DOE 2016 LV XFMR, 3 Phase, 112.5kVA, 480 Delta-208Y/120, AL, 150°C Rise-220C INS

DOE 2016 LV XFMR, 3 Phase, 112.5kVA, 480 Delta-208Y/120, AL, 150°C Rise-220C INS

SQDEXN112T3H EXN112T3H 785901357599
4995.00 / EA
  • Depth: 722 mm
  • Efficiency: 98.80 % At 35 % Load Factor , 75.0 °C
  • Height: 953 mm
  • Material: Aluminum
  • Net Weight: 328.4 kg
  • Number of Holes: 13
  • Number of Phases: 3
  • Secondary Voltage: 120 V
  • Standard: CSA C22.2 No 47, NEMA ST-20, UL 1561
  • Voltage: 480 V
  • Width: 795 mm
New Three-Phase Offering from Square D, DOE 2016 EX Exceed the efficiency levels. The DOE EX are terminals sized to handle wire ranges to match Square D circuit breakers, switches, panelboards, etc. Located to meet NEC bending radius and layout to simplifiy connections. The IZ Levels will allow for designing with the minimum AIC Panels available. The In-rush current limited to expand the Square D circuit breaker options at both 125 and 250% sizing. This DOE 2016 energy efficient transformer, is a 3 phase, 112.5 kVA, 60 Hz, with a natural convection cooling. The primary voltage of 480 V delta and a secondary voltage of 208Y/120 V. This trandformer has a rated Impedence withstand voltage of 10 kV and a temperature rise of 150 °C & 220 °C insulated. This product has an ambient air temperature of 40-40 °C and an average air temperature of 30 °C. It has an efficiency of 98.80 % and a load factor of 35 % and an ambient air temperature of 75.0 °C. With a peak withstand current of 8.44 kA and a tap loss of 222 & 2586. Dimensions for this product are 16.6 % (H), 953 mm (W), 722 mm (D) and a weight of 795 mm. This product complies to UL 1561, CSA C22.2 No 47 & NEMA ST-20.
  • Product Description
  • Specifications
New Three-Phase Offering from Square D, DOE 2016 EX Exceed the efficiency levels. The DOE EX are terminals sized to handle wire ranges to match Square D circuit breakers, switches, panelboards, etc. Located to meet NEC bending radius and layout to simplifiy connections. The IZ Levels will allow for designing with the minimum AIC Panels available. The In-rush current limited to expand the Square D circuit breaker options at both 125 and 250% sizing. This DOE 2016 energy efficient transformer, is a 3 phase, 112.5 kVA, 60 Hz, with a natural convection cooling. The primary voltage of 480 V delta and a secondary voltage of 208Y/120 V. This trandformer has a rated Impedence withstand voltage of 10 kV and a temperature rise of 150 °C & 220 °C insulated. This product has an ambient air temperature of 40-40 °C and an average air temperature of 30 °C. It has an efficiency of 98.80 % and a load factor of 35 % and an ambient air temperature of 75.0 °C. With a peak withstand current of 8.44 kA and a tap loss of 222 & 2586. Dimensions for this product are 16.6 % (H), 953 mm (W), 722 mm (D) and a weight of 795 mm. This product complies to UL 1561, CSA C22.2 No 47 & NEMA ST-20.
  • Mounting Support : floor || floor, with 7400FMB || ceiling, with 7400CMB21M
  • Temperature Rise : 150 °C || 220 °C insulated
  • Noise Level : 44 dB || 6 dB NEMA ST-20
  • Device Short Name : DOE 2016
  • Rated Operational Power In Va : 112.5 kVA
  • Primary Operational Current : 135.32-135.32 A 312.27 A 112.5 kVA
  • Average Ambient Air Temperature For Operation : 30 °C
  • Maximum Depth : 722 mm
  • Secondary Voltage : 208Y/120 V
  • Standards : UL 1561 || CSA C22.2 No 47 || NEMA ST-20
  • [Uimp] Rated Impulse Withstand Voltage : 10 kV
  • Phase : 3 phase
  • Primary Voltage : 480 V delta
  • Net Weight : 328.4 kg
  • Ambient Air Temperature For Operation : 40-40 °C
  • Tap Loss : 222 no load (core loss) || 2586 load loss (coil loss)
  • Material : aluminium
  • Efficiency : 98.80 % at 35 % load factor , 75.0 °C
  • Number Of Tap-Offs : 2 2.5 % FCAN || 4 2.5 % FCBN
  • Network Frequency : 60 Hz
  • Range Of Product : Square D
  • Device Application : low voltage electrical distribution
  • Box Number : 21M
  • Number Of Mounting Holes : 13 mm
  • Continuous Thermal Current Rating Factor : 1003 16.6 % || 1309 25 % || 2963 50 % || 5721 75 % || 9581 100 %
  • [Ipk] Rated Peak Withstand Current : 8.44 kA
  • Maximum Height : 953 mm
  • Percentage Impedance Voltage : 3.7 %
  • Transformer Type : energy efficient
  • Type Of Cooling : natural convection
  • Electrical Connection : 4 Hole Nema Pad primary 11.1 mm || 4 Hole Nema Pad secondary 11.1 mm || 6 Hole Nema Pad sec - XO 11.1 mm
  • Degree Of Protection : UL type 2 || UL type 3R, with 7400WS21M
  • Maximum Width : 795 mm
  • Percentage Reactance : 2.94 %
  • Product Or Component Type : DOE 2016 energy efficient transformer
  • X/R Ratio : 1.42
  • Inrush Current : 1939 A