Circuit breaker, PowerPacT R, 800A, 3 pole, 600VAC, 50kA, busbar, Micrologic 3.0, 100%

CIRCUIT BREAKER, POWERPACT R,

SQDRLF36080CU31A RLF36080CU31A SQDRLF36080CU31A
0.00 / EA
http://schema.org/OutOfStock
  • Certifications: CSA, NOM, UL
  • Depth: 14.49 in
  • Height: 16.24 in
  • Line Rated Current: 800-800 A
  • Mounting Type: Unit Mount Busbar)
  • Net Weight: 52 lb
  • Standard: CSA, IEC 60947-2, NEMA, NMX J-266, UL
  • Storage Temperature: -50-85 °C
  • Strip Length: 35 mm
  • Warranty Length: 18 mth
  • Width: 16.53 in
PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard Trip with a 3.0 trip unit and an LI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT R circuit breakers are available in 2, 3, and 4-pole unit mount and I-Line construction (I-Line construction is available for 1000A and 1200A rated circuit breakers only). This unit has a busbar connection. This PowerPacT P, 800A, 3 pole, circuit breaker has an interrupting rating of 50kA at 600VAC. The circuit breaker has a continuous current rating of 100%. PowerPacT R circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
QTY
  • Product Description
  • Specifications
PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Standard Trip with a 3.0 trip unit and an LI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT R circuit breakers are available in 2, 3, and 4-pole unit mount and I-Line construction (I-Line construction is available for 1000A and 1200A rated circuit breakers only). This unit has a busbar connection. This PowerPacT P, 800A, 3 pole, circuit breaker has an interrupting rating of 50kA at 600VAC. The circuit breaker has a continuous current rating of 100%. PowerPacT R circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
  • Complementary
    • Circuit Breaker Application : HACR rated
    • Mounting Mode : unit mount busbar)
    • Network Frequency : 50/60 Hz
    • Wire Stripping Length : 35 mm
    • Terminal Identifier : AL2500RK
    • Line Rated Current : 800-800 A
    • Utilisation Category : category A
    • [Ics] Rated Service Breaking Capacity : 65 kA 240 V AC 50/60 Hz IEC 60947-2 || 45 kA 380/415 V AC 50/60 Hz IEC 60947-2
    • Trip Unit Technology : electronic, standard, MicroLogic 3.0, LI
    • Trip Unit Name : MicroLogic 3.0
    • Height : 16.24 in
    • Continuous Current Rating : 100 %
    • Breaking Capacity : AIR 125 kA 240 V AC 50/60 Hz UL 489 || AIR 100 kA 480 V AC 50/60 Hz UL 489 || AIR 50 kA 600 V AC 50/60 Hz UL 489 || Icu 125 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 85 kA 380/415 V AC 50/60 Hz IEC 60947-2
    • [Ui] Rated Insulation Voltage : 750 V IEC 60947-2
    • Suitability For Isolation : yes IEC 60947-2
    • [Ue] Rated Operational Voltage : 600 V AC 50/60 Hz UL 489
    • Tightening Torque : 62-62 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 62-62 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
    • Mounting Support : busbar
    • Breaking Capacity Code : L
    • Poles Description : 3P
    • Local Signalling : alarm 1 LED yellow)long-time pick up)
    • Quantity Per Set : 1
    • Number Of Slots : 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
    • Awg Gauge : AWG 3/0...750 kcmil aluminium/copper
    • Width : 16.53 in
    • Electrical Connection : busbar connection, line || busbar connection, load
    • Depth : 14.49 in
    • Net Weight : 52 lb(US)
    • [Uimp] Rated Impulse Withstand Voltage : 8 kV IEC 60947-2
    • Control Type : operating handle
  • Environment
    • Ambient Air Temperature For Operation : -25-70 °C
    • Pollution Degree : 3 IEC 60947-1
    • Ambient Air Temperature For Storage : -50-85 °C
    • Standards : UL || CSA || NEMA || NMX J-266 || IEC 60947-2
    • Quality Labels : CE
    • Product Certifications : UL || CSA || NOM
    • Operating Altitude : < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
    • Ip Degree Of Protection : IP40
  • Specifications
    • Product Or Component Type : circuit breaker
    • Product Name : PowerPact R
    • Device Application : distribution
    • Range : PowerPact
  • Contractual warranty
    • Warranty : 18 months