SQUARE D

Transformer, dry type, DOE 2016, 300kVA, 3 phase, 480V delta primary, 240V delta secondary, 25J, 150C rise

DOE 2016 LV XFMR, 3 PHASE, 300

SQDEX300T6H EX300T6H SQDEX300T6H
25937.54 / EA
http://schema.org/OutOfStock
  • Depth: 832 mm
  • Efficiency: 99.13 % At 35 % Load Factor , 75.0 °C
  • Height: 1461 mm
  • Material: Aluminum
  • Net Weight: 843.68 kg
  • Number of Phases: 3
  • Secondary Voltage: 240 V
  • Standard: CSA C22.2 No 47, NEMA ST-20, UL 1561
  • Voltage: 480 V
  • Width: 1018 mm
EX three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 300kVA, 480V primary (three wire), 240V secondary (three wire) with aluminum windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 99.02% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of 1/2 inch. Units are shipped as Type 1 for indoor installation, field convertible to Type 2 via dripshield for indoor applications with dropping water or to Type 3R via weathershield for outdoor installation. The transformer's open bottom design limits the units to floor mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
QTY
  • Product Description
  • Specifications
EX three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 300kVA, 480V primary (three wire), 240V secondary (three wire) with aluminum windings with a 220 insulation system design for 150 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 99.02% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of 1/2 inch. Units are shipped as Type 1 for indoor installation, field convertible to Type 2 via dripshield for indoor applications with dropping water or to Type 3R via weathershield for outdoor installation. The transformer's open bottom design limits the units to floor mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
  • Specifications
    • Range Of Product : Square D
    • Product Or Component Type : transformer
    • Transformer Type : energy efficient
    • Device Application : low voltage electrical distribution
    • Device Short Name : DOE 2016
  • Complementary
    • Tap Loss : 484.0 load loss (coil loss) || 4423.0 no load (core loss)
    • Network Frequency : 60 Hz
    • Primary Voltage : 480 V delta
    • Percentage Impedance Voltage : 4.7 %
    • Height : 1461 mm
    • [Uimp] Rated Impulse Withstand Voltage : 10 kV
    • Temperature Rise : 150 °C || 220 °C insulated
    • Degree Of Protection : UL type 1 || UL type 2, with 7400DS25J || UL type 3R, with 7400WS25J
    • Number Of Tap-Offs : 2 2.5 % FCAN || 4 2.5 % FCBN
    • X/R Ratio : 3.05
    • Rated Operational Power In Va : 300 kVA
    • Electrical Connection : 4 Hole Nema Pad primary 11.1 mm || 6 Hole Nema Pad secondary 11.1 mm
    • Phase : 3 phase
    • Material : aluminium
    • Net Weight : 843.68 kg
    • Secondary Voltage : 240 V delta
    • Percentage Reactance : 0.0449 %
    • Noise Level : 6 dB NEMA ST-20 || 49 dB
    • Type Of Cooling : natural convection
    • Efficiency : 99.13 % at 35 % load factor , 75.0 °C
    • Mounting Support : floor || floor, with 7400FMB
    • Continuous Thermal Current Rating Factor : 2067.3492364426957 16.6 % || 2594.720732125 25 % || 5424.452744499999 50 % || 10140.672765124998 75 % || 16743.380794 100 %
    • Width : 1018 mm
    • Depth : 832 mm
    • Box Number : 25J
    • [Ipk] Rated Peak Withstand Current : 15.3 kA
  • Offer Sustainability
    • Rohs Exemption Information : Yes
    • Mercury Free : Yes
    • Environmental Disclosure : ENVPEP1604028EN
    • Sustainable Offer Status : Green Premium product
    • Pvc Free : Yes
    • Toxic Heavy Metal Free : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • California Proposition 65 : WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
    • Reach Free Of Svhc : Yes
    • China Rohs Regulation : Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Circularity Profile : N/A
    • Eu Rohs Directive : Compliant
    • Halogen Content Performance : Halogen free plastic parts product
  • Environment
    • Average Ambient Air Temperature For Operation : 30 °C
    • Ambient Air Temperature For Operation : 40-40 °C
    • Standards : UL 1561 || CSA C22.2 No 47 || NEMA ST-20