Enercept Meter, class 0.2S, Modbus/BACnet RS485, Split Core 100A, ANSI wire code

Enercept Meter, class 0.2S, Mo

SQDMETSEEM4236B101 3606489564698
1432.09 / EA
http://schema.org/OutOfStock
  • Certifications: ANSI, BTL, CE EN 61010-1, CULus UL 61010-1
  • Depth: 35.81 mm
  • Height: 152.36 mm
  • Line Rated Current: 100 A
  • Mounting Type: By Hook, By Screws
  • Number of Outputs: 0
  • Standard: CAN/CSA C22.2 No. 61010-1-12, EN 61010-1, UL 61010-1
  • Storage Temperature: -40-85 °C
  • Strip Length: 6 mm
  • Width: 46.63 mm
The PowerLogic EM4200 Series Enercept power and energy meter is a unique compact retrofit solution for measuring energy data. This bundle ships with 3, 100 A split-core current transformers. Accuracy calibrated at 1%. ANSI version, fuse packs factory mounted. Designed for simplicity, the EM4200 has flexibility of a wide range of Current Transducers to match most applications from 50-5000A. This billing-rated, four-quadrant meter offers BACnet and Modbus communication protocols and supply power options from 90-480VAC. ANSI C12.1 rated and UL 61010-1.
QTY
  • Product Description
  • Specifications
The PowerLogic EM4200 Series Enercept power and energy meter is a unique compact retrofit solution for measuring energy data. This bundle ships with 3, 100 A split-core current transformers. Accuracy calibrated at 1%. ANSI version, fuse packs factory mounted. Designed for simplicity, the EM4200 has flexibility of a wide range of Current Transducers to match most applications from 50-5000A. This billing-rated, four-quadrant meter offers BACnet and Modbus communication protocols and supply power options from 90-480VAC. ANSI C12.1 rated and UL 61010-1.
  • Complementary
    • Network Frequency : 50 Hz || 60 Hz
    • Provided Equipment : bracket for support || hook || split core current transducer 3 || fuse
    • Height : 152.36 mm
    • Measurement Voltage : 90-90 V AC 45...65 Hz minimum per phase || 480-480 V AC 45...65 Hz between phases || 300-300 V AC 45...65 Hz between phase and neutral
    • Number Of Outputs : 0
    • Standards : EN 61010-1 || UL 61010-1 || CAN/CSA C22.2 No. 61010-1-12
    • Product Certifications : CE EN 61010-1 || cULus UL 61010-1 || BTL || ANSI
    • Communication Port Protocol : Modbus RTU 9600 bauds...115200 bauds (automatic detection) || BACnet MS/TP 9600 bauds...115200 bauds (automatic detection)
    • Frequency Measurement Range : 45-65 Hz
    • Communication Of Data : remote control orders || total energy || net energy
    • Number Of Inputs : 0
    • Depth : 35.81 mm
    • Measurement Current : 0-100 A
    • Wire Stripping Length : 6 mm
    • Local Signalling : status LED green and red) || line fault 3 LED green, orange and red) || dial pointer indication LED Yellow) || RX/TX 2 LED green, orange and red)
    • Connections - Terminals : input/output plug-in connector bottom) 0.2-1.5 mm² || current transformer plug-in connector bottom) 0.2-1.5 mm² || communication plug-in connector bottom) 0.2-1.5 mm²
    • Function Available : external synchronisation to communication || fixed or rolling block
    • Mounting Mode : by screws || clip-on || by hook
    • Measurement Accuracy : 1 %
    • Mounting Support : enclosure || DIN rail
    • Line Rated Current : 100 A
    • Analogue Input Type : split core current transducer 0.333 V (impedance 33 kOhm) || voltage (impedance 2.5 MOhm)single phase || voltage (impedance 5 MOhm)phase to phase
    • Width : 46.63 mm
    • Display Type : Without Display
    • Accuracy Class : class 1 ANSI C12.1 || class 1S IEC 62053-22
    • Metering Type : active, reactive, apparent energy (signed, four quadrant) || apparent power S, S1, S2, S3 || demand power P, Q, S || active power P, P1, P2, P3 || reactive power Q, Q1, Q2, Q3 || power factor || average current Iavg || peak demand power PM, QM, SM || frequency || voltage U21, U32, U13, V1, V2, V3
  • Environment
    • Ambient Air Temperature For Operation : -30-70 °C
    • Electromagnetic Compatibility : conducted and radiated emissions conforming to FCC Part 15 class A || conducted and radiated emissions conforming to EN 61000-6-4 || conducted and radiated emissions conforming to EN 61326 + A1 || immunity to conducted disturbances conforming to EN 61000-6-2 || immunity to conducted disturbances conforming to EN 61326-1 || immunity to radiated fields conforming to EN 61000-6-2 || immunity to radiated fields conforming to EN 61326-1
    • Pollution Degree : 2
    • Ambient Air Temperature For Storage : -40-85 °C
    • Relative Humidity : 0-95 %
    • Ip Degree Of Protection : IP20 conforming to IEC 60529
    • Measurement Category : category III 277-277 V || category III 300-300 V
    • Operating Altitude : < 9842.52 ft (3000 m)
  • Specifications
    • Product Or Component Type : energy meter
    • Product Name : PowerLogic EM4200
    • Type Of Cable : ANSI cable
    • Range : PowerLogic
    • Device Application : power monitoring
    • Device Short Name : Enercept
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Eu Rohs Directive : Compliant with Exemptions