Transformer, dry type, DOE 2016, 150kVA, 3 phase, 480V delta primary, 240V delta secondary, 22M, 150C rise, 120V ctr

150KVA 480-240 3 PH TRANS

SQDEXN150T6HCT EXN150T6HCT 785901521235
7324.89 / EA
http://schema.org/OutOfStock
  • Depth: 827 mm
  • Height: 1031 mm
  • Net Weight: 456.77 kg
  • Primary Voltage: 480 V
  • Temperature Rise: 150 °C, 220 °C
  • Weight: 456.77 kg
  • Width: 855 mm
EXN three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 150kVA, 480V primary (three wire), 240/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.83% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 2 for indoor installation, field convertible to Type 3R via weathershield for outdoor installation. The transformers are floor mounted but field accessories are available for wall or trapeze (ceiling) mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
QTY
  • Product Description
  • Features
  • Specifications
EXN three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 150kVA, 480V primary (three wire), 240/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.83% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 2 for indoor installation, field convertible to Type 3R via weathershield for outdoor installation. The transformers are floor mounted but field accessories are available for wall or trapeze (ceiling) mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Complementary
    • Tap Loss : 306 no load (core loss) || 2721 load loss (coil loss)
    • Primary Voltage : 480 V delta
    • Network Frequency : 60 Hz
    • Percentage Impedance Voltage : 3.08 %
    • Height : 1031 mm
    • Number Of Mounting Holes : 4 Ø: 13 mm
    • [Uimp] Rated Impulse Withstand Voltage : 10 kV
    • Primary Operational Current : 180.42-180.42 A 360.84 A 150 kVA
    • Temperature Rise : 150 °C || 220 °C insulated
    • Degree Of Protection : UL type 2 || UL type 3R, with 7400WS22M
    • Number Of Tap-Offs : 2 2.5 % FCAN || 4 2.5 % FCBN
    • X/R Ratio : 1.66
    • Rated Operational Power In Va : 150 kVA
    • Electrical Connection : 4 Hole Nema Pad secondary 11.1 mm || 2 Hole Nema Pad primary 11.1 mm
    • Phase : 3 phase
    • Material : aluminium
    • Net Weight : 456.77 kg
    • Secondary Voltage : 240 V delta || centre tap 120 V
    • Percentage Reactance : 2.57 %
    • Noise Level : 47 dB || 3 dB NEMA ST-20
    • Type Of Cooling : natural convection
    • Efficiency : 98.91 % at 35 % load factor , 75.0 °C
    • Mounting Support : floor || floor, with 7400FMB || ceiling, with 7400CMB22M
    • Continuous Thermal Current Rating Factor : 1302 16.6 % || 1624 25 % || 3365 50 % || 6267 75 % || 10329 100 %
    • Width : 855 mm
    • Depth : 827 mm
    • Inrush Current : 2053 A
    • Box Number : 22M
    • [Ipk] Rated Peak Withstand Current : 11.72 kA
  • Specifications
    • Country of Origin : Mexico
    • Width : 855 mm
    • Height : 1031 mm
    • Weight : 456.77 kg
    • Range Of Product : Square D
    • Product Or Component Type : transformer
    • Transformer Type : energy efficient
    • Device Application : low voltage electrical distribution
    • Device Short Name : DOE 2016
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP1604028_V2
    • Packaging Without Single Use Plastic : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : N/A
    • Take-Back : No
    • Declare : Red list free
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 41849.771116209464
  • Environment
    • Average Ambient Air Temperature For Operation : 30 °C
    • Ambient Air Temperature For Operation : 40-40 °C
    • Standards : UL 1561 || CSA C22.2 No 47 || NEMA ST-20