Motor Management, TeSys T, motor controller, CANopen, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 100 to 240 VAC

Motor Management, TeSys T, motor controller, CANopen, 6 logic inputs, 3 relay logic outputs, 5 to 100A, 100 to 240 VAC

SQDLTMR100CFM LTMR100CFM 785901498582
756.38 / EACH
  • Certifications: ABS, ATEX, BV, CCC, CSA, C-tick, DNV, EAC, GL, KERI, LROS (Lloyds Register Of Shipping), NOM, RINA, RMRoS, UL
  • Country of Origin: China
  • Current: 8-62.8 mA
  • Depth: 122.5 mm, 4.82 in
  • Height: 2.40 in, 61 mm
  • Operating Cycles: 1800 cyc/h
  • Standard: CSA C22.2 No 14, EN 60947-4-1, IACS E10, IEC 60947-4-1, UL 508
  • Warranty Length: 18 mth
  • Weight: 0.53 kg, 1.17 lb
  • Width: 3.58 in, 91 mm
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. It manages most critical processes while reducing downtime and increasing productivity as well as predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This motor management system is also a flexible system that supports six communication protocols which are Modbus™, CANopen, DeviceNet™, Profibus™, Ethernet/IP, and Modbus/TCP. TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories. The LTMR controller is the main component of the system that manages the basic functions. This includes the measurement of the ground current, motor temperature, three phase current of the motor, the controller also includes logic inputs and outputs which is used in fault management. The expansion module is directly connected to the controller and provides additional inputs as well as measure the voltage between the phases which allow the controller the monitor additional functions. TeSys T is highly reliable and has a very long product life thanks to a state-of-the-art component selection, to the all in one design and to the advanced electronic protection. TeSys T can be integrated in many different types of harsh environment such as dusty atmospheres, marine applications, high vibration applications and corrosive atmospheres and is used in Metal/Mining/Mineral, Oil & Gas, Water Wastewater. This is a TeSys T LTMR controller that measure current range of 5-100A with a supply voltage of 100-240 Vac and uses CANopen as the communication protocol. This controller measures temperature, phase current, imbalance current, average current and earth-fault current. The dimensions of this device are 61 mm (H) X 91 mm (W) X 122.5 mm (D) and it weighs 0.53 kg. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
  • Product Description
  • Specifications
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. It manages most critical processes while reducing downtime and increasing productivity as well as predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This motor management system is also a flexible system that supports six communication protocols which are Modbus™, CANopen, DeviceNet™, Profibus™, Ethernet/IP, and Modbus/TCP. TeSys T motor management system consist of several components which include the LTMR controller, the expansion module, HMI and software along with several accessories. The LTMR controller is the main component of the system that manages the basic functions. This includes the measurement of the ground current, motor temperature, three phase current of the motor, the controller also includes logic inputs and outputs which is used in fault management. The expansion module is directly connected to the controller and provides additional inputs as well as measure the voltage between the phases which allow the controller the monitor additional functions. TeSys T is highly reliable and has a very long product life thanks to a state-of-the-art component selection, to the all in one design and to the advanced electronic protection. TeSys T can be integrated in many different types of harsh environment such as dusty atmospheres, marine applications, high vibration applications and corrosive atmospheres and is used in Metal/Mining/Mineral, Oil & Gas, Water Wastewater. This is a TeSys T LTMR controller that measure current range of 5-100A with a supply voltage of 100-240 Vac and uses CANopen as the communication protocol. This controller measures temperature, phase current, imbalance current, average current and earth-fault current. The dimensions of this device are 61 mm (H) X 91 mm (W) X 122.5 mm (D) and it weighs 0.53 kg. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
  • Ordering And Shipping Details
    • Returnability : Yes
    • Discount Schedule : I12
    • Nbr. Of Units In Pkg. : 1
    • Country Of Origin : CN
    • Category : 22338 - SOLID STATE OVERLOAD RELAYS
    • GTIN : 00785901498582
  • Offer Sustainability
    • WEEE : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Mercury Free : Yes
    • Pvc Free : Yes
    • Green Premium Status : Green Premium product
    • EU RoHs Directive : Compliant
    • Halogen Content Performance : Halogen free plastic parts product
  • Contractual Warranty
    • Warranty : 18 months
  • Complementary
    • Electromagnetic Compatibility : Electrostatic discharge, 3 8 kV air, 6 kV contact)EN/IEC 61000-4-2) || Radiated RF fields, 3 10 V/m)EN/IEC 61000-4-3) || Fast transients immunity test, level 3 2 kV)EN/IEC 61000-4-4) || Fast transients immunity test, level 4 4 kV)EN/IEC 61000-4-4) || Voltage dips and interruptions immunity test 70 %, 500 ms)EN/IEC 61000-4-11) || Conducted RF disturbances 10 V)EN/IEC 61000-4-6) || Surges 0.5 kV)EN/IEC 61000-4-5) || Surges 1 kV)EN/IEC 61000-4-5) || Surges 1 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5) || Surges 4 kV)EN/IEC 61000-4-5) || Surges 2 kV)EN/IEC 61000-4-5)
    • Short-Circuit Withstand : 100 kA EN/IEC 60947-4-1
    • Ui Rated Insulation Voltage : 690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
    • Product Weight : 1.17 lb(US) (0.53 kg)
    • Uimp Rated Imp Wstd Voltage : 4 kV supply, inputs and outputs EN/IEC 60947-4-1 || 6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1
    • Measurement Accuracy : 5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 5 % active and reactive power || 0,02 current
    • Connections - Terminals : Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible with cable end || Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 1 0.00…0.00 in² (0.25…2.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 1 0.00…0.00 in² (0.2…2.5 mm²) AWG 24...AWG 14)solid without cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)flexible with cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 2 0.00…0.00 in² (0.5…1.5 mm²) AWG 24...AWG 14)flexible without cable end || Control circuit connector 2 0.00…0.00 in² (0.2…1 mm²) AWG 24...AWG 14)solid without cable end
    • Pollution Degree : 3
    • Protection Type : Thermal protection || Locked rotor || Phase failure || Earth-leakage protection || Overload (long time) || Power factor variation || Phase unbalance || Load fluctuation || Thermal overload protection || Reverse polarity protection || Overload
    • Current State 1 Guaranteed : Logic input 79...264 V >= 2 mA 25 ms
    • Overvoltage Category : III
    • Width : 3.58 in (91 mm)
    • Ntw And Machine Diagnosis Type : Event recording || Trip history information || Starting current and time || Running hours counter/operating time || Motor control command recording || Remaining operating time before overload tripping || Fault recording || Phase fault and earth fault trip counters || Waiting time after overload tripping || Trip context information
    • Associated Fuse Rating : 4 A gG output || 0.5 A gG control circuit
    • Load Current : 5 A 250 V AC logic output || 5 A 30 V DC logic output
    • Compatibility Code : LTMR
    • Current State 0 Guaranteed : Logic input 0...40 V <= 15 mA 25 ms
    • Tightening Torque : Control circuit 4.43…5.31 lbf.in (0.5…0.6 N.m) flat 0.12 in (3 mm)
    • Input Current : 3.1 mA 100 V || 7.5 mA 240 V
    • Height : 2.40 in (61 mm)
    • Maximum Output Switching Frequency : 2 Hz
    • Web Services : Web server
    • Metering Type : Earth-fault current || Phase current I1, I2, I3 RMS || Imbalance current || Temperature || Average current Iavg
    • Operating Rate : 1800 cyc/h
    • Connection Pitch : 0.20 in (5.08 mm)
    • Logic Input Number : 6
    • Depth : 4.82 in (122.5 mm)
    • Contacts Type And Composition : 1 NO + 1 NC fault signal || 3 NO
    • Permissible Power : 480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
  • Environment
    • Standards : IEC 60947-4-1 || CSA C22.2 No 14 || IACS E10 || EN 60947-4-1 || UL 508
    • Ambient Air Temp For Storage : -40…176 °F (-40…80 °C)
    • IP Degree Of Protection : IP20
    • Protective Treatment : 12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
    • Operating Altitude : <= 6561.68 ft (2000 m) without derating
    • Product Certifications : LROS (Lloyds register of shipping) || DNV || UL || EAC || GL || CCC || BV || ABS || KERI || ATEX || NOM || RINA || RMRoS || C-tick || CSA
    • Ambient Air Temp For Op : -4…140 °F (-20…60 °C)
    • Fire Resistance : 1202 °F (650 °C) EN/IEC 60695-2-12 || 1760 °F (960 °C) UL 94
    • Mechanical Robustness : Vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || Vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || Shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
  • Main
    • Communication Port Protocol : CANopen
    • Device Application : Equipment monitoring and control
    • Product Name : TeSys T
    • Bus Type : CANopen ISO 1198 1...127 10...1000 kbit/s, SUB-D 9 4 twisted shielded pairs cable || CANopen ISO 1198 1...127 10...1000 kbit/s, terminal block 4 twisted shielded pairs cable
    • Product Or Component Type : Motor controller
    • Supply Voltage Limits : 93.5…264 V AC
    • Current Consumption : 8...62.8 mA
    • Measurement Current : 5…100 A
    • Device Short Name : LTMR
    • Range : TeSys
    • [Us] Rated Supply Voltage : 100...240 V AC 50/60 Hz