SQUARE D

Transformer, dry type, DOE 2016, 30kVA, 3 phase, 480V delta primary, 208Y/120V secondary, 18K, 115C rise, K13

TRANSFORMER DRY TYPE 30KVA 480

SQDEX30T3HFNLP EX30T3HFNLP 785901544869
5254.57 / EA
http://schema.org/OutOfStock
  • Country of Origin: USA
  • Depth: 533 mm
  • Height: 897 mm
  • Net Weight: 224.53 kg
  • Primary Voltage: 480 V
  • Temperature Rise: 115 °C, 220 °C
  • Weight: 224.53 kg
  • Width: 648 mm
EX three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 30kVA, 480V primary (three wire), 208Y/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 115 degree C temperature rise, K-13 rated. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.23% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 1 for indoor installation, field convertible to Type 2 via dripshield for indoor applications with dropping water or to Type 3R via weathershield for outdoor installation. The transformer's open bottom design limits the units to floor mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
QTY
  • Product Description
  • Features
  • Specifications
EX three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 30kVA, 480V primary (three wire), 208Y/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 115 degree C temperature rise, K-13 rated. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 98.23% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 1 for indoor installation, field convertible to Type 2 via dripshield for indoor applications with dropping water or to Type 3R via weathershield for outdoor installation. The transformer's open bottom design limits the units to floor mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Phenyl glycidyl ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Environmental data
    • Packaging Made With Recycled Cardboard : Yes
    • Environmental Disclosure : ENVPEP1604028_V2
    • Halogen Content Performance : Halogen free plastic parts product
    • Packaging Without Single Use Plastic : Yes
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: Phenyl glycidyl ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Circularity Profile : N/A
    • Take-Back : No
    • Declare : Red list free
    • Pvc Free : Yes
    • Carbon Footprint (Kg Co2 Eq, Total Life Cycle) : 12633.991988555003
  • Complementary
    • Tap Loss : 100.0 no load (core loss) || 501.0 load loss (coil loss)
    • Primary Voltage : 480 V delta
    • Network Frequency : 60 Hz
    • Percentage Impedance Voltage : 2.5 %
    • Height : 897 mm
    • [Uimp] Rated Impulse Withstand Voltage : 10 kV
    • Temperature Rise : 115 °C || 220 °C insulated
    • Degree Of Protection : UL type 1 || UL type 2, with 7400DS18K || UL type 3R, with 7400WS18K
    • Number Of Tap-Offs : 2 2.5 % FCAN || 4 2.5 % FCBN
    • X/R Ratio : 1.09
    • Rated Operational Power In Va : 30 kVA
    • Electrical Connection : 2 Hole Nema Pad primary 11.1 mm || 2 Hole Nema Pad secondary 11.1 mm || 4 Hole Nema Pad sec - XO 11.1 mm
    • Phase : 3 phase
    • Material : aluminium
    • Net Weight : 224.53 kg
    • Secondary Voltage : 208Y/120 V
    • Percentage Reactance : 0.0182 %
    • Noise Level : 6 dB NEMA ST-20 || 39 dB
    • Type Of Cooling : natural convection
    • Efficiency : 98.56 % at 35 % load factor , 75.0 °C
    • Mounting Support : floor || floor, with 7400FMB || ceiling, with 7400CMB18K || wall, with 7400WMB18K20K
    • Continuous Thermal Current Rating Factor : 388.30455707199997 16.6 % || 448.03825 0.25 % || 768.553 0.5 % || 1302.74425 0.75 % || 2050.612 1.0 %
    • Width : 648 mm
    • Depth : 533 mm
    • Box Number : 18K
    • [Ipk] Rated Peak Withstand Current : 3.4 kA
  • Specifications
    • Country of Origin : United States
    • Width : 648 mm
    • Height : 897 mm
    • Weight : 224.53 kg
    • Range Of Product : Square D
    • Product Or Component Type : transformer
    • Transformer Type : energy efficient
    • Device Application : low voltage electrical distribution
    • Device Short Name : DOE 2016
  • Environment
    • Average Ambient Air Temperature For Operation : 30 °C
    • Ambient Air Temperature For Operation : 40-40 °C
    • Standards : UL 1561 || CSA C22.2 No 47 || NEMA ST-20