Motor Circuit Protector, TeSys BV4, high fault, 80A, 600Y/347 VAC, 320 to 650 instantaneous trip, up to 100kA SCCR

Motor Circuit Protector, TeSys BV4, high fault, 80A, 600Y/347 VAC, 320 to 650 instantaneous trip, up to 100kA SCCR

SQDBV4T080J BV4T080J 360648132842
0.00 / EA
  • Certifications: CSA, UL
  • Color: Gray
  • Depth: 116 mm
  • Height: 162 mm
  • Line Rated Current: 40 °C, 80 A
  • Mounting Type: By Clips, By Screws
  • Net Weight: 1.5 kg
  • Standard: CSA C22.2 No 5, UL 489
  • Storage Temperature: -50-85 °C
  • Strip Length: 20 mm
  • Width: 81 mm
The TeSys BV4 motor circuit protector allows for compact motor protection in conjunction with both the TeSys and Square D NEMA product families for motor control. These protectors have UL508 type D combination ratings in accordance to current NEC installation requirements The BV4 is a magnetic only protector. It is a UL489 Listed circuit protector rated up to 100kA short circuit protection rating per a listed combination motor controller rating. This 3 pole motor circuit protector with high fault has a 80A rating. It also has an adjustable instantaneous trip rating of 320 to 1150 amperes. BV4 protectors have wiring terminals with the EverLink patented technology. These terminals reduce the risk of loose bare cables due to copper creeping. Vibration withstand is improved and periodic retightening is no longer needed. BV4 motor circuit protectors can be installed directly to a panel or on standard DIN rail. This circuit protector is 6.38 inches tall, 3.19 inches wide and 4.57 inches deep. This motor circuit protector is UL Listed and CSA certified.
  • Product Description
  • Specifications
The TeSys BV4 motor circuit protector allows for compact motor protection in conjunction with both the TeSys and Square D NEMA product families for motor control. These protectors have UL508 type D combination ratings in accordance to current NEC installation requirements The BV4 is a magnetic only protector. It is a UL489 Listed circuit protector rated up to 100kA short circuit protection rating per a listed combination motor controller rating. This 3 pole motor circuit protector with high fault has a 80A rating. It also has an adjustable instantaneous trip rating of 320 to 1150 amperes. BV4 protectors have wiring terminals with the EverLink patented technology. These terminals reduce the risk of loose bare cables due to copper creeping. Vibration withstand is improved and periodic retightening is no longer needed. BV4 motor circuit protectors can be installed directly to a panel or on standard DIN rail. This circuit protector is 6.38 inches tall, 3.19 inches wide and 4.57 inches deep. This motor circuit protector is UL Listed and CSA certified.
  • Tightening Torque : 5-5 N.m 10-10 mm² (AWG 8) || 9-9 N.m 16-16 mm² (AWG 6)
  • Local Signalling : for presence of auxiliary contacts flag (green)
  • Connections - Terminals : 2 EverLink BTR screw connectors 1.5-70 mm² AWG 14...AWG 2/0), solid copper || 2 EverLink BTR screw connectors 1.5-50 mm² AWG 6...AWG 1/0), flexible copper
  • Poles Description : 3P
  • Wire Stripping Length : 20 mm
  • Maximum Width : 81 mm
  • Operating Altitude : 6561.68 ft (2000 m) without derating || > 2000...5000 m with derating
  • Product Certifications : CSA || UL
  • Product Or Component Type : Motor Circuit Protector
  • Line Rated Current : 80 A 40 °C
  • Product Name : TeSys BV4
  • Device Application : motor
  • Ambient Air Temperature For Operation : -25-70 °C
  • Net Weight : 1.5 kg
  • Range : TeSys
  • Connection Pitch : 27 mm
  • Electrical Durability : 14000 cycles AC-3 440 V In/2 || 7000 cycles AC-3 440 V In
  • Number Of Slots : 1 alarm switch fault signalling contact, plug-in || 1 voltage release electrical remote tripping, plug-in || 1 auxiliary switch open/close contact, plug-in
  • Quantity Per Set : 1
  • Trip Unit Rating : 320-1150 A 40 °C
  • Maximum Height : 162 mm
  • Mechanical Robustness : vibrations +/- 1 mm 2...13.2 Hz IEC 60068-2-6 || vibrations 0.7 gn 13.2...100 Hz IEC 60068-2-6 || shocks 15 gn 11 ms IEC 60068-2-27
  • Performance Level : high performance
  • Trip Unit Technology : magnetic
  • Utilisation Category : category A
  • Mounting Support : 35 mm symmetrical DIN rail || 75 mm symmetrical DIN rail || plate
  • Standards : UL 489 || CSA C22.2 No 5
  • Ip Degree Of Protection : IP40 front face IEC 60529
  • [Ue] Rated Operational Voltage : 600Y/347 V AC 50/60 Hz
  • Color : Gray RAL 7016)
  • Ik Degree Of Protection : IK07 IEC 62262
  • Control Type : toggle
  • Protection Type : short-circuit
  • Mounting Mode : by clips || by screws
  • Ambient Air Temperature For Storage : -50-85 °C
  • Maximum Depth : 116 mm
  • Mechanical Durability : 40000 cycles
  • Device Short Name : BV4