Schneider Electric at Mayer

Control relay, TeSys K, 3NO+1NC, 600V, 120V AC 50/60Hz coil

CONTROL RELAY 600VAC 10AMP IEC

SQDCA2KN31G7 CA2KN31G7 3389110787917
59.86 / EA
http://schema.org/OutOfStock
  • Warranty Length: 18 mth
TeSys K IEC industrial control relays are used in industrial control circuits. This Type K control relays has 3 normally open and 1 normally closed contacts. The contacts have AC-15 and DC13 contact ratings. Type K control relays can be mounted on 35mm DIN rail or can be mounted directed to a panel. The relay has a 120 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The relay is 2.28 inches tall, 1.77 inches wide and 2.24 inches deep. It weighs 0.40 lbs. This control relay is UL Listed and CSA certified.
QTY
  • Product Description
  • Features
  • Specifications
TeSys K IEC industrial control relays are used in industrial control circuits. This Type K control relays has 3 normally open and 1 normally closed contacts. The contacts have AC-15 and DC13 contact ratings. Type K control relays can be mounted on 35mm DIN rail or can be mounted directed to a panel. The relay has a 120 VAC 50/60 Hz coil. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The relay is 2.28 inches tall, 1.77 inches wide and 2.24 inches deep. It weighs 0.40 lbs. This control relay is UL Listed and CSA certified.
  • Prop 65
    • WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
  • Conformance Attributes
    • Standards : EN/IEC 60947-5-1, GB/T 14048.5, UL 60947-5-1, CSA C22.2 No 60947-5-1, JIS C8201-5-1
  • Complementary Attributes
    • Control Circuit Voltage Limits : drop-out: 0.2...0.75 Uc (at <50 °C), operational: 0.8...1.15 Uc (at <50 °C)
    • UE Rated Operational Voltage : <= 690 V <= 400 Hz, <= 690 V <= 400 Hz
    • UI Rated Insulation Voltage : 690 V IEC 60947, 750 V VDE 0110 group C, 690 V BS 5424, 600 V CSA C22.2 No 14
    • Control Circuit Type : AC 50/60 Hz
    • IRMS Rated Making Capacity : 110 A IEC 60947
    • Maximum Operating Rate : 10000 cyc/h
    • Minimum Switching Current : 5 mA
    • Minimum Switching Voltage : 17 V
    • UC Control Circuit Voltage : 120 V AC 50/60 Hz
  • Important Information Attributes
    • Persona Type Ids : EU, LC, OM, OM8, PB, SI
    • Persona Type Names : End User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder, System Integrator
    • Market Segmentation Id : COMMERCIAL, INDUSTRIAL
    • Market Segmentation : Commercial, Industrial
    • Associated Fuse Rating : 10 A gG conforming to IEC 60947, 10 A gG conforming to VDE 0660
    • Flame Retardance : V1 conforming to UL 94, requirement 2 conforming to NF F 16-101, requirement 2 conforming to NF F 16-102
    • Mechanical Robustness : vibrations contactor open2 Gn, 5...300 Hz IEC 60068-2-6, vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6, shocks contactor open10 Gn for 11 ms IEC 60068-2-27, shocks contactor closed15 Gn for 11 ms IEC 60068-2-27
    • Operating Time : 10...20 ms coil de-energisation and NO opening, 10...20 ms coil energisation and NO closing, 15...25 ms coil de-energisation and NC closing, 5...15 ms coil energisation and NC opening
    • Tightening Torque : 1.3 N.m screw clamp terminals flat Ø 6 mm, 1.3 N.m screw clamp terminals Philips No 2 6 mm, 1.3 N.m screw clamp terminals pozidriv No 2
    • Carbon Footprint Of The Distribution Phase A4 : 0.0699882448144537, 0.1 kg CO2 eq.
    • Carbon Footprint Of The End Of Life Phase C1 To C4 : 0.2979052988386399, 0.3 kg CO2 eq.
    • Carbon Footprint Of The Installation Phase A5 : 0 kg CO2 eq., 0.010778292366401048
    • Carbon Footprint Of The Manufacturing Phase A1 To A3 : 1 kg CO2 eq., 0.9753347007368284
    • Carbon Footprint Of The Use Phase B2 B3 B4 B6 : 57 kg CO2 eq., 56.65241524409139
    • Connections Terminals : screw clamp terminals 1 1.5-4 mm²solid, screw clamp terminals 2 1.5-4 mm²solid, screw clamp terminals 1 0.75-4 mm²flexible with cable end, screw clamp terminals 2 0.75-4 mm²flexible without cable end, screw clamp terminals 1 0.34-1.5 mm²flexible with cable end, screw clamp terminals 2 0.34-1.5 mm²flexible without cable end
    • Add Ons : LA1KN22, LA1KN40, LA1KN31, LA1KN04, LA1KN13, LA2KT2U
    • Local Data Status : Publishable
    • Local Publishable Date : 2025-12-16
    • HTML Description : Control relay, TeSys K, 3NO+1NC, 600V, 120V AC 50/60Hz coil
    • Manufacturer : Square D
    • Device Type : LV equipment - LV contactor
    • Serviceability : No
    • Traceability : No
    • Legacy WEEE Scope : In
    • Scope Perimeter : At least in Europe
    • EOLI Availability Display : Yes
    • End Of Life Doc Ref : ENVEOLI1503003
    • Reach Full Compliance Status : Free of Substances of Very High Concern above the threshold
    • Reach Full Compliance Status Id : NOT_CONTAINING_SVHC
    • Reach Compliance Directive : Free of Substances of Very High Concern above the threshold
    • ROHS EUR In Scope : Yes
    • ROHS EUR Status : Compliant
    • ROHS EUR Full Compliance Status : Compliant
    • ROHS EUR Full Compliance Status Id : COMPLIANT
    • Green Premium Status For Reporting : Green Premium product
    • With Recycled Cardboard : Yes
    • Without Single Use Plastic : Yes
    • Product Contributes To Saved And Avoided Emissions : No
    • Return Indicator : Y
    • WD Status : 1 - GSC certified
    • Function Option Id : STANDARD
    • Function Option : Standard
    • Compatibility Code : CA2K
    • Contactor Application : control circuit
    • Device Short Name : CA2K
    • Heat Dissipation : 1.3-1.3 W
    • Hold In Power Consumption In VA : 4.5-4.5 VA (at 20 °C)
    • Immunity To Microbreaks : 2 ms
    • Inrush Power In VA : 30-30 VA (at 20 °C)
    • Insulation Resistance : > 10 MOhm
    • Non Overlap Distance : 0.5 mm
    • Package Weight Lbs : 178.000 g
    • Product Availability : Stock - Normally stocked in distribution facility
    • Product Or Component Type : control relay
    • Protective Treatment : TC IEC 60068
    • Range : TeSys
    • Range Of Product : TeSys K control relay
    • Returnability : Yes
    • Sustainable Packaging : Yes
    • Total Lifecycle Carbon Footprint : 58 kg CO2 eq.
    • Weee Label : The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
    • ITH Conventional Free Air Thermal Current : 10 A (at 50 °C)
    • Relationship Type : Compatible relationship
    • Auxiliaries : LA4KE1FC
    • Pep Code : ENVPEP1503003
    • Pep Verification Date : 2025-11-21
    • PCR Version : PEP-PCR-ed4-2021 09 06
    • PSR Version : PSR-0005-ed3-2023 06 06
    • Type Of Verification For The Pep : Independent internal review
    • Functional Unit Description : Establish and cut off the supply of a downstream installation from an electrical and/or mechanical control characterised by the composition of the poles or type of contacts X, a rated voltage of Ue, a rated current Ie, a control circuit voltage Uc, with Np poles, and if applicable the specific specifications, in the Household/Commercial or Industrial application areas, according to the appropriate use scenario, and during the reference service life of the product of 20 years
    • Functional Unit Unit : unit
    • Product Kit Identifier : N
  • Environment Attributes Main
    • EU ROHS Directive : Compliant​, Compliant
    • ROHS Exemption Information : Yes
    • Take Back : No
    • Reach Free SHVC : Yes
    • Recycled Metal Content At Cr Level : 0 %
    • China ROHS Regulation : X
    • Toxic Heavy Metal Free : Yes
    • Mercury Free : Yes
    • Carbon Footprint : 58.00642178084771
    • Circularity Profile : ENVEOLI1503003
    • Environmental Disclosure : ENVPEP1503003
    • IP Degree Of Protection : IP2X
    • Operating Altitude : 6561.68 ft (2000 m) without derating
    • Packaging Made With Recycled Cardboard : Yes
    • Packaging Without Single Use Plastic : Yes
    • Reach Free Of SVHC : Yes
    • Reach Regulation : Free of Substances of Very High Concern above the threshold
    • Pep Code : ENVPEP1503003
    • Pep Verification Date : 2025-11-21
    • PCR Version : PEP-PCR-ed4-2021 09 06
    • PSR Version : PSR-0005-ed3-2023 06 06
    • Type Of Verification For The Pep : Independent internal review
  • General Attributes
    • Product Or Component Type : control relay
    • Range Of Product : TeSys K control relay
  • Contractual Warranty Attributes
    • Warranty Period : 18 months
    • Warranty : 18 months