EM4000 multi-circuit energy meter, 24 x 80 mA inputs, 120V control power 60 Hz

EM4000 MULTI-CIRCUIT ENERGY ME

SQDMETSEEM408016 METSEEM408016 SQDMETSEEM408016
0.00 / EA
http://schema.org/OutOfStock
This multi-circuit power meter is part of the PowerLogic EM4000 Series. This compact multi-circuit energy meter enables reliable metering of building electrical loads with a low installation cost-per-point. It combine revenue-accurate electricity sub-metering with advanced communications technology. It is ideal for departmental metering applications and M&V within office, condominiums, malls and other multi-user environments. This version monitor up to 24 tenants with a single device, combined with 80 mA solid core current transformers. Designed for 277 (phase neutral) or 480 volts (phase phase) networks, working at 60 Hz. Measurement accuracy is plus or minus 0.5 %, compliant with ANSI C12.1 and C12.20 Class 0.5 ; IEC 62053-22 Class 0.5S. The printed board is installed in a Type 1 black enclosure, with an integrated backlit LCD display, 2 lines, on the door. Mechanical dimensions are 335 mm in width, 305 mm in height and 55 mm in depth ; for 4 kg.
QTY
  • Product Description
  • Specifications
This multi-circuit power meter is part of the PowerLogic EM4000 Series. This compact multi-circuit energy meter enables reliable metering of building electrical loads with a low installation cost-per-point. It combine revenue-accurate electricity sub-metering with advanced communications technology. It is ideal for departmental metering applications and M&V within office, condominiums, malls and other multi-user environments. This version monitor up to 24 tenants with a single device, combined with 80 mA solid core current transformers. Designed for 277 (phase neutral) or 480 volts (phase phase) networks, working at 60 Hz. Measurement accuracy is plus or minus 0.5 %, compliant with ANSI C12.1 and C12.20 Class 0.5 ; IEC 62053-22 Class 0.5S. The printed board is installed in a Type 1 black enclosure, with an integrated backlit LCD display, 2 lines, on the door. Mechanical dimensions are 335 mm in width, 305 mm in height and 55 mm in depth ; for 4 kg.
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : "WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov"
    • Reach Free Of Svhc : Yes
    • Weee : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • China Rohs Regulation : Product out of China RoHS scope. Substance declaration for your information.
    • Eu Rohs Directive : Compliant
  • Environment
    • Ambient Air Temperature For Operation : -40-70 °C
    • Height : 33.5 cm
    • Standards : IEC 6100-4-5 || ICES-003 || FCC Part 15 class B || CSA C22.2 No 61010-1 || EN 55022 || ANSI/TIA-968-A : 2002 || CSA C22.2 No 61010-1-4
    • Device Mounting : wall mounted
    • Product Certifications : UL
    • Enclosure Type : NEMA type 1
    • Net Weight : 4 kg
    • Type Of Installation : enclosed outdoor || indoor installation
    • Pollution Degree : 2
    • Mounting Mode : wall mount
    • Ambient Air Temperature For Storage : -40-70 °C
    • Relative Humidity : 90-90 % 40-40 °C
    • Width : 30.5 cm
    • Depth : 5.5 cm
    • Operating Altitude : <= 9842.52 ft (3000 m)
  • Specifications
    • Country of Origin : Canada
    • Width : 30.5 cm
    • Height : 33.5 cm
    • Weight : 4 kg
    • Network Frequency : 60 Hz
    • Power Quality Analysis : compliance monitoring
    • Type Of Measurement : current per phase, rms || negative active energy || voltage per phase, rms || negative reactive energy || apparent energy || pulse count || active and reactive power || apparent power || positive active energy || positive reactive energy
    • Power Monitoring : basic instrumentation
    • Product Or Component Type : multi-circuit energy meter
    • Product Name : PowerLogic EM4000
    • Range : PowerLogic
    • Energy Management : sub billing and cost allocation || billing analysis
    • [Us] Rated Supply Voltage : 120 V AC 60 Hz
    • Device Application : sub billing
    • Device Short Name : EM4080
  • Complementary
    • Communication Port Support : RJ45 ETHERNET || RS485
    • Measurement Voltage : 80-480 V without PTs || 480-999000 V with external PTs
    • Sampling Rate : 256 samples/cycle
    • Communication Port Protocol : BACnet IP || FTP || HTTP || Modbus TCP/IP || SNTP
    • Communication Of Data : negative active energy || positive active energy || voltage || positive reactive energy || apparent energy || negative reactive energy
    • Number Of Inputs : 2 pulse
    • Messages Display Capacity : 2 lines of 16 characters
    • Measurement Accuracy : +/- 0.5 % of the measuring range
    • Analogue Input Type : solid core CT 80 mA24 x single pole || solid core CT 80 mA12 x single phase || solid core CT 80 mA8 x three phase
    • Display Type : Backlit LCD