SQUARE D

IEC contactor, TeSys Deca, nonreversing, 80A, 40HP at 480VAC, 3 phase, 3 pole, 3 NO, 400VAC 50/60Hz coil, open style

IEC CONTACTOR, TESYS DECA, NON

SQDLC1D80AV7 LC1D80AV7 3606481312235
440.37 / EA
http://schema.org/OutOfStock
QTY
  • Product Description
  • Specifications
TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 66A/440V AC-3 (37kW@400V). They can be used to create motor starters for almost any type of application. It provides a 400V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by EverLink BTR screw connectors, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (55mm width), DIN-rail mounting or screw fixing. Contactor is rated for 25HP at 200 to 208VAC, 30HP at 240VAC, 40HP at 480VAC and 60HP at 600VAC three phase. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh). Contactor is supplied with a 400 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
  • Environment
    • Product Certifications : CCC || CSA || EAC || UL || KC || DNV-GL || LROS (Lloyds register of shipping)
    • Height : 122 mm
    • Standards : EN/IEC 60947-4-1 || EN/IEC 60947-5-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1 || IEC 60335-1
    • Climatic Withstand : IACS E10 exposure to damp heat || IEC 60947-1 Annex Q category D exposure to damp heat
    • Net Weight : 0.86 kg
    • Flame Retardance : V1 conforming to UL 94
    • Protective Treatment : THIEC 60068-2-30
    • Ip Degree Of Protection : IP20 front face IEC 60529
    • Mechanical Robustness : vibrations contactor open 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor closed 15 Gn for 11 ms) || shocks contactor open 10 Gn for 11 ms)
    • Operating Altitude : 0...9842.52 ft (0...3000 m)
    • Fire Resistance : 850 °C IEC 60695-2-1
    • Width : 55 mm
    • Depth : 120 mm
    • Permissible Ambient Air Temperature Around The Device : -40-60 °C || 60-70 °C with derating
  • Contractual warranty
    • Warranty : 18 months
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1503009EN
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Reach Free Of Svhc : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Circularity Profile : ENVEOLI1503009EN
    • Eu Rohs Directive : Compliant
  • Complementary
    • Non-Overlap Time : 1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
    • Minimum Switching Current : 5 mA for signalling circuit
    • Power Dissipation Per Pole : 9.6 W AC-1 || 6.3 W AC-3 || 6.3 W AC-3e
    • Average Impedance : 1.5 mOhm - Ith 80 A 50 Hz for power circuit
    • Auxiliary Contact Composition : 1 NO + 1 NC
    • [Ith] Conventional Free Air Thermal Current : 10 A (at 60 °C) for signalling circuit || 80 A (at 60 °C) for power circuit
    • Control Circuit Voltage Limits : 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz || 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
    • Mounting Support : plate || rail
    • Control Circuit Type : AC 50/60 Hz standard
    • Safety Reliability Level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
    • Pollution Degree : 3
    • Insulation Resistance : > 10 MOhm for signalling circuit
    • Rated Breaking Capacity : 1000 A at 440 V for power circuit conforming to IEC 60947
    • Irms Rated Making Capacity : 140 A AC for signalling circuit conforming to IEC 60947-5-1 || 250 A DC for signalling circuit conforming to IEC 60947-5-1 || 1000 A at 440 V AC for power circuit conforming to IEC 60947
    • Associated Fuse Rating : 10 A gG for signalling circuit conforming to IEC 60947-5-1 || 125 A gG at <= 690 V coordination type 1 for power circuit || 125 A gG at <= 690 V coordination type 2 for power circuit
    • Inrush Power In Va : 140-140 VA 60 Hz cos phi 0.75 (at 20 °C) || 160-160 VA 50 Hz cos phi 0.75 (at 20 °C)
    • [Uimp] Rated Impulse Withstand Voltage : 6 kV IEC 60947
    • Pole Contact Composition : 3 NO
    • Connections - Terminals : control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible with cable end || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: solid || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: solid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible || power circuit: EverLink BTR screw connectors 1 1-35 mm² - cable stiffness: flexible || power circuit: EverLink BTR screw connectors 2 1-25 mm² - cable stiffness: flexible
    • Coil Technology : without built-in suppressor module
    • Operating Time : 4...19 ms opening || 12...26 ms closing
    • Minimum Switching Voltage : 17 V for signalling circuit
    • Maximum Operating Rate : 3600 cyc/h 60 °C
    • Signalling Circuit Frequency : 25...400 Hz
    • Tightening Torque : control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm || power circuit 5 N.m EverLink BTR screw connectors 1-25 mm² hexagonal 4 mm || control circuit 1.7 N.m screw clamp terminals pozidriv No 2 || power circuit 2.5 N.m screw clamp terminals pozidriv No 2
    • Electrical Durability : 0.7 Mcycles 80 A AC-1 <= 440 V || 1 Mcycles 66 A AC-3 <= 440 V || 1 Mcycles 66 A AC-3e <= 440 V
    • Mechanical Durability : 6 Mcycles
    • Auxiliary Contacts Type : mechanically linked 1 NO + 1 NC IEC 60947-5-1 || mirror contact 1 NC IEC 60947-4-1
    • Compatibility Code : LC1D
    • Hold-In Power Consumption In Va : 13-13 VA 60 Hz cos phi 0.3 (at 20 °C) || 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
    • Overvoltage Category : III
    • Maximum Horse Power Rating : 5 hp at 115 V AC 60 Hz for 1 phase motors || 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp at 575/600 V AC 60 Hz for 3 phase motors
    • Motor Power Kw : 22 kW at 220...230 V AC 50/60 Hz (AC-3) || 37 kW at 380...400 V AC 50/60 Hz (AC-3) || 37 kW at 415 V AC 50/60 Hz (AC-3) || 37 kW at 440 V AC 50/60 Hz (AC-3) || 37 kW at 500 V AC 50/60 Hz (AC-3) || 37 kW at 660...690 V AC 50/60 Hz (AC-3) || 22 kW at 220...230 V AC 50/60 Hz (AC-3e) || 37 kW at 380...400 V AC 50/60 Hz (AC-3e) || 37 kW at 415 V AC 50/60 Hz (AC-3e) || 37 kW at 440 V AC 50/60 Hz (AC-3e) || 37 kW at 500 V AC 50/60 Hz (AC-3e) || 37 kW at 660...690 V AC 50/60 Hz (AC-3e)
    • [Ui] Rated Insulation Voltage : signalling circuit 690 V IEC 60947-1 || power circuit 690 V IEC 60947-4-1
    • [Icw] Rated Short-Time Withstand Current : 640 A 40 °C - 10 s for power circuit || 900 A 40 °C - 1 s for power circuit || 110 A 40 °C - 10 min for power circuit || 260 A 40 °C - 1 min for power circuit || 100 A - 1 s for signalling circuit || 120 A - 500 ms for signalling circuit || 140 A - 100 ms for signalling circuit
    • Heat Dissipation : 4-5 W at 50/60 Hz
    • Protective Cover : with
  • Specifications
    • Country of Origin : Indonesia
    • Width : 55 mm
    • Height : 122 mm
    • Weight : 0.86 kg
    • [Uc] Control Circuit Voltage : 400 V AC 50/60 Hz
    • [Ue] Rated Operational Voltage : power circuit 690 V AC 25...400 Hz || power circuit 300 V DC
    • Range Of Product : TeSys Deca
    • Contactor Application : motor control || resistive load
    • Product Or Component Type : contactor
    • Range : TeSys || TeSys Deca
    • Utilisation Category : AC-1 || AC-4 || AC-3 || AC-3e
    • [Ie] Rated Operational Current : 80 A (at <60 °C) at <= 440 V AC-1 for power circuit || 66 A (at <60 °C) at <= 440 V AC-3 for power circuit || 66 A (at <60 °C) at <= 440 V AC-3e for power circuit
    • Poles Description : 3P
    • Device Short Name : LC1D