Motor Management, TeSys T, motor controller, Ethernet/IP, Modbus/TCP, 6 logic inputs, 3 logic outputs, 5 to 100A, 24 VDC

Motor Management, TeSys T, motor controller, Ethernet/IP, Modbus/TCP, 6 logic inputs, 3 logic outputs, 5 to 100A, 24 VDC

SQDLTMR100EBD LTMR100EBD 785901830535
912.11 / EACH
  • Certifications: ABS, ATEX, BV, CCC, CSA, C-tick, DNV, EAC, GL, KERI, LROS (Lloyds Register Of Shipping), NOM, RINA, RMRoS, UL
  • Country of Origin: China
  • Current: 56-127 mA
  • Depth: 122.5 mm, 4.82 in
  • Height: 2.40 in, 61 mm
  • Operating Cycles: 1800 cyc/h
  • Standard: CSA C22.2 No 14, EN 60947-4-1, IACS E10, IEC 60947-4-1, UL 508
  • Warranty Length: 18 mth
  • Weight: 0.53 kg, 1.17 lb
  • Width: 3.58 in, 91 mm
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. Ethernet/IP and Modbus/TCP protocol is used by this controller. Ethernet TCP/IP communication is used. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 5 to 100 amperes. 24 VDC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
  • Product Description
  • Specifications
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. Ethernet/IP and Modbus/TCP protocol is used by this controller. Ethernet TCP/IP communication is used. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 5 to 100 amperes. 24 VDC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
  • Ordering And Shipping Details
    • Discount Schedule : I12
    • Nbr. Of Units In Pkg. : 1
    • Returnability : Yes
    • GTIN : 00785901830535
    • Category : 22338 - SOLID STATE OVERLOAD RELAYS
    • Country Of Origin : CN
  • Offer Sustainability
    • EU RoHs Directive : Compliant
    • Mercury Free : Yes
    • Halogen Content Performance : Halogen free plastic parts product
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Green Premium Status : Green Premium product
    • Pvc Free : Yes
  • Contractual Warranty
    • Warranty : 18 months
  • Complementary
    • Protection Type : Locked rotor || Overload || Thermal overload protection || Earth-leakage protection || Reverse polarity protection || Overload (long time) || Power factor variation || Phase unbalance || Load fluctuation || Phase failure || Thermal protection
    • Ntw And Machine Diagnosis Type : Fault recording || Trip context information || Waiting time after overload tripping || Trip history information || Running hours counter/operating time || Motor control command recording || Starting current and time || Phase fault and earth fault trip counters || Event recording || Remaining operating time before overload tripping
    • Depth : 4.82 in (122.5 mm)
    • Connection Pitch : 0.20 in (5.08 mm)
    • Tightening Torque : Control circuit 4.43…5.31 lbf.in (0.5…0.6 N.m) flat 0.12 in (3 mm)
    • Contacts Type And Composition : 1 NO + 1 NC fault signal || 3 NO
    • Pollution Degree : 3
    • Metering Type : Average current Iavg || Earth-fault current || Temperature || Phase current I1, I2, I3 RMS || Imbalance current
    • Overvoltage Category : III
    • Permissible Power : 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
    • Input Current : 7 mA
    • Product Weight : 1.17 lb(US) (0.53 kg)
    • Width : 3.58 in (91 mm)
    • Web Services : Web server
    • Current State 1 Guaranteed : Logic input < 15 V 2...15 mA 15 ms
    • Connections - Terminals : Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible with cable end || Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)solid without cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)flexible with cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 2 0.00…0.00 in² (0.5…1.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)solid without cable end
    • Maximum Output Switching Frequency : 2 Hz
    • Current State 0 Guaranteed : Logic input < 5 V <= 15 mA 5 ms
    • Height : 2.40 in (61 mm)
    • Logic Input Number : 6
    • Operating Rate : 1800 cyc/h
    • Uimp Rated Imp Wstd Voltage : 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1 || 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
    • Ui Rated Insulation Voltage : 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
    • Compatibility Code : LTMR
    • Load Current : 5 A 250 V AC logic output || 5 A 30 V DC logic output
    • Electromagnetic Compatibility : Electrostatic discharge, 3 8 kV air, 6 kV contact)EN/IEC 61000-4-2) || Radiated RF fields, 3 10 V/m)EN/IEC 61000-4-3) || Fast transients immunity test, level 3 2 kV)EN/IEC 61000-4-4) || Fast transients immunity test, level 4 4 kV)EN/IEC 61000-4-4) || Voltage dips and interruptions immunity test 70 %, 500 ms)EN/IEC 61000-4-11) || Conducted RF disturbances 10 V)EN/IEC 61000-4-6) || Surges 0.5 kV)EN/IEC 61000-4-5) || Surges 1 kV)EN/IEC 61000-4-5) || Surges 1 kV)EN/IEC 61000-4-5) || Surges 1 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5) || Surges 4 kV)EN/IEC 61000-4-5)
    • Short-Circuit Withstand : 100 kA EN/IEC 60947-4-1
    • Associated Fuse Rating : 4 A gG output || 0.5 A gG control circuit
    • Measurement Accuracy : 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 5 % active and reactive power || 0,02 current
  • Environment
    • Protective Treatment : 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
    • Ambient Air Temp For Op : -4…140 °F (-20…60 °C)
    • Product Certifications : C-tick || KERI || BV || ABS || NOM || LROS (Lloyds register of shipping) || RMRoS || RINA || GL || DNV || ATEX || CCC || EAC || UL || CSA
    • Ambient Air Temp For Storage : -40…176 °F (-40…80 °C)
    • Fire Resistance : 1202 °F (650 °C) EN/IEC 60695-2-12 || 1760 °F (960 °C) UL 94
    • Operating Altitude : <= 6561.68 ft (2000 m) without derating
    • Mechanical Robustness : Vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || Vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || Shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
    • IP Degree Of Protection : IP20
    • Standards : IEC 60947-4-1 || UL 508 || IACS E10 || EN 60947-4-1 || CSA C22.2 No 14
  • Main
    • Measurement Current : 5…100 A
    • Supply Voltage Limits : 20.4…26.24 V DC
    • Current Consumption : 56...127 mA
    • Device Application : Equipment monitoring and control
    • Device Short Name : LTMR
    • Product Or Component Type : Motor controller
    • Product Name : TeSys T
    • [Us] Rated Supply Voltage : 24 V DC
    • Communication Port Protocol : Modbus TCP/EtherNet/IP
    • Bus Type : Ethernet IEEE 802.3 0...159 10...100 Mbit/s, RJ45 2 shielded twisted pairs
    • Range : TeSys