environment such as dusty atmospheres, marine applications, high vibration applications and corrosive atmospheres and is used in Metal/Mining/Mineral, Oil & Gas, Water Wastewater. This is a TeSys T LTMR controller that measure current range of 5-100A with a supply voltage of 100-240 Vac and uses Modbus as the communication protocol. This controller measures temperature, phase current, imbalance current, average current and earth-fault current. The dimensions of this device are 61 mm (H) X 91 mm (W) X 122.5 mm (D) and it weighs 0.53 kg. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
  • Product Description
  • Specifications
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. It manages most critical processes while reducing downtime and increasing productivity as well as predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This motor management system is also a flexible system that supports six communication protocols which are Modbus™, CANopen, DeviceNet™, Profibus™, Ethernet/IP, and Modbus/TCP. TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories. The LTMR controller is the main component of the system that manages the basic functions. This includes the measurement of the ground current, motor temperature, three phase current of the motor, the controller also includes logic inputs and outputs which is used in fault management. The expansion module is directly connected to the controller and provides additional inputs as well as measure the voltage between the phases which allow the controller the monitor additional functions. TeSys T is highly reliable and has a very long product life thanks to a state-of-the-art component selection, to the all in one design and to the advanced electronic protection. TeSys T can be integrated in many different types of harsh environment such as dusty atmospheres, marine applications, high vibration applications and corrosive atmospheres and is used in Metal/Mining/Mineral, Oil & Gas, Water Wastewater. This is a TeSys T LTMR controller that measure current range of 5-100A with a supply voltage of 100-240 Vac and uses Modbus as the communication protocol. This controller measures temperature, phase current, imbalance current, average current and earth-fault current. The dimensions of this device are 61 mm (H) X 91 mm (W) X 122.5 mm (D) and it weighs 0.53 kg. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
  • Environment
    • Fire Resistance : 1202 °F (650 °C) EN/IEC 60695-2-12 || 1760 °F (960 °C) UL 94
    • IP Degree Of Protection : IP20
    • Operating Altitude : <= 6561.68 ft (2000 m) without derating
    • Ambient Air Temp For Storage : -40…176 °F (-40…80 °C)
    • Product Certifications : LROS (Lloyds register of shipping) || UL || ABS || ATEX || EAC || CCC || BV || RINA || DNV || C-tick || RMRoS || CSA || GL || NOM || KERI
    • Mechanical Robustness : Vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || Vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || Shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
    • Standards : IACS E10 || IEC 60947-4-1 || UL 508 || EN 60947-4-1 || CSA C22.2 No 14
    • Protective Treatment : 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
    • Ambient Air Temp For Op : -4…140 °F (-20…60 °C)
  • Main
    • Communication Port Protocol : Modbus
    • Range : TeSys
    • Measurement Current : 5…100 A
    • Bus Type : Modbus 2-wire RS 485 1...247 1.2...19.2 kbit/s, RJ45 2 shielded twisted pairs || Modbus 2-wire RS 485 1...247 1.2...19.2 kbit/s, terminal block 2 shielded twisted pairs
    • Device Application : Equipment monitoring and control
    • Device Short Name : LTMR
    • [Us] Rated Supply Voltage : 100...240 V AC 50/60 Hz
    • Product Name : TeSys T
    • Current Consumption : 8...62.8 mA
    • Supply Voltage Limits : 93.5…264 V AC
    • Product Or Component Type : Motor controller
  • Ordering And Shipping Details
    • Nbr. Of Units In Pkg. : 1
    • Discount Schedule : I12
    • Returnability : Yes
    • Country Of Origin : CN
    • GTIN : 00785901502272
    • Category : 22338 - SOLID STATE OVERLOAD RELAYS
  • Contractual Warranty
    • Warranty : 18 months
  • Complementary
    • Associated Fuse Rating : 4 A gG output || 0.5 A gG control circuit
    • Protection Type : Load fluctuation || Earth-leakage protection || Overload (long time) || Overload || Locked rotor || Thermal protection || Thermal overload protection || Power factor variation || Reverse polarity protection || Phase failure || Phase unbalance
    • Depth : 4.82 in (122.5 mm)
    • Connection Pitch : 0.20 in (5.08 mm)
    • Tightening Torque : Control circuit 4.43…5.31 lbf.in (0.5…0.6 N.m) flat 0.12 in (3 mm)
    • Web Services : Web server
    • Connections - Terminals : Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible with cable end || Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)solid without cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)flexible with cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 2 0.00…0.00 in² (0.5…1.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)solid without cable end
    • Pollution Degree : 3
    • Maximum Output Switching Frequency : 2 Hz
    • Product Weight : 1.17 lb(US) (0.53 kg)
    • Permissible Power : 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
    • Short-Circuit Withstand : 100 kA EN/IEC 60947-4-1
    • Electromagnetic Compatibility : Electrostatic discharge, 3 8 kV air, 6 kV contact)EN/IEC 61000-4-2) || Radiated RF fields, 3 10 V/m)EN/IEC 61000-4-3) || Fast transients immunity test, level 3 2 kV)EN/IEC 61000-4-4) || Fast transients immunity test, level 4 4 kV)EN/IEC 61000-4-4) || Voltage dips and interruptions immunity test 70 %, 500 ms)EN/IEC 61000-4-11) || Conducted RF disturbances 10 V)EN/IEC 61000-4-6) || Surges 0.5 kV)EN/IEC 61000-4-5) || Surges 1 kV)EN/IEC 61000-4-5) || Surges 1 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5) || Surges 4 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5)
    • Compatibility Code : LTMR
    • Metering Type : Temperature || Earth-fault current || Average current Iavg || Imbalance current || Phase current I1, I2, I3 RMS
    • Width : 3.58 in (91 mm)
    • Load Current : 5 A 250 V AC logic output || 5 A 30 V DC logic output
    • Contacts Type And Composition : 1 NO + 1 NC fault signal || 3 NO
    • Logic Input Number : 6
    • Overvoltage Category : III
    • Current State 0 Guaranteed : Logic input 0...40 V <= 15 mA 25 ms
    • Input Current : 3.1 mA 100 V || 7.5 mA 240 V
    • Current State 1 Guaranteed : Logic input 79...264 V >= 2 mA 25 ms
    • Ui Rated Insulation Voltage : 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
    • Operating Rate : 1800 cyc/h
    • Uimp Rated Imp Wstd Voltage : 4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1
    • Ntw And Machine Diagnosis Type : Motor control command recording || Starting current and time || Trip history information || Phase fault and earth fault trip counters || Running hours counter/operating time || Remaining operating time before overload tripping || Fault recording || Trip context information || Event recording || Waiting time after overload tripping
    • Height : 2.40 in (61 mm)
    • Measurement Accuracy : 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 5 % active and reactive power || 0,02 current
  • Offer Sustainability
    • Halogen Content Performance : Halogen free plastic parts product
    • Mercury Free : Yes
    • Green Premium Status : Green Premium product
    • Pvc Free : Yes
    • EU RoHs Directive : Compliant
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.