Circuit breaker, PowerPacT P, 400A, 3 pole, 600VAC, 18kA, lugs, Micrologic 5.0, 80%

MOLDED CASE CIRCUIT BREAKER 60

SQDPGL36040U33A PGL36040U33A 785901084853
14388.51 / EA
http://schema.org/OutOfStock
  • Certifications: CSA, NOM, UL
  • Depth: 8.05 in
  • Height: 12.86 in
  • Line Rated Current: 400-400 A
  • Net Weight: 32 lb
  • Standard: CSA, IEC 60947-2, NEMA, NOM-003-SCFI-2000, UL
  • Storage Temperature: -50-85 °C
  • Strip Length: 25 mm
  • Warranty Length: 18 mth
  • Width: 8.27 in
PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard with a 5.0 trip unit and an LSI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 400A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
QTY
  • Product Description
  • Specifications
PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard with a 5.0 trip unit and an LSI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 400A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
  • Environment
    • Ambient Air Temperature For Operation : -25-70 °C
    • Standards : UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
    • Product Certifications : UL || CSA || NOM
    • Ip Degree Of Protection : front cover IP40
    • Pollution Degree : 3 IEC 60947-1
    • Ambient Air Temperature For Storage : -50-85 °C
    • Quality Labels : CE
    • Operating Altitude : < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP2206033EN
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Reach Regulation : Reference contains Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Circularity Profile : ENVEOLI2206033EN
    • Eu Rohs Directive : Compliant with Exemptions
  • Complementary
    • Network Frequency : 50/60 Hz
    • Terminal Identifier : AL800M23K
    • [Ics] Rated Service Breaking Capacity : 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
    • Trip Unit Technology : electronic, standard, MicroLogic 5.0, LSI
    • Trip Unit Name : MicroLogic 5.0
    • Height : 12.86 in
    • [Ue] Rated Operational Voltage : 600 V AC 50/60 Hz UL 489
    • Tightening Torque : 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
    • Breaking Capacity Code : G
    • Local Signalling : overload 1 1 LED amber) || 1 trip indicator green)
    • Number Of Slots : 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
    • Electrical Connection : lugs, load || lugs, line
    • Net Weight : 32 lb(US)
    • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947-2
    • Control Type : toggle
    • Circuit Breaker Application : HACR rated
    • Wire Stripping Length : 25 mm
    • Line Rated Current : 400-400 A
    • Long Time Pick-Up Adjustment Range : 0.4...1 x Ir
    • Continuous Current Rating : 80 %
    • Breaking Capacity : AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
    • [Ui] Rated Insulation Voltage : 750 V IEC 60947-2
    • Poles Description : 3P
    • Quantity Per Set : 1
    • Awg Gauge : 3 x AWG 3/0...500 kcmil aluminium/copper
    • Width : 8.27 in
    • Depth : 8.05 in
  • Specifications
    • Product Or Component Type : circuit breaker
    • Product Name : PowerPact P
    • Range : PowerPact
    • Device Application : distribution