SQUARE D

Transformer, dry type, DOE 2016, 300kVA, 3 phase, 480V delta primary, 208Y/120V secondary, 25J, 115C rise

Transformer Dry Type 300kVA 48

SQDEX300T3HF EX300T3HF 785901004332
29367.21 / EA
http://schema.org/OutOfStock
  • Depth: 832 mm
  • Material: Aluminum
  • Primary Voltage: 480 V
  • Temperature Rise: 115 °C, 220 °C
  • Weight: 843680 g
EX three phase low voltage dry type distribution transformers from Square D comply with DOE energy conservation standards and Natural Resources Canada (NRCan) minimum energy efficiency levels. This transformer is a 300kVA, 480V primary (three wire), 208Y/120V secondary (four wire) with aluminum windings with a 220 insulation system design for 115 degree C temperature rise. This transformer’s DOE 2016 and NRCan efficiency is a minimum of 99.02% at 35% loading and 75°C temperature. Terminals are designed to accommodate wire ranges sized for 125% of the secondary nameplate current and 250% of the primary nameplate current. The terminals allow for NEMA two hole lugs and wiring bending radius to align with the wire ranges and to allow for side and bottom access. Units are natural air cooled with exhaust vents located on the front only, allowing the transformers to be mounted with rear clearance to obstructions of ½ inch. Units are shipped as Type 1 for indoor installation, field convertible to Type 2 via dripshield for indoor applications with dropping water or to Type 3R via weathershield for outdoor installation. The transformer's open bottom design limits the units to floor mounting. EX transformers have a low sound level, with a minimum of 3dB below NEMA Standard ST-20 requirements. Units are specifically designed to function with other Square D equipment; inrush is coordinated to meet identified breaker trip curves, and IZ levels allow for let through current to match AIR levels of panelboards. See product data sheets for these values.
QTY
  • Features
  • Specifications
  • Features
    • Comes in a space-saving design and DOE 2016 fully compliant
    • Terminals sized to handle Square D equipment
    • Bending radius for side and bottom access to the transformer
    • Product characteristics conformity is certified by UL
    • .
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Phenyl Glycidyl Ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • Complementary Attributes
    • Rated Operational Power In Va : 300 kVA
    • Ipk Rated Peak Withstand Current : 19.2 kA
    • Uimp Rated Impulse Withstand Voltage : 10 kV
  • Important Information Attributes
    • Mounting Support : floor, floor, with 7400FMB
    • Noise Level : 6 dB NEMA ST-20, 49 dB
    • Temperature Rise : 115 °C, 220 °C insulated
    • Certificate Agency : UL 1561, CSA C22.2 No 47, NEMA ST-20
    • Carbon Footprint Of The Distribution Phase A4 : 159.1822010466763, 159 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 1 800 kg CO2 eq., 1800.4100672005422
    • Carbon Footprint Of The Installation Phase A5 : 0, 0 kg CO2 eq.
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 5 638 kg CO2 eq., 5638.461750840613
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 57 864 kg CO2 eq., 57863.9263136673
    • Local Data Status : Publishable
    • Local Publishable Date : 2026-09-04
    • Return Indicator : Y
    • Device Type : Transformer - dry
    • Serviceability : Yes
    • Traceability : Yes
    • Field Service Division : PSIBS
    • Average Life Duration : 25 year(s)
    • Weee Scope : In
    • Weee Product Category : 4
    • Scope Perimeter : Outside of Europe
    • Eoli Availability Display : No need of specific recycling operations
    • Reach Full Compliance Status : Free of Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : NOT_CONTAINING_SVHC
    • Reach Compliance Directive : Free of Substances of Very High Concern above the threshold
    • Rohs Eur In Scope : Yes
    • Rohs Eur Status : Compliant
    • Rohs Eur Conformity Date : 1909
    • Rohs Eur Full Compliance Status : Compliant
    • China Rohs In Scope : No
    • China Rohs Label : 1
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Product Kit Identifier : N
    • Box Number : 25J
    • Continuous Thermal Current Rating Factor : 2009.2936330036239 16.6 %2484.679152625 25 %5035.4685565 50 %9286.784229625 75 %15238.626171999998 100 %
    • Device Application : low voltage electrical distribution
    • Device Short Name : DOE 2016
    • Efficiency : 99.15 % at 35 % load factor , 75.0 °C
    • Electrical Connection : 4 Hole Nema Pad primary 11.1 mm6 Hole Nema Pad secondary 11.1 mm8 Hole Nema Pad sec - XO 11.1 mm
    • Energy Efficiency Optimized : False
    • Material : aluminium
    • Network Frequency : 60 Hz
    • Number Of Tap Offs : 2 2.5 % FCAN4 2.5 % FCBN
    • Percentage Impedance Voltage : 0.043 %
    • Percentage Reactance : 0.0414 %
    • Phase : 3 phase
    • Primary Voltage : 480 V delta
    • Product Availability : Non-Stock - Not normally stocked in distribution facility
    • Product Or Component Type : transformer
    • Range Of Product : Square D
    • Returnability : Yes
    • Secondary Voltage : 208Y/120 V
    • Software Version : v6.2.4
    • Sustainable Packaging : Yes
    • Tap Loss : 479.0 no load (core loss)3987.0 load loss (coil loss)
    • Total Lifecycle Carbon Footprint : 65 462 kg CO2 eq.
    • Transformer Type : energy efficient
    • Type Of Cooling : natural convection
    • Database Version : 2024-11
    • Data Source : extrapolated product
    • Height Nominal : 1461 mm
    • Width Nominal : 1018 mm
    • X/R Ratio : 3.11
    • Nbr. Of Units In Pkg. : 1
    • Customs Code : 8504330040
    • Halogen Free Status : Halogen free plastic parts product
    • Warranty In Months : 18
    • Functional Unit Description : Other switchgear and controlgear solutions mentioned in the scope (e.g. fuses TC32, all-or-nothing relays TC94, Measuring relays and protection equipment TC95), apply the general rules of PCR and mention in the accompanying report the functional unit, the reference product characteristics, the reference lifetime and the use scenario which are applied consistently with the relevant IEC technical standards.To step down a distribution line voltage of 75kVA to voltage levels used by the end customer at the energy efficiency requirements defined by the DOE for 20 years.
    • Functional Unit Quantity : 1
    • Functional Unit Unit : Unit
    • Reference Lifetime In Y : 20
    • Recyclability Potential In % : 95
  • Environment Attributes Main
    • China Rohs Regulation : Product out of China RoHS scope , Pro-active China RoHS declaration (out of China RoHS legal scope)
    • Take Back : No
    • Reach Free Shvc : Yes
    • Halogene Performance : Halogen free plastic parts product
    • Recycled Metal Content At Cr Level : 0 %
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Carbon Footprint : 65461.980332755134
    • Ambient Air Temperature For Operation : 40-40 °C
    • Average Ambient Air Temperature For Operation : 30 °C
    • Environmental Disclosure : ENVPEP1604028EN
    • Eu Rohs Directive : Compliant
    • Halogen Content Performance : Halogen free plastic parts product
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Free Of Svhc : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Pep Code : ENVPEP1604028EN
    • Pep Verification Date : 2025-02-01
    • Pcr Version : PCR-4-ed4-EN-2021 09 06
    • Psr Version : PSR-0005-ed3.1-EN-2023 12 08
    • Type Of Verification For The Pep : Independent external review
  • General Attributes
    • Phase : 3 phase
    • Product Or Component Type : transformer
    • Range Of Product : Square D
  • Input Attributes
    • Efficiency : 99.15 % at 35 % load factor , 75.0 °C
  • Specifications
    • Country of Origin : Mexico
    • Weight : 843680 g
    • Depth : 832 mm