SQUARE D

IEC contactor, TeSys Deca, nonreversing, 80A resistive, 4 pole, 2 NO and 2 NC, 42VAC 50/60Hz coil, open style

IEC CONTACTOR, TESYS DECA, NON

SQDLC1D65008D7 LC1D65008D7 3389110265514
860.85 / EA
http://schema.org/OutOfStock
  • Depth: 125 mm
  • Warranty Length: 18 mth
TeSys Deca contactor, 4 poles (2NO+2NC), for non-inductive load applications up to 80A/690V AC-1. They can be used to create motor starters for almost any type of application. It provides a 42V 50/60Hz AC coil, power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (85mm width), DIN-rail mounting or screw fixing. Without build-in auxiliary contacts, side and front mounting auxiliary contact blocks available (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 4.92 inches deep. It weighs 3.20 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.
QTY
  • Product Description
  • Features
  • Specifications
TeSys Deca contactor, 4 poles (2NO+2NC), for non-inductive load applications up to 80A/690V AC-1. They can be used to create motor starters for almost any type of application. It provides a 42V 50/60Hz AC coil, power connection by screw terminals, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (85mm width), DIN-rail mounting or screw fixing. Without build-in auxiliary contacts, side and front mounting auxiliary contact blocks available (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine). Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 5.00 inches tall, 3.35 inches wide and 4.92 inches deep. It weighs 3.20 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards.
  • Features
    • New modern look & feel of all machines
    • Designed to meet the requirements of industrial and HVAC applications
    • Easier to install and operate with multi-standard screws
    • With IEC60335-1 compliance, improved fire resistance, and dustproof auxiliaries
    • Digital customer experience for technical documents
    • Maintenance guide via EcoStruxureTM Facility Expect
    • Compatible for all the voltages on the market
    • Multiple international certifications
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Conformance Attributes
    • Product Certifications : CCC, UL, CSA, BV, GL, RINA, DNV, GOST, LROS (Lloyds register of shipping)
    • Standards : CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1
  • Complementary Attributes
    • Control Circuit Voltage Limits : 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz, 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz, 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz
    • Control Circuit Type : AC 50/60 Hz
    • IRMS Rated Making Capacity : 1000 A at 440 V for power circuit conforming to IEC 60947
    • Maximum Operating Rate : 3600 cyc/h at 60 °C
    • Rated Breaking Capacity : 1000 A at 440 V for power circuit conforming to IEC 60947
  • Important Information Attributes
    • Persona Type Ids : EU, LC, OM, OM8, PB, SI
    • Persona Type Names : End User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder, System Integrator
    • Market Segmentation Id : COMMERCIAL, INDUSTRIAL
    • Market Segmentation : Commercial, Industrial
    • Associated Fuse Rating : 125 A gG at <= 690 V coordination type 1 for power circuit, 125 A gG at <= 690 V coordination type 2 for power circuit
    • Hold In Power Consumption In VA : 13-13 VA 60 Hz cos phi 0.3 (at 20 °C), 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
    • Inrush Power In VA : 140-140 VA 60 Hz cos phi 0.75 (at 20 °C), 160-160 VA 50 Hz cos phi 0.75 (at 20 °C)
    • Mechanical Robustness : shocks contactor open 8 Gn for 11 ms), shocks contactor closed 10 Gn for 11 ms), vibrations contactor opened 2 Gn, 5...300 Hz), vibrations contactor closed 3 Gn, 5...300 Hz)
    • Mounting Support : plate, rail
    • Operating Time : 4...19 ms opening, 12...26 ms closing
    • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm, control circuit 1.7 N.m screw clamp terminals Philips No 2, power circuit 8 N.m screw clamp terminals 25-35 mm² hexagonal 4 mm, power circuit 5 N.m screw clamp terminals 1-25 mm² hexagonal 4 mm, control circuit 1.7 N.m screw clamp terminals pozidriv No 2
    • Icw Rated Short Time Withstand Current2 : 640 A 40 °C - 10 s for power circuit, 900 A 40 °C - 1 s for power circuit, 110 A 40 °C - 10 min for power circuit, 260 A 40 °C - 1 min for power circuit
    • Uc Control Circuit Voltage2 : 42 V, 42 V AC 50/60 Hz
    • Ue Rated Operational Voltage2 : power circuit <= 690 V AC 25...400 Hz, power circuit <= 300 V DC
    • Ui Rated Insulation Voltage2 : power circuit 600 V CSA, power circuit 600 V UL, power circuit 690 V IEC 60947-4-1
    • Carbon Footprint Of The Distribution Phase A4 : 0.18215610334927448, 0.2 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 3.444713035648395, 3 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase A5 : 0.3 kg CO2 eq., 0.26117718842388454
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 9 kg CO2 eq., 9.23368400909753
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 57 kg CO2 eq., 56.91943840579708
    • Connections Terminals : screw clamp terminals, control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible without cable end
    • Connections Terminals3 : control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible without cable end, power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: flexible without cable end, power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminals 1 1-35 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminals 2 1-25 mm² - cable stiffness: solid without cable end
    • Icw Rated Short Time Withstand Current5 : 640 A 40 °C - 10 s for power circuit, 900 A 40 °C - 1 s for power circuit, 110 A 40 °C - 10 min for power circuit, 260 A 40 °C - 1 min for power circuit
    • Ue Rated Operational Voltage5 : power circuit <= 690 V AC 25...400 Hz, power circuit <= 300 V DC
    • Ui Rated Insulation Voltage5 : power circuit 600 V CSA, power circuit 600 V UL, power circuit 690 V IEC 60947-4-1
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-02-26
    • Device Type : LV equipment - LV contactor
    • Serviceability : No
    • Traceability : No
    • Field Service Division : PPIBS
    • Average Life Duration : 20 year(s)
    • Legacy WEEE Scope : In
    • Scope Perimeter : At least in Europe
    • EOLI Availability Display : No need of specific recycling operations
    • Reach Full Compliance Status : Free of Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : NOT_CONTAINING_SVHC
    • Reach Compliance Directive : Free of Substances of Very High Concern above the threshold
    • ROHS EUR In Scope : Yes
    • ROHS EUR Status : Compliant
    • ROHS EUR Full Compliance Status : Compliant
    • ROHS EUR Full Compliance Status Id : COMPLIANT
    • China ROHS In Scope : No
    • Green Premium Status For Reporting : Green Premium product
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Return Indicator : N
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz for power circuit
    • Coil Technology : without built-in suppressor module
    • Compatibility Code : LC1D
    • Contact Compatibility : M1
    • Contactor Application : resistive load
    • Device Short Name : LC1D
    • Electrical Durability : 1.4 Mcycles 80 A AC-1 <= 440 V
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Flame Retardance : V1 conforming to UL 94
    • Heat Dissipation : 4-5 W at 50/60 Hz
    • Mechanical Durability : 6 Mcycles
    • Overvoltage Category : III
    • Package Weight Lbs : 1.500 kg
    • Pole Contact Composition : 2 NO + 2 NC
    • Poles Description : 4P
    • Power Dissipation Per Pole : 9.6 W AC-1
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Or Component Type : contactor
    • Protective Treatment : THIEC 60068-2-30
    • Range : TeSys
    • Range Of Product : TeSys Deca
    • Returnability : No
    • Sustainable Packaging : Yes
    • Total Lifecycle Carbon Footprint : 70 kg CO2 eq.
    • Utilisation Category : AC-1
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • Ie Rated Operational Current2 : 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
    • Ith Conventional Free Air Thermal Current2 : 80 A (at 60 °C) for power circuit
    • Uimp Rated Impulse Withstand Voltage2 : 6 kV IEC 60947
    • Medium Desc : IEC contactor, TeSys Deca, nonreversing, 80A resistive, 4 pole, 2 NO and 2 NC, 42VAC 50/60Hz coil, open style
    • Stocking Flag : Y
    • Product Kit Identifier : N
    • Rated Thermal Current Ith2 : 80 A
    • Rated Thermal Current Ith3 : 80 A
    • Pep Code : ENVPEP1102005EN
    • Database Version : 2022-01
    • Pep Verification Date : 2025-11-20
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed2-2016 03 29
    • Type Of Verification For The Pep : Independent internal review
    • Data Source : extrapolated product
    • Functional Unit Description : Switch on and off during 20 years electrical power supply of a downstream installation with an electrical and/or mechanical control. The functional unit is characterized by a type 3P(3NO), a control circuit voltage 230V AC, a power circuit voltage 690V and a rated operational current 80A
    • Functional Unit Unit : unit
    • Energy Model Manufacturing A1 A3 2 : Electricity Mix; Production mix; Low voltage; CZ
    • Energy Model Installation A5 2 : Electricity Mix; Production mix; Low voltage; FR
    • Energy Model Use B6 2 : Electricity Mix; Production mix; Low voltage; FR
    • Energy Model End Of Life C1 C4 2 : Electricity Mix; Production mix; Low voltage; FR
    • Global Commercial Status : Commercialised
    • Ie Rated Operational Current5 : 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
    • Ith Conventional Free Air Thermal Current5 : 80 A (at 60 °C) for power circuit
    • Uc Control Circuit Voltage5 : 42 V AC 50/60 Hz
    • Uimp Rated Impulse Withstand Voltage5 : 6 kV IEC 60947
  • Environment Attributes Main
    • Take Back : Nej, No
    • China ROHS Regulation : Product out of China RoHS scope , Pro-active China RoHS declaration (out of China RoHS legal scope)
    • EU ROHS Directive : Compliant , Compliant
    • Permissible Ambient Air Temperature Around The Device : -40-60 °C, -40-60 °C, 60-70 °C with derating
    • ROHS Exemption Information : Yes
    • Reach Free SHVC : Yes
    • Recycled Metal Content At Cr Level : 0 %
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Carbon Footprint : 70.04116874231616
    • Climatic Withstand : IACS E10 exposure to damp heat
    • Environmental Disclosure : ENVPEP1102005EN
    • IP Degree Of Protection : IP20 front face IEC 60529
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Free Of SVHC : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Pep Code : ENVPEP1102005EN
    • Pep Verification Date : 2025-11-20
    • Pcr Version : PEP-PCR-ed4-2021 09 06
    • Psr Version : PSR-0005-ed2-2016 03 29
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : contactor
    • Range Of Product : TeSys Deca
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months
  • Specifications
    • Depth : 125 mm